Background technology
Three-phase ac power system neutral, the i.e. transformer of Y-connection and the neutral point of motor, and the electric connecting mode between the earth, be called Power Network Neutral.Neutral grounding mode relates to security reliability, the economy of electrical network, directly affects the selection of apparatus insulated level, system overvoltage level and the means of relay protection, communication interference etc.
110kV and above electrical network generally adopt big current earthing mode, i.e. neutral point effective grounding mode, and such neutral point potential is fixed as earth potential, and when there is single phase ground fault, healthy phases voltage raises and can not run phase voltage more than 1.4 times; Temporary overvoltage level is also lower; Fault current is very large, and relaying protection can action be in tripping operation rapidly, and excision fault, it is shorter that system equipment bears the overvoltage time.In actual motion, for reducing single-phase-to-ground current, some transformers adopts earth-free mode.
3 ~ 66 kV power distribution networks generally adopt small current neutral grounding mode, isolated neutral or the three-phase system through arc suppression coil and high resistance grounding, when a certain earth fault of generation mutually, due to can not short-circuit loop be formed, earth fault current is often much smaller than load current, i.e. neutral non-effective grounding mode.This mode electrical network allows band single phase ground fault to run in short-term, and power supply quality is better.It is generally acknowledged in China
system belongs to small current neutral grounding system power network, the U.S. and West Europe generally handle
system belong to small current neutral grounding system.
Neutral point small current neutral grounding mode mainly can be divided into following three kinds: earth-free, through grounding through arc and resistance grounded.If regulation 35kV electrical network unbalanced earth fault capacitance current is greater than 10A in China's electric equipment design specification, if 3kV ~ 10kV electrical network earthing capacitance current is greater than 30A, all need to adopt neutral by arc extinction coil grounding mode.Along with the development of supply network, particularly adopt the user of cable line day by day to increase, electric capacity and current with single-phase earthing in system is constantly increased, the possibility causing single phase ground fault in electrical network to develop into accident increases.In order to avoid single phase ground fault expands; power distribution network adopts Neutral Grounding through Resistance in Electrical mode; coordinate relaying protection to excise faulty line fast day by day to increase; " 35kV, 10kV city net; when cable line is longer, system capacitive current is larger, also can adopt resistance mode " is specified in the 59th article, China's " urban power network planning Guidance Rule " (execution).
Neutral Grounding through Resistance in Electrical connects to access resistor between neutral point of electric network with the earth; when there is single phase ground fault, line-to-ground point produces larger zero-sequence current, and zero-sequenceprotection acts on tripping operation; excision faulty line and fault point, quick recovery system normal operating condition.The resistance of suitable selection grounding resistor, the energy of half-wave after single-phase earthing electric arc of can releasing, reduces the possibility of arc reignition, suppresses power network overvoltage, improve the sensitivity of protective relaying device, thus available protecting system is normally run.This earthing mode makes the tripping operation number of times of circuit increase, affect the normal power supply of user, the reliability decrease of customer power supply, but there is stand-by power supply particularly with in the electrical network of cable power supply, the reliability service of whole electrical network can be ensured, apply increasingly extensive, particularly the industrial park of Europe and China.
Neutral resistor grounding system generally adopts the grounding transformer access electrical network of star or zigzag star connection, resistor access grounding transformer neutral point, resistor needs the electric current and voltage bearing earth fault in short-term, should have corresponding capacity and heat dissipation element, resistance box needs specialized designs manufacture.
Summary of the invention
The invention provides a kind of power electronic technology being applicable to 3 ~ 66kV power network, being easy to realization, the advanced method of power network single phase ground fault Quick for the constant current in resistance property of earth point can be realized, substitute existing neutral resistor grounding technology.Can supply earth point current in resistance property by Quick after power network generation single phase ground fault, and keep current constant, thus start relaying protection tripping operation fast, excision faulty line, to reduce arcing time restriction system overvoltage.
The technical scheme that technical solution problem of the present invention is taked is: between the three-phase bus and ground network of the power network of isolated neutral, arrange three-phase four-arm power electronics change of current assembly and corresponding detection components, generation that control assembly is grounded a current in resistance property.
A kind of power network neutral point active pull-up earthing method of the present invention specifically comprises following content: detection components monitoring network voltage curent change; when judging power network generation single phase ground fault; control power electronics change of current assembly to exporting constant current in resistance property between fault phase and ground; earth point current in resistance property is provided; thus make protective relaying device starting tripping; excision faulty line and earth point, substitute neutral grounded transformer and earth resistance.Be equivalent to increase exchanges constant-current source between ground connection phase and ground, constant-current source energy source is in power network.
Compared with prior art the beneficial effect of the inventive method is:
1, play power electronics assembly and adjust feature fast, Quick is for ground connection current in resistance property.
2, by earth point current feedback, make by the electric current of earth point close to constant, constant earth current can make this circuit relay protection sensitivity improve, and ensures relaying protection correct operation.
3, static electric power reliability of electronic equipment is higher, installs simple, easy modularization.
4, reduce the wastage, improve utilization rate of equipment and installations.
Embodiment
Below in conjunction with accompanying drawing, the present invention is further described.
Power network neutral point active pull-up earthing method of the present invention, can be applied in 3 ~ 66kV power network, is used to provide the constant current in resistance property of earth point after single phase ground fault, realizes the function of excision faulty line fast.
Its specific implementation process is:
1. determine active resistance circuit structure
Owing to provide in 3 ~ 66kV power network current in resistance property over the ground to need to produce the zero-sequence current to ground network, and adjustable in the amplitude of electric current, phase place, frequency requirement certain limit.In the inventive method, three-phase four-arm structure power electronics change of current assembly general DC busbar, four brachium pontis outputs connect three-phase bus and ground network respectively, and high frequency wholly-controled device selected by power electronics change of current device.
(1) power electronics change of current assembly
In the present invention, described three-phase four-arm power electronics change of current assembly should select high frequency wholly-controled device.Selectable high frequency wholly-controled device comprises the devices such as IGBT, IGCT, GTO, MOSFET.
As shown in Figure 2, entirely control device IGBT for voltage-type and form change of current assembly, this assembly can produce the electric current of random waveform, and can realize needs power frequency constant current, to compensate the unsteadiness of arc resistance and system voltage.
The capacity of three-phase four-arm power electronics change of current assembly should meet the requirement of ground connection current in resistance property size, generally selects between 10 ~ 1000A, and particular capacity depends on configuration and the sensitivity requirement of relaying protection system.
(2) active pull-up ground connection principle during single-phase earthing
As shown in Figure 3, for A phase circuit metallic earthing, detection components detects that A phase voltage is zero, control assembly sends instruction, control A phase and the inversion of ground connection brachium pontis, the rectification of B, C two-phase brachium pontis runs, and produces A relatively resistive power current, inversion energy takes from electrical network, is supplied to DC bus by B, C two-phase brachium pontis.
As shown in Figure 1, A phase and ground connection brachium pontis can be equivalent to constant-current source, make by the electric current of A phase earth point close to a certain set point.
2. power network state recognition
Operationally, Real-Time Monitoring electrical network three-phase voltage, electric current, judge electric network state according to electric current and voltage change to power network capacitance current active compensation equipment.
When power network normally runs, due to three relatively parameter unbalances, do not replace as three-phase line or replace not exclusively etc., the system three phase-to-ground voltage non-equilibrium state caused can occur with residual voltage simultaneously, and voltage unbalance factor is substantially identical in system.And the unbalance voltage that the uneven reactive current caused by system asymmetric load etc. produces can not occur with residual voltage.
During single phase ground fault, different according to fault point transition resistance, power network neutral point voltage (residual voltage) changes between 0 to phase voltage.
According to above-mentioned electric current and voltage feature, can recognition system status.
3. determine the control procedure of active earth resistance
It is constant that content of the present invention needs to control current in resistance property, and control section needs to increase zero sequence voltage detection and feedback control element, develops new detection control algorithm.
A kind of control program as shown in Figure 4, illustrates active ground connection control principle with A phase ground connection.
Bus-bar potential transformer 1 is connected to system busbar 9, and three-phase brachium pontis 11,12,13 is connected to bus 9, and ground connection brachium pontis 10 connects ground network 0.Definite value input unit 5 can according to zero-sequence current protection definite value setting earth current value.
By the three-phase voltage that voltage transformer 1 provides, grounding of network detection components 2 judges that system is normal, PT breaks or single-phase earthing, automatic resetting when electrical network is normal, artificial involution after PT break alarm.After single-phase earthing being detected, send alarm signal, ground connection phase selection and voltage synthesis unit 4 synthesize Earth Phase voltage U an for inversion earth current provides phase angle, add earth current instrument transformer 8 between ground connection brachium pontis 10 and ground network 0 and detect grounding reverse supply current, definite value input unit 5 sets earth current value, above three kinds of signals by comparator 6 control PWM device 7 export driving pulse control four brachium pontis 10,11,12 and 13 run.Meanwhile, ground connection phase selection and voltage synthesis unit 4 are selected fault phase and are provided phase selection signal, locking B phase brachium pontis 12 and C phase brachium pontis 13 driving pulse, and B phase and C phase brachium pontis form full-bridge rectification, directly provide DC bus power supply from electrical network; Drive A phase brachium pontis 11 and ground connection brachium pontis 10 to form full-bridge inverting, fault point current in resistance property is provided.Add feedback current by comparator 6, overcome fault point earth resistance impact, ensure that earth current is constant, improve zero-sequenceprotection action accuracy.
In Fig. 4, current waveform is desirable compensation power frequency electric capacitance current, with A phase voltage phase place for reference phase.
If other phase ground connection, provide different Earth Phase voltage and phase selection to export by unit 4, different phase brachium pontis output resistance earth currents can be controlled easily.