KR101004733B1 - Floor structure - Google Patents
Floor structure Download PDFInfo
- Publication number
- KR101004733B1 KR101004733B1 KR1020080062655A KR20080062655A KR101004733B1 KR 101004733 B1 KR101004733 B1 KR 101004733B1 KR 1020080062655 A KR1020080062655 A KR 1020080062655A KR 20080062655 A KR20080062655 A KR 20080062655A KR 101004733 B1 KR101004733 B1 KR 101004733B1
- Authority
- KR
- South Korea
- Prior art keywords
- layer
- floor
- wall
- mortar layer
- finishing mortar
- Prior art date
Links
Images
Classifications
-
- E—FIXED CONSTRUCTIONS
- E04—BUILDING
- E04F—FINISHING WORK ON BUILDINGS, e.g. STAIRS, FLOORS
- E04F15/00—Flooring
- E04F15/18—Separately-laid insulating layers; Other additional insulating measures; Floating floors
- E04F15/20—Separately-laid insulating layers; Other additional insulating measures; Floating floors for sound insulation
-
- E—FIXED CONSTRUCTIONS
- E04—BUILDING
- E04F—FINISHING WORK ON BUILDINGS, e.g. STAIRS, FLOORS
- E04F15/00—Flooring
- E04F15/18—Separately-laid insulating layers; Other additional insulating measures; Floating floors
- E04F15/188—Edge insulation strips, e.g. for floor screed layers
-
- E—FIXED CONSTRUCTIONS
- E04—BUILDING
- E04F—FINISHING WORK ON BUILDINGS, e.g. STAIRS, FLOORS
- E04F15/00—Flooring
- E04F15/22—Resiliently-mounted floors, e.g. sprung floors
-
- E—FIXED CONSTRUCTIONS
- E04—BUILDING
- E04F—FINISHING WORK ON BUILDINGS, e.g. STAIRS, FLOORS
- E04F2290/00—Specially adapted covering, lining or flooring elements not otherwise provided for
- E04F2290/04—Specially adapted covering, lining or flooring elements not otherwise provided for for insulation or surface protection, e.g. against noise, impact or fire
- E04F2290/041—Specially adapted covering, lining or flooring elements not otherwise provided for for insulation or surface protection, e.g. against noise, impact or fire against noise
-
- E—FIXED CONSTRUCTIONS
- E04—BUILDING
- E04F—FINISHING WORK ON BUILDINGS, e.g. STAIRS, FLOORS
- E04F2290/00—Specially adapted covering, lining or flooring elements not otherwise provided for
- E04F2290/04—Specially adapted covering, lining or flooring elements not otherwise provided for for insulation or surface protection, e.g. against noise, impact or fire
- E04F2290/044—Specially adapted covering, lining or flooring elements not otherwise provided for for insulation or surface protection, e.g. against noise, impact or fire against impact
Landscapes
- Engineering & Computer Science (AREA)
- Architecture (AREA)
- Civil Engineering (AREA)
- Structural Engineering (AREA)
- Floor Finish (AREA)
- Building Environments (AREA)
Abstract
본 발명은 바닥 슬래브와, 상기 바닥 슬래브의 벽을 이루는 벽체를 갖는 바닥 구조물에 관한 것으로서, 상기 바닥 슬래브 위에 적층되며, 바닥 표면을 형성하는 마감 모르타르층과; 부틸고무, 천연고무, E.P.D.M(Ethylene Propylene Terpolymers) 고무, 경질 우레탄, 연질 우레탄, 에폭시, 석재 및 목재용 본드, 아스팔트 레진, 실리콘, 실란트, 석고, 석회, 콘크리트, 모르타르, 경량기포콘크리트 중 적어도 어느 하나로 이루어지며, 상기 마감 모르타르층의 측벽과 상기 벽체 사이에 일체로 접합되어, 상기 마감 모르타르층에서 발생하는 진동을 저감하는 제진부를 포함하는 것을 특징으로 한다. 이에 의하여, 건축 구조물의 바닥 구조를 형성하는 마감 모르타르층의 판 진동을 제어하여, 상부층에서 발생하는 바닥 충격음이 하부층으로 전달되는 것을 저감할 수 있다.The present invention relates to a floor structure having a floor slab and a wall constituting a wall of the floor slab, comprising: a finishing mortar layer laminated on the floor slab and forming a floor surface; Butyl rubber, natural rubber, EPDM (Ethylene Propylene Terpolymers) rubber, hard urethane, soft urethane, epoxy, stone and wood bond, asphalt resin, silicone, sealant, gypsum, lime, concrete, mortar, lightweight foam concrete It is made, and integrally bonded between the side wall and the wall of the mortar layer, characterized in that it comprises a vibration damping unit for reducing the vibration generated in the finish mortar layer. Thereby, by controlling the plate vibration of the finishing mortar layer forming the floor structure of the building structure, it is possible to reduce the transmission of the floor impact sound generated in the upper layer to the lower layer.
Description
본 발명은, 바닥 구조물에 관한 것으로서, 보다 상세하게는, 바닥을 형성하는 마감 모르타르층의 진동을 제어하도록 구조를 개선한 바닥 구조물에 관한 것이다.The present invention relates to a floor structure, and more particularly, to a floor structure having an improved structure to control the vibration of the finishing mortar layer forming the floor.
아파트와 같은 공동주택 구조물에서 상층으로부터 하층으로 전달되는 소음 및 진동은 언제나 중요한 문제로 제기되는 것이며, 이들 중 가장 큰 문제는 상층의 바닥판에 대한 충격이 하층의 천정을 통해 전달되는 바닥 충격음이라 할 수 있다.Noise and vibration transmitted from the upper floor to the lower floor are always important issues in multi-unit buildings such as apartments, and the biggest problem among them is the floor impact sound transmitted from the ceiling of the lower floor. Can be.
이러한 바닥 충격음은 상층 바닥을 긁는 행위 등에 의해 발생하는 경량충격음(고주파의 소음)과, 상층 바닥 위에서 뛰는 행위 등에 의해 발생하는 중량충격음(저주파의 소음)으로 나누어 볼 수 있다.The floor impact sound may be classified into a light impact sound (high frequency noise) generated by scratching an upper floor and the like, and a heavy impact sound (low frequency noise) generated by running on an upper floor.
공동주택의 바닥 충격음은 중대한 소음 공해의 원인이 되므로, 이를 규제하기 위하여 '공동주택 바닥충격음 차단구조인정 및 관리기준'에서는 그 허용 한도에 관한 규제를 두고 있으며, 경량충격음에 관하여는 한국공업규격 KS F 2863-1에서, 중량충격음에 관하여는 한국공업규격 KS F 2863-2에서 구체적인 사항을 규정하고 있다.Since floor impact sounds of MDUs cause significant noise pollution, in order to regulate them, the regulations for the recognition and management of floor shock sound blocking structure of MDUs have restrictions on their allowable limits, and KS KS In F 2863-1, the details of heavy impact sound are specified in Korean Industrial Standard KS F 2863-2.
종래의 바닥 구조물은 기본적으로 콘크리트 바닥 슬래브의 상부에 경량기포콘크리트층과 마감 모르타르층이 적층되어 온돌과 같은 구조를 취하는데, 경량기포콘크리트층과 마감 모르타르층은 같은 재질로서 하나의 판으로 시공 후 양생이 완료되면 완전한 하나의 판으로 진동 거동하게 된다.Conventional flooring structure is basically a lightweight foam concrete layer and a finishing mortar layer is laminated on the top of the concrete floor slab to take the same structure as the ondol, the lightweight foam concrete layer and the finishing mortar layer is the same material after construction in one plate When the curing is completed, it vibrates into a complete plate.
바닥 충격음의 흡수를 위하여, 바닥 슬래브와 경량기포콘크리트층 사이에 스티로폼, E.V.A(ethylene vinyl acetate) 등의 완충재료에 의한 충격음 완충층이 추가로 형성된다. 이러한 바닥 슬래브와 경량기포콘크리트층과 충격음 완충층은 벽체에 점착제가 점착된 벽면 완충재를 시공하고 있으며, 벽체 방향으로 홈을 두어 공기층을 형성시키는 것도 있다. 또한, 경량충격음 저감을 위해 P.E(poly ethylene)나 E.V.A(ethylene vinyl acetate) 등 동탄성계수가 낮은 제품을 적용하여 벽을 통해 전달되는 충격소음을 저감시키기 위해 벽면 완충재를 설치하고 있는데, 종래의 벽면 완충재의 경우 단순히 완충재로서의 적용하는 것으로서, 바닥 슬래브와 경량기포콘크리트층과 마감 모르타르층이 완전히 분리되어 있기 때문에 경량기포콘크리트층과 마감 모르타르층의 판 진동을 저감시킬 수 없다.In order to absorb the floor impact sound, an impact sound buffer layer made of a buffer material such as styrofoam or E.V.A (ethylene vinyl acetate) is further formed between the floor slab and the lightweight foamed concrete layer. The floor slab, lightweight foam concrete layer, and the impact sound buffer layer are constructed with a wall cushioning material having a pressure-sensitive adhesive adhered to the wall, and some air grooves are formed in the wall direction. In addition, by applying products with low elastic modulus of elasticity such as PE (poly ethylene) or EVA (ethylene vinyl acetate) to reduce light impact sound, wall shock absorbers are installed to reduce shock noise transmitted through walls. In the case of simply applying as a cushioning material, since the floor slab, lightweight foam concrete layer and the finishing mortar layer are completely separated, the plate vibration of the lightweight foam concrete layer and the finishing mortar layer cannot be reduced.
이러한 이유로 중량충격음 저감 성능은 극히 미미한 것이다. 또한, 벽면 완충재의 상부에 마감 모르타르층이 벽체에 직접 닿게 하는 시공 방법도 있으나 미리 양생된 콘크리트 벽체에 신규 이어치기하는 방법으로 이것도 완전한 접합으로 볼 수 없다. 오히려, 벽면 완충재가 두꺼우면 두꺼울수록 벽체와 완전한 분리가 이루어지게 된다. 또한, 강성이 나슬래브와 같이 접합부가 강접합되어 있는 경우 거실의 중앙부에 증폭현상이 발생한다.For this reason, the impact shock reduction performance is extremely minimal. In addition, there is a construction method in which the finishing mortar layer directly touches the wall on the top of the wall cushioning material, but this method cannot be regarded as a complete joining method by newly connecting the previously cured concrete wall. Rather, the thicker the wall cushion, the more complete the separation with the wall. In addition, amplification occurs in the center of the living room when the joint is rigidly bonded, such as slab slab.
이러한 기존의 구조나 재료는 이미 발생한 바닥 충격음의 전달 경로에 완충재료를 시공하여 저감시키는 방법으로서, 고주파의 소음에 대한 흡음 성능은 우수하지만, 저주파 소음에 대하여는 그 성능을 발휘할 수 없다는 점에서 문제로 지적된다.This existing structure or material is a method of reducing the shock absorbing material by constructing a shock absorbing material in the transmission path of the floor impact sound that has already occurred. The sound absorbing performance of the high frequency noise is excellent, but the low frequency noise cannot exhibit its performance. It is pointed out.
즉, 완충재료에 의해 충격음 완충층을 형성하고, 기존의 시공방법인 벽면 완충재(2)와 같은 재질과 시공 방법으로서는, 고주파 소음인 경량충격음의 전달은 저감시킬 수 있지만, 저주파 영역의 중량충격음의 전달에는 거의 영향을 미치지 못한다.That is, the impact sound buffer layer is formed of a buffer material, and the material and construction method of the wall buffer material 2, which is a conventional construction method, can reduce the transmission of the light impact sound, which is a high frequency noise. Has little effect.
따라서, 중량충격음의 저감을 위해서는 바닥 슬래브의 두께를 두껍게 할 수밖에 없다고 할 것이나, 이 경우도 구조물 자중이 증가하므로 효율적인 설계가 이루어질 수 없다는 점, 시공 비용이 증가한다는 점 등의 문제를 야기하므로, 근본적인 해결책이 될 수 없는 것이다.Therefore, in order to reduce the weight impact sound, it is necessary to increase the thickness of the floor slab, but in this case, since the weight of the structure increases, efficient design cannot be achieved and construction cost increases. It cannot be a solution.
상기 배경기술의 문제점에서 해결하고자 하는 과제는, 본 발명에 따라, 건축 구조물의 바닥 구조를 형성하는 마감 모르타르층의 판 진동을 제어하여, 상부층에서 발생하는 바닥 충격음이 하부층으로 전달되는 것을 저감할 수 있는 바닥 구조물을 제공하는 것이다.The problem to be solved in the problem of the background art, according to the present invention, by controlling the vibration of the plate of the finishing mortar layer forming the floor structure of the building structure, it is possible to reduce the transmission of the floor impact sound generated in the upper layer to the lower layer. To provide a floor structure.
상기 과제의 해결 수단은 본 발명에 따라, 바닥 슬래브와, 상기 바닥 슬래브 의 벽을 이루는 벽체를 갖는 바닥 구조물에 있어서, 상기 바닥 슬래브 위에 적층되며, 바닥 표면을 형성하는 마감 모르타르층과; 부틸고무, 천연고무, E.P.D.M(Ethylene Propylene Terpolymers) 고무, 경질 우레탄, 연질 우레탄, 에폭시, 석재 및 목재용 본드, 아스팔트 레진, 실리콘, 실란트, 석고, 석회, 콘크리트, 모르타르, 경량기포콘크리트 중 적어도 어느 하나로 이루어지며, 상기 마감 모르타르층의 측벽과 상기 벽체 사이에 일체로 접합되어, 상기 마감 모르타르층에서 발생하는 진동을 저감하는 제진부를 포함하는 것을 특징으로 하는 바닥 구조물을 제공한다.According to the present invention, there is provided a floor structure having a floor slab and a wall constituting the wall of the floor slab, a layer of mortar laminated on the floor slab, forming a floor surface; Butyl rubber, natural rubber, EPDM (Ethylene Propylene Terpolymers) rubber, hard urethane, soft urethane, epoxy, stone and wood bond, asphalt resin, silicone, sealant, gypsum, lime, concrete, mortar, lightweight foam concrete It is made, and integrally bonded between the side wall of the finishing mortar layer and the wall, to provide a floor structure comprising a vibration damping unit for reducing the vibration generated in the finishing mortar layer.
여기서, 상기 바닥 슬래브와 상기 마감 콘크리트층 사이에 마련되는 경량기포콘크리트층을 더 포함하며, 상기 제진부는 상기 경량기포콘크리트층의 측벽과 상기 벽체 사이에 일체로 접합되어, 상기 경량기포콘크리트층에서 발생하는 진동을 저감하여, 상부층에서 발생하는 진동이 하부층으로 전달되는 것을 저감할 수 있다.Here, further comprising a lightweight foam concrete layer provided between the floor slab and the finishing concrete layer, wherein the vibration damping unit is integrally bonded between the side wall and the wall of the lightweight foam concrete layer, in the lightweight foam concrete layer By reducing the vibration generated, it is possible to reduce the transmission of the vibration generated in the upper layer to the lower layer.
상기 바닥 슬래브와 상기 경량기포콘크리층 사이에 마련되어, 상기 바닥 슬래브와 상기 경량기포콘크리층 사이를 단열하는 단열 완충재를 더 포함할 수 있다.It may further include a heat insulating buffer provided between the bottom slab and the lightweight foam concrete layer, and insulates between the bottom slab and the lightweight foam concrete layer.
또한, 상기 과제의 해결 수단은 본 발명의 다른 실시예로서, 바닥 슬래브와, 상기 바닥 슬래브의 벽을 이루는 벽체를 갖는 바닥 구조물에 있어서, 상기 바닥 슬래브 위에 적층되며, 바닥 표면을 형성하는 마감 모르타르층과; 상기 바닥 슬래브와 상기 벽체 중 적어도 어느 하나 및 상기 마감 모르타르층에 각각 적어도 일부가 매설되어 상기 마감 모르타르층에서 발생하는 진동을 저감하는 제진부를 포함하는 것을 특징으로 하는 바닥 구조물을 제공한다.In addition, a solution to the above problem is another embodiment of the present invention, in the floor structure having a floor slab, and a wall constituting the wall of the floor slab, laminated on the floor slab, the finishing mortar layer to form a floor surface and; At least any one of the floor slab and the wall and at least a portion of each of the finishing mortar layer is embedded in the bottom structure provides a floor structure comprising a vibration damping to reduce the vibration generated in the layer.
상기 바닥 슬래브와 상기 마감 모르타르층 사이에 마련되는 경량기포콘크리트층을 더 포함하며, 상기 바닥 슬래브 및 상기 벽체 중 적어도 어느 하나에 돌출되게 마련된 상기 제진부는 상기 경량기포콘크리트층에 매설되어, 상기 경량기포콘크리트층에서 발생하는 진동을 저감하여, 상부층에서 발생하는 진동이 하부층으로 전달되는 것을 저감할 수 있다.Further comprising a lightweight foamed concrete layer provided between the bottom slab and the finishing mortar layer, wherein the vibration damping portion provided to project at least one of the floor slab and the wall is embedded in the lightweight foamed concrete layer, the lightweight By reducing the vibration generated in the foam concrete layer, it is possible to reduce the transmission of the vibration generated in the upper layer to the lower layer.
상기 바닥 슬래브와 상기 경량기포콘크리트층 사이에 마련되어, 상기 바닥 슬래브와 상기 경량기포콘크리트층 사이를 단열하는 단열 완충재를 더 포함할 수 있다.The insulation may further include a heat insulating buffer provided between the bottom slab and the lightweight foam concrete layer to insulate the floor slab from the lightweight foam concrete layer.
상기 제진부는 핀, 볼트, 파이프, 판재, 패드 중 어느 하나인 것이 바람직하다.It is preferable that the said damping part is any one of a pin, a bolt, a pipe, a board | plate material, and a pad.
그리고, 상기 과제의 해결 수단은 본 발명의 또 다른 실시예로서, 거실 발코니의 창호문틀을 지지하는 문틀 지지층을 갖는 바닥 구조물에 있어서, 실내의 바닥 슬래브 위에 적층되며, 실내 바닥 표면을 형성하는 마감 모르타르층과; 상기 문틀 지지층에 돌출되게 마련되며, 상기 마감 모르타르층에 매설되어 상기 마감 모르타르층에서 발생하는 진동을 저감하는 제진부를 포함하는 것을 특징으로 하는 바닥 구조물을 제공한다.In another aspect of the present invention, there is provided a floor structure having a door frame support layer supporting a window and door frame of a living room balcony, the mortar being laminated on a floor slab in an interior and forming an interior floor surface. A layer; It is provided to protrude in the door frame support layer, it is embedded in the finish mortar layer provides a floor structure comprising a vibration damping unit for reducing the vibration generated in the finish mortar layer.
상기 실내의 바닥 슬래브와 상기 마감 모르타르층 사이에 마련되는 경량기포콘크리트층을 더 포함하며, 상기 문틀 지지층에 돌출되게 마련된 상기 제진부는 상기 경량기포콘크리트층에 매설되어, 상기 경량기포콘크리트층에서 발생하는 진동을 저감하여, 상부층에서 발생하는 진동이 하부층으로 전달되는 것을 저감할 수 있다.Further comprising a lightweight foam concrete layer provided between the indoor floor slab and the finishing mortar layer, wherein the vibration damping portion provided to project to the door frame support layer is embedded in the lightweight foam concrete layer, generated in the lightweight foam concrete layer By reducing the vibration to be transmitted, it is possible to reduce the transmission of the vibration generated in the upper layer to the lower layer.
상기 바닥 슬래브와 상기 경량기포콘크리층 사이에 마련되어, 상기 바닥 슬래브와 상기 경량기포콘크리층 사이를 단열하는 단열 완충재를 더 포함할 수 있다.It may further include a heat insulating buffer provided between the bottom slab and the lightweight foam concrete layer, and insulates between the bottom slab and the lightweight foam concrete layer.
상기 제진부는 핀, 볼트, 파이프, 판재, 패드 중 어느 하나인 것이 바람직하다.It is preferable that the said damping part is any one of a pin, a bolt, a pipe, a board | plate material, and a pad.
따라서, 상기 과제의 해결 수단에 따르면, 건축 구조물의 바닥 구조를 형성하는 마감 모르타르층의 판 진동을 제어하여, 상부층에서 발생하는 바닥 충격음이 하부층으로 전달되는 것을 저감할 수 있다.Therefore, according to the solution of the above problem, by controlling the plate vibration of the finishing mortar layer forming the floor structure of the building structure, it is possible to reduce the transmission of the floor impact sound generated in the upper layer to the lower layer.
이하에서는 첨부도면을 참조하여 본 발명에 대해 상세히 설명한다.Hereinafter, the present invention will be described in detail with reference to the accompanying drawings.
설명에 앞서, 여러 실시예에 있어서, 동일한 구성을 가지는 구성요소에 대해서는 동일 부호를 사용하여 대표적으로 제1실시예에서 설명하고, 그 외의 실시예에서는 제1실시예와 다른 구성에 대해서만 설명하기로 한다.Prior to the description, in various embodiments, components having the same configuration will be representatively described in the first embodiment using the same reference numerals, and in other embodiments, only the configuration different from the first embodiment will be described. do.
도 1은 본 발명의 제1실시예에 따른 바닥 구조물의 종단면도이다.1 is a longitudinal sectional view of a floor structure according to a first embodiment of the present invention.
도면에 도시된 바와 같이, 본 발명의 제1실시예에 따른 바닥 구조물(10a)은, 바닥 슬래브(11)와, 바닥 슬래브(11)의 벽을 이루는 벽체(15)와, 바닥 슬래브(11) 위에 적층되며 바닥 표면을 형성하는 마감 모르타르층(21)과, 마감 모르타르층(21)의 측벽과 벽체(15) 사이에 일체로 접합되어 마감 모르타르층(21)에서 발생하는 진동을 저감하는 제진부(31a)를 가진다.As shown in the drawing, the
바닥 슬래브(11)와 마감모르타르층(21) 사이에는 경량기포콘크리트층(41)이 마련되어 있다.The light weight
또한, 바닥 슬래브(11)와 경량기포콘크리트층(41) 사이에는 바닥 슬래브(11)와 경량기포콘크리트층(41) 사이를 단열하는 단열 완충재(45)가 마련되어 있다.In addition, a
이에, 전체적으로 바닥 슬래브(11) 위에는 단열 완충재(45), 경량기포콘크리트층(41), 마감 모르타르층(21)이 순차적으로 적층되어 있다.Thus, on the
여기서, 마감 모르타르층(21)에는 난방배관(23)이 매입될 수 있다. 또한, 바닥 슬래브(11)와 마감 모르타르층(21) 사이에 마련되는 단열 완충재(45)와 경량기포콘크리트층(41)은 선택적으로 개재될 수 있다.Here, the
한편, 본 발명의 제1실시예에 따른 바닥 구조물(10a)은 제진부(31a)는 마감 모르타르층(21) 및 경량기포콘크리트층(41)의 각 측벽과 벽체(15) 사이에 마련되어 있다.On the other hand, in the floor structure (10a) according to the first embodiment of the present invention, the vibration damping portion (31a) is provided between each side wall and the
제진부(31a)는 부틸고무, 천연고무, E.P.D.M(Ethylene Propylene Terpolymers) 고무, 경질 우레탄, 연질 우레탄, 에폭시, 석재 및 목재용 본드, 아스팔트 레진, 실리콘, 실란트, 석고, 석회, 콘크리트, 모르타르, 경량기포콘크리트 중 적어도 어느 하나로 이루어지며, 마감 모르타르층(21) 및 경량기포콘크리트층(41)의 각 측벽과 벽체(15) 사이에 일체로 접합되어, 즉, 벽체(15)와 경량기포콘크리트층(41)과 마감 모르타르층(21)을 일체화시킨다. 이에, 마감 모르타르층(21) 및 경량기포콘크리트층(41)에서 발생하는 진동을 저감하여, 마감 모르타르층(21)으로부터 바닥 슬래브(11)로 전달되는 바닥 충격음을 저감할 수 있게 된다.The
즉, 단열 완충재(45) 상부의 경량기포콘크리트층(41)과 마감 모르타르층(21) 으로 이루어진 판의 진동을 저감하기 위해 경량기포콘크리트층(41)과 마감 모르타르층(21)의 각 측벽과 벽체(15)를 제진부(31d)로 부착시켜 경량기포콘크리트층(41)과 마감 모르타르층(21)의 판 진동 자체를 원천적으로 발생되기 어렵게 만들어 하부층으로 전달되는 바닥 충격음을 저감시킬 수 있게 된다.That is, in order to reduce vibrations of the plate made of the light weight
여기서, 제진부(31d)는 기존의 벽면 완충재의 형상을 통해 경량기포콘크리트층(41), 마감 모르타르층(21)과 벽체(15)를 일체화되도록 벽면 완충재가 시공되는 부분을 공간으로 비워 두고 마감 모르타르층(21)이 양생된 후에 제진부(31d)의 소재를 충진하여 시공될 수 있다. 이 경우, 경량기포콘크리트층(41)이나 마감 모르타르층(21)이 양생되면서 발생하는 열로 인해 양생이 완료된 후, 제진부(31d)의 소재가 경량기포콘크리트층(41)이나 마감 모르타르층(21) 사이에 스며들어 일체화되는 구조가 바람직하다.Here, the
도 2에는 본 발명의 제2실시예에 따른 바닥 구조물의 종단면도가 도시되어 있다.2 is a longitudinal sectional view of a floor structure according to a second embodiment of the present invention.
본 발명의 제2실시예에 따른 바닥 구조물(10b)은 전술한 제1실시예와는 달리, 제진부(31b)로서 복수의 볼트가 마련되어 있다.Unlike the first embodiment described above, the
제진부(31b)는 바닥 슬래브(11)의 판면을 따라 간격을 두고 배치되며, 제진부(31b)의 일단부는 바닥 슬래브(11)에 지지되고, 타단부는 마감 모르타르층(21)을 향해 돌출되어 있다.The damping
바닥 슬래브(11)의 판면으로부터 돌출된 제진부(31b)의 일 영역은 단열 완충재(45), 경량기포콘크리트층(41), 마감 모르타르층(21)에 매설된다. 특히, 제진 부(31b)의 나사 영역이 경량기포콘크리트층(41), 마감 모르타르층(21)에 밀착하며 매설되어, 제진부(31b)와 경량기포콘크리트층(41)과 마감 모르타르층(21)의 결합력이 증대하여, 바닥 슬래브(11)와 경량기포콘크리트층(41)과 마감 모르타르층(21)을 일체화시켜, 마감 모르타르층(21)으로부터 바닥 슬래브(11)로 전달되는 바닥 충격음을 저감할 수 있게 된다.One region of the
여기서, 제진부(31b)는 볼트 대신에 핀, 파이프, 판재, 패드 중 어느 하나가 적용될 수 있다.Here, the damping
한편, 본 발명의 제2실시예에 따른 바닥 구조물(10b)은 단열 완충재(45), 경량기포콘크리트층(41), 마감 모르타르층(21)의 각 측벽과 벽체(15) 사이에는 벽을 통해 전달되는 충격소음을 저감시키기 위한 벽면 완충재(51)가 마련되어 있다.On the other hand, the floor structure (10b) according to the second embodiment of the present invention is a heat insulating
도 3에는 본 발명의 제3실시예에 따른 바닥 구조물의 종단면도가 도시되어 있다.3 is a longitudinal sectional view of the floor structure according to the third embodiment of the present invention.
본 발명의 제3실시예에 따른 바닥 구조물(10c)은 전술한 제2실시예와는 달리, 제진부(31c)가 방진고무 재질로 이루어진 패드로 이루어져 있다.The
제진부(31c)의 하부는 고정볼트(33)에 의해 바닥 슬래브(11)에 지지되어 있으며, 제진부(31c)의 상부 및 중간부에는 각각 마감 모르타르층(21) 및 경량기포콘크리트층(41)과의 결합력을 증대시키기 위해 복수의 요철(35) 및 함몰된 그루브(37)가 형성되어 있다.The lower part of the
이로써, 제진부(31c)와 경량기포콘크리트층(41)과 마감 모르타르층(21)의 결합력이 증대하여, 바닥 슬래브(11)와 경량기포콘크리트층(41)과 마감 모르타르 층(21)을 일체화시켜, 마감 모르타르층(21)으로부터 바닥 슬래브(11)로 전달되는 바닥 충격음을 저감할 수 있게 된다.As a result, the bonding force between the
도 4에는 본 발명의 제4실시예에 따른 바닥 구조물의 종단면도가 도시되어 있다.4 is a longitudinal sectional view of the floor structure according to the fourth embodiment of the present invention.
본 발명의 제4실시예에 따른 바닥 구조물(10d)은 전술한 실시예들과는 달리, 제진부(31d)로서 방진고무 재질로 이루어진 긴 띠형상의 패드가 마련되어 있다.Unlike the above-described embodiments, the
제진부(31d)는 마감 모르타르층(21) 및 경량기포콘크리트층(41)의 각 측벽과 벽체(15) 사이에 개재되어 있다. 제진부(31d)의 일측은 고정볼트(33)에 의해 벽체(15)에 지지되어 있으며, 제진부(31d)의 타측은 마감 모르타르층(21) 및 경량기포콘크리트층(41)과의 결합력을 증대시키기 위해 요철(35)이 형성되어 있다. 이에, 제진부(31d)에 마감 모르타르 및 경량기포콘크리트가 스며들게 하여 일체화를 향상시켜 판진동의 저감 성능을 향상시킬 수 있게 된다.The
여기서, 제진부(31d)는 패드 대신에 핀, 파이프, 판재, 볼트 중 어느 하나가 적용될 수 있다.Here, the damping
이로써, 제진부(31d)와 경량기포콘크리트층(41)과 마감 모르타르층(21)의 결합력이 증대하여, 벽체(15)와 경량기포콘크리트층(41)과 마감 모르타르층(21)을 일체화시켜, 마감 모르타르층(21)으로부터 바닥 슬래브(11)로 전달되는 바닥 충격음을 저감할 수 있게 된다.As a result, the bonding force between the
도 5에는 본 발명의 제5실시예에 따른 바닥 구조물의 종단면도가 도시되어 있다.5 is a longitudinal sectional view of the floor structure according to the fifth embodiment of the present invention.
본 발명의 제5실시예에 따른 바닥 구조물(10e)은 전술한 실시예들과는 달리, 거실 발코니(5)의 창호문틀(7)을 지지하는 문틀 지지층(13)과, 실내의 바닥 슬래브(11) 위에 적층되며 실내 바닥 표면을 형성하는 마감 모르타르층(21)과, 문틀 지지층(13)에 돌출되게 마련되며 마감 모르타르층(21)에 매설되어 마감 모르타르층(21)에서 발생하는 진동을 저감하는 제진부(31e)를 가진다.Unlike the above-described embodiments, the
실내 바닥 슬래브(11)와 마감 모르타르층(21) 사이에는 경량기포콘크리트층(41)이 마련되어 있다.The lightweight
또한, 실내 바닥 슬래브(11)와 경량기포콘크리트층(41) 사이에는 바닥 슬래브(11)와 경량기포콘크리트층(41) 사이를 단열하는 단열 완충재(45)가 마련되어 있다.In addition, an
이에, 전체적으로 실내 바닥 슬래브(11) 위에는 단열 완충재(45), 경량기포콘크리트층(41), 마감 모르타르층(21)이 순차적으로 적층되어 있다.Thus, on the
여기서, 도시되어 있지 않지만, 마감 모르타르층(21)에는 난방배관(23)이 매입될 수 있다. 또한, 실내 바닥 슬래브(11)와 마감 모르타르층(21) 사이에 마련되는 단열 완충재(45)와 경량기포콘크리트층(41)은 선택적으로 개재될 수 있다.Here, although not shown, a
한편, 본 발명의 제5실시예에 따른 바닥 구조물(10e)은 제진부(31e)로서 복수의 볼트가 마련되어 있다.On the other hand, the floor structure (10e) according to the fifth embodiment of the present invention is provided with a plurality of bolts as the vibration damping portion (31e).
제진부(31e)는 문틀 지지층(13)의 판면을 따라 간격을 두고 배치되며, 제진부(31e)의 일단부는 문틀 지지층(13)에 지지되고, 타단부는 마감 모르타르층(21) 및 경량기포콘크리트층(41)을 향해 돌출되어 있다.The
문틀 지지층(13)의 판면으로부터 돌출된 제진부(31e)의 일 영역은 마감 모르타르층(21) 및 경량기포콘크리트층(41)에 매설된다. 특히, 제진부(31e)의 나사 영역이 마감 모르타르층(21) 및 경량기포콘크리트층(41)에 밀착하며 매설되어, 제진부(31e)와 마감 모르타르층(21)과 경량기포콘크리트층(41)의 결합력이 증대하여, 벽체(15)와 마감 모르타르층(21)과 경량기포콘크리트층(41)을 일체화시켜, 마감 모르타르층(21)으로부터 실내 바닥 슬래브(11)로 전달되는 바닥 충격음을 저감할 수 있게 된다.One region of the
여기서, 제진부(31e)는 볼트 대신에 핀, 파이프, 판재, 패드 중 어느 하나가 적용될 수 있다.Here, the damping
전술한 실시예들에 기재된 바와 같이, 본 발명에 따른 바닥 구조물은 기본적으로, 일 실시예로서 도 6에 도시된 타격 및 측정 포인트 A,B,C,D의 하부와, 벽이 꺾이는 부분과, 판 진동이 가장 많이 발생하는 발코니와 거실이 이어지는 창틀 하부에 시공하는 것이 바람직하다.As described in the above-described embodiments, the floor structure according to the present invention basically includes, as an embodiment, the lower part of the hitting and measuring points A, B, C, and D shown in FIG. It is desirable to install under the window frame where the balcony and living room where plate vibration occurs most frequently.
판 진동은 강성이 약한 부분으로 흘러가는 습성을 가지고 있으므로 이러한 강성이 약한 부분에서 중량 바닥 충격음이 증폭하는 경향을 가진다. 판 진동의 세기는 거실과 발코니가 연결되는 부분이 강성이 약하므로 진동은 가장 강하게 나타난다. 이러한 이유로 바닥 충격음을 측정하면 발코니 쪽 부분의 증폭량이 중앙부 보다 피크(PEAK)값이 19dB 이상 높게 나타나는 경우도 많다. 바닥 충격음의 측정은 아래의 〔식1〕에 의해 피크(PEAK)값을 에너지 평균하기 때문에 이러한 피크(PEAK)값은 바닥 충격음 특히 중량충격음에 직접적으로 영향을 미친다.The plate vibration tends to amplify the heavy floor impact sound in the weak stiffness because it has the habit of flowing to the weak stiffness. The strength of the plate vibration is the strongest because the area connecting the living room and the balcony is weak. For this reason, when the floor impact sound is measured, the peak of the balcony is often 19 dB higher than the peak. Since the measurement of the floor impact sound energy averages the peak value by the following [Equation 1], the peak value directly affects the floor impact sound, especially the heavy impact sound.
〔식1〕[Equation 1]
중량충격음은 특히 63Hz 대역에 의해 좌우되는 경우가 많은데 이러한 63Hz 대역은 50Hz 대역을 포함하는 개념이고, 상부의 판 진동은 50Hz 대역에서 피크(PEAK)값을 나타낸다. The heavy shock sound is often influenced by the 63Hz band. The 63Hz band is a concept including the 50Hz band, and the upper plate vibration shows a peak value in the 50Hz band.
이하에서는 본 발명이 제시하는 구조를 취함에 따라 마감 모르타르층으로부터 바닥 슬래브로 전달되는 바닥 충격음이 저감되는지 여부를 입증하기 위한 실험내용 및 실험결과에 대하여 설명하기로 한다.Hereinafter, the experimental content and experimental results for demonstrating whether the floor impact sound transmitted from the finishing mortar layer to the floor slab is reduced according to the present invention will be described.
기본적으로 바닥 충격음 측정은 뱅머신과 태핑머신을 이용하여 한국공업규격 KS F 2810-1, 2에 의해 현장에서 실시하였으며, 비교 측정을 위해 나슬래브 상태 즉, 콘크리트 슬래브와 벽체로만 이루어진 상태로 단열 완충재와 경량기콘크리트층과 마감 모르타르층이 시공되지 않은 상태에서 미리 측정하여 결과값을 확보한 다음, 기존의 방법과 동일한 방법으로 시공하여 측정한 것 1세대와 본 발명을 통해 시공된 2개 구조를 총 3개 세대를 측정하여 비교 평가하였다.Basically, the floor impact sound measurement was conducted on-site by Korean Industrial Standard KS F 2810-1, 2 using bang machine and tapping machine.Insulation buffer material is made of naslab state, namely concrete slab and wall only for comparative measurement. And the light weight concrete layer and the finishing mortar layer were measured in advance without the result of securing the result value, and then measured and constructed by the same method as the existing method of the first generation and the two structures constructed through the present invention A total of three generations were measured and compared.
현장은 바닥 슬래브 두께가 180mm인 현장으로서 103동 302호 402호, 502호 3개 세대를 비교 측정하였다. 단열 완충재는 3세대 모두 동탄성계수가 5MN/㎥ 전후의 것을 동일하게 적용하였다. 성능 평가시 분석 장비와 마이크로폰 모두 일본 RION社 장비를 사용하였으며 1/3 옥타브밴드로 측정하였다. 시공은 아래 표와 같은 방법으로 실시하였다. 측정 시에 창호와 문 입구는 스치로폼 등으로 밀폐시켰고, 거실 창호는 설치된 상태였다. 또한, 천정은 없는 구조였으며, 마감재는 시공되지 않은 상태로 측정하였다.The site was a floor slab with a thickness of 180mm and measured three generations of 103-302, 402 and 502. As for the thermal insulation buffer, the same elastic modulus of 5MN / m 3 was applied to all three generations. For performance evaluation, both the analytical instrument and the microphone used Japanese RION equipment and measured with 1/3 octave band. Construction was carried out in the same manner as the table below. At the time of measurement, the window and the door entrance were sealed with styrofoam etc., and the living room window was installed. In addition, there was no ceiling structure, the finish was measured without construction.
나슬래브 상태의 측정값은 아래 〔표1〕,〔표2〕,〔표3〕과 같다.The measured values of the screw slab state are shown in the following [Table 1], [Table 2], and [Table 3].
〔표1〕103동 302호 나슬래브Table 1 Building No. 302 Naslab
〔표2〕103동 402호 나슬래브Table 2 Building No. 402 Naslab
〔표3〕103동 502호 나슬래브Table 3 Building No. 502 Naslab
단일수치로는 중량충격음이 103동 302호가 50dB이었고, 103동 402호는 49dB, 103동 502호 50dB로 슬래브 180 현장으로서는 상당히 양호한 결과를 나타내었다. 또한, 63Hz에 영향을 미치는 50Hz의 경우 중앙부(Excite3) 타격시 하부층의 증폭은 중앙에서 일어난다는 것을 알 수 있다. 즉, 마감 모르타르층이 시공되기 전에는 중앙부가 강성이 가장 약한 부위가 되는데 그 이유는 나슬래브 상태에서는 벽체로 인해 슬래브가 고정되어 있기 때문에 벽체로 고정된 부분이 강성이 되어 중앙부분이 가장 약한 강성을 나타내게 된다. 이러한 나슬래브의 성능에도 불구하고 완충층을 추가하면 대부분이 나슬래브 상태의 충격음보다 높게 나타나는 것이 일반적이다. 중량 충격음 성능이 103동 302호, 402호, 502호가 각각 46dB, 46dB, 54dB로 나타났다.As a single value, the weight impact sound was 50dB in 103-302 and 49dB in 103-402, 50dB in 103-502, which was quite good for the slab 180 site. In addition, in the case of 50 Hz, which affects 63 Hz, it can be seen that the amplification of the lower layer occurs at the center when the center portion (Excite3) is hit. That is, before the finishing mortar layer is constructed, the central part becomes the weakest part of the stiffness because the slab is fixed by the wall in the naslab state, so the part fixed by the wall becomes stiff and the center part is the weakest stiffness. Will be displayed. In spite of the performance of such a slab, the addition of a buffer layer is generally higher than the impact sound of the slab state. The weight impact sound performances of 103-302, 402, and 502 were 46dB, 46dB, and 54dB, respectively.
〔표4〕103동 302호 시공후 측정값[Table 4] Measured value after construction of Building 103
〔그래프1〕103동 302호 시공 전과 후의 측정값 비교[Graph 1] Comparison of measured values before and after construction of Building 103, Room 302
나슬래브와 비교해서 본 발명품을 적용한 103동 302호, 402호가 각각 4dB, 3dB 저감된 반면에 기존의 구조로 시공된 103동 502호는 오히려 4dB 증폭하는 경향을 보여주고 있다. 여기서, 주목할 점은 63Hz∼125Hz 대역에서만 성능의 차이가 클 뿐 다른 주파수 대역에서는 거의 유사한 결과를 나타낸다는 것이다. 63Hz 대역은 보통의 사람은 인지하지 못하는 주파수 대역으로서 주로 진동에 의해 전달되며, 기 계로만 측정되는 주파수 대역이다. 이러한 결과는 마감 모르타르층의 판 진동으로 인해 1차 진동 모드가 벽체에 부딪혀 사라지기 전에 2차 진동모드와 중첩되는 현상, 즉 공진이 발생하게 되는데 이러한 공진의 원인이 마감 모르타르층의 판 진동으로 인한 것이다. 본 발명품은 이러한 판진동을 원천적으로 발생을 억제시키기 위한 것이다. 특히 63Hz 대역의 저감은 현재의 완충재로 현장에서 성능을 발휘한다는 것은 현재의 벽식 구조에서는 거의 불가능에 가깝다는 것이 대부분의 공통된 의견이지만 본 발명품은 기술의 발전과 공법의 발전에 따라 전혀 새로운 개념의 바닥 충격음 저감 구조물인 것이다.Compared to naslab, 103-302 and 402, which applied the present invention, were reduced by 4dB and 3dB, respectively, while 103-502, which was constructed with the existing structure, tended to amplify 4dB. It should be noted that the difference in performance is large only in the 63 Hz to 125 Hz band, but shows similar results in other frequency bands. The 63 Hz band is a frequency band that is not recognized by the average person and is mainly transmitted by vibration and is a frequency band measured only by a machine. This resulted in the phenomenon that the first vibration mode overlaps with the second vibration mode before the disappearance due to the plate vibration of the finishing mortar layer, that is, the resonance occurs. This resonance is caused by the plate vibration of the finishing mortar layer. will be. The present invention is intended to suppress the generation of such plate vibration inherently. In particular, it is the common opinion that the reduction of the 63Hz band is almost impossible in the current wall structure to perform performance in the field as the current buffer material, but the present invention is based on a completely new concept according to the development of technology and the development of the method. It is an impact sound reduction structure.
실제 실험실에서 측정한 결과 값은 거의 직사각형의 단판이므로 마감 모르타르층의 강성이 약한 부분과 강한 부분이 없고 거의 유사하기 때문에 단열 완충재의 동탄성계수에 따라 성능이 거의 유사한 패턴을 보인다. 즉, 동탄성계수가 낮으면 낮을수록 바닥 충격음 성능이 향상되는 패턴을 보이는 것이다. 하지만, 현장에 적용할 경우 실제 성능이 크게 달라지는 것은 현장 구조상 마감 모르타르층의 강성이 다르기 때문에 판진동이 강성이 약한 부분이 증폭하기 때문에 실제 성능을 구현하기 어려운 것이다. 실제 본 측정 결과에서도 거실의 발코니쪽 수음 포인트가 중앙부에 비해 19dB이상 증폭하는 현상이 발생하였다. 거실의 발코니쪽(30, 40)이 강성이 약한 부분이 되기 때문이다. 현장 시공에 있어서 발명의 적용은 도 6의 굵은 실선으로 표기한 부분에 시공하였으며 제진재는 두께 5mmm와 폭 100mm의 부틸 고무로 제작하여 각 부위마다 1m씩 적용하였다. 마감 모르타르층과 경량기포콘크리트층의 강성 결정은 판 자체의 형상과 벽체와의 접합에 의해 결정된다. 특정한 형상을 가 지는 부분이 강성축이 되며, 벽체와의 접합된 곳이 강성이 되는 것이다.Since the actual laboratory measurements are almost rectangular single-plates, the stiffness of the finished mortar layer is similar to that of the weak and strong parts, which is almost the same, and shows a similar pattern according to the dynamic modulus of the insulating buffer. That is, the lower the dynamic modulus of elasticity, the lower the impact sound performance of the floor. However, if the actual performance is greatly changed when applied to the field, it is difficult to realize the actual performance because the stiffness of the plate vibration is weakened because the rigidity of the finishing mortar layer is different due to the structure of the site. In fact, this measurement resulted in amplification of 19dB more than the center of the living room's balcony. This is because the balcony side (30, 40) of the living room is a weak portion. Application of the invention in the field construction was applied to the portion indicated by the thick solid line of Figure 6, the vibration damping material was made of butyl rubber of 5mm thickness and 100mm width was applied by 1m for each site. The stiffness of the finishing mortar layer and the lightweight foam concrete layer is determined by the shape of the plate itself and the joining of the wall. The part with a certain shape becomes the rigid shaft, and the joint with the wall becomes the rigid shaft.
마감 모르타르층의 중앙부에서 발생한 진동은 벽체가 시공되지 않는 발코니 부분으로 흐르기 때문에 각각의 부분에 시공하는 것이 바람직하다.Since the vibration generated in the central part of the finishing mortar layer flows to the part of the balcony where the wall is not constructed, it is preferable to apply to each part.
이하, 상술한 바와 같은 제진재를 시공하는 방법에 관한 구체적인 실시예에 관하여 설명한다.Hereinafter, specific examples of the method for constructing the vibration damper as described above will be described.
첫째, 도 5에서 단열 완충재를 시공하기 전에 제진재를 벽체나 거실과 발코니가 연결되는 창호 아래(PL 창호 하부)에 일부 또는 전체를 시공하는 것이 바람직하다.First, before constructing the insulating buffer in FIG. 5, it is preferable to install the vibration damping material under part or the whole of the window (below the PL window) to which the wall or living room and the balcony are connected.
둘째, 도 1에 도시된 바와 같이, 벽체에 적용되는 제진재는 벽체와 마감 모르타르층과 경량기포콘크리트층이 접착이 잘되는 재료이어야 하며, 제진 성능과 마감 모르타르층, 경량기포콘크리트층의 진동을 억제할 수 있는 재료이어야 한다. 이러한 진동은 제진이나 강성을 통해 확보할 수도 있다. 여기서, 벽체에 적용되는 제진재의 두께는 1∼20mm인 것이 바람직하다.Second, as shown in Figure 1, the vibration damping material applied to the wall should be a material that the wall and the finishing mortar layer and lightweight foam concrete layer is well adhered, and suppress the vibration of the vibration damping performance and the finishing mortar layer, lightweight foam concrete layer It must be a material that can be used. Such vibration can also be ensured through damping or stiffness. Here, it is preferable that the thickness of the damping material applied to a wall is 1-20 mm.
셋째, 도 1에 도시된 바와 같이, 벽체에 적용되는 제진재는 마감 모르타르층의 강성이 약한 부분, 예를 들면, 벽체가 꺾이거나 끊어지는 부분, 마감 모르타르층 및 경량콘크리트층의 각 측벽과 벽체가 닿지 않은 부분 등을 중심으로 시공하는 것이 바람직하며, 일부만 마감 모르타르층 및 경량콘크리트층의 각 측벽과 벽체 사이에 기존의 벽면완충재를 시공하고 나머지 부분을 제진재로 시공하여도 그 성능은 확보되나 전체를 시공하게 되면 중량충격음 저감 성능은 더 많아진다.Third, as shown in Figure 1, the vibration damping material applied to the wall is a weak part of the finishing mortar layer, for example, the part where the wall is bent or broken, the finishing mortar layer and the light concrete layer each side wall and wall It is preferable to construct the parts that are not in contact with each other, and only part of the finishing mortar layer and the light concrete layer may be constructed between the existing wall buffers and the remaining parts as vibration dampers. The whole construction increases the weight impact sound reduction performance.
넷째, 도 4에 도시된 바와 같이 벽체로부터 제진재를 돌출하여 마감 모르타 르층, 경량기포콘크리트층에 묻혀 고정시키는 것도 유효하다.Fourth, as shown in Figure 4 it is also effective to protrude the vibration damping material from the wall buried in the finishing mortar layer, lightweight foam concrete layer and fixed.
다섯째, 마감 모르타르층의 강성이 약한 부분, 즉 도 6에서 타격 및 측정 포인트 A,B 영역과 같은 부위 하부에 도 2에 도시된 바와 같이 제진재를 시공하여 마감 모르타르층 및 경량기포콘크리트층과 일체화시키는 것도 바람직하다. Fifth, integrating the finishing mortar layer and the light-foamed concrete layer by applying a vibration damping material as shown in FIG. 2 under the stiffness part of the finishing mortar layer, that is, the lower part such as the hitting and measuring point A and B areas in FIG. It is also preferable to make it.
여섯째, 마감몰 모르타르층의 강성이 약한 부분 즉, 도 6에서 타격 및 측정 포인트 A,B,C,D 영역과 같은 부위 하부에 도 3에 도시된 바와 같이 방진고무로 이루어진 패드를 일정 부분 시공하는 것이 바람직하다.Sixth, the pads made of the anti-vibration rubber, as shown in Figure 3 in the lower portion of the stiffness of the finishing mortar layer, that is, the impact and measurement points A, B, C, D region in Figure 6 It is preferable.
일곱째, 종래의 벽면 완충재 부분에 공간을 두어 마감 모르타르층이 양생된 후 충진하는 방법과 종래의 벽면 완충재를 제거하고 충진하는 것도 유효하다.Seventh, it is also effective to leave a space in a portion of the conventional wall cushioning material to fill the finishing mortar layer after curing, and to remove and fill the conventional wall cushioning material.
여덟째, 부엌을 포함한 거실의 스팬비(경간비)가 크면 클수록 효과적이다.Eighth, the larger the span ratio (span ratio) of the living room, including the kitchen, the more effective.
아홉째, 단열 완충재의 동탄성계수는 낮으면 낮을수록 효과적이다. 이러한 이유는 동탄성계수가 높은 재료의 경우 마감 모르타르층의 판진동이 강성이 약한 부분으로 흐르기 전에 단열 완충재를 통해 하부층으로 진동과 소음을 전달시켜 버리기 때문이다. 따라서, 바람직한 동탄성계수는 10MN/㎥이하의 단열 완충재를 적용하는 것이 바람직하다.Ninth, the lower the dynamic modulus of elasticity of the heat insulating buffer, the more effective it is. This is because, for materials with high modulus of elasticity, plate vibration of the finishing mortar layer transmits vibration and noise to the lower layer through the thermal insulation buffer before flowing to the weaker part. Therefore, it is preferable to apply the heat insulating buffer material of 10 MN / m <3> or less as preferable dynamic elastic modulus.
열번째, 기존의 벽면 완충재의 두께는 1∼30mm 범위 내에서 두꺼우면 두꺼울수록 좋으며, 본 발명품인 벽면재진재료의 두께는 1∼20mm인 것이 바람직하다.Tenth, the thickness of the existing wall cushioning material is as thick as the thickness within the range of 1 to 30mm, the better, and the thickness of the wall jamming material of the present invention is preferably 1 to 20mm.
이와 같이, 본 발명은 기존 구조물에 하중의 증가, 시공 비용의 증가를 방지하였고 경제성을 확보하였을 뿐만 아니라, 마감 모르타르층 및 경량기포콘크리트층의 판진동을 효율적으로 저감시켜 중량 바닥 충격음을 획기적으로 저감시킬 수 있 으며 실험실 성능과 유사한 성능을 현장에서 발현하도록 것으로서 기존 바닥 구조물과는 전혀 다르다. 또한, 실험실 측정 후 현장 측정 시에 평균 오차가 2등급(6dB) 정도의 레벨을 보이고 있어 실제 실험실 측정값의 신뢰성에 많은 문제가 있었다. 이러한 문제는 실험실과는 전혀 다른 현장의 구조에 기인한 것이다. 따라서 본 발명은 현장에서 바닥 충격음 성능을 획기적으로 향상시킬 수 있게 된다.As such, the present invention prevents the increase of load and construction cost of the existing structure and secures economic feasibility, and effectively reduces the plate vibration of the finishing mortar layer and the lightweight foam concrete layer, thereby significantly reducing the weight floor impact sound. It is possible to produce on-site performance similar to laboratory performance, which is completely different from existing floor structures. In addition, since the average error is about 2 level (6dB) level in the field measurement after the laboratory measurement, there were many problems in the reliability of the actual laboratory measurement value. This problem is due to the site structure being completely different from the laboratory. Therefore, the present invention can significantly improve the floor impact sound performance in the field.
따라서, 본 발명에 따르면, 건축 구조물의 바닥 구조를 형성하는 마감 모르타르층의 판 진동을 제어하여, 상부층에서 발생하는 바닥 충격음이 하부층으로 전달되는 것을 저감할 수 있게 된다.Therefore, according to the present invention, by controlling the vibration of the plate of the finishing mortar layer forming the floor structure of the building structure, it is possible to reduce the transmission of the floor impact sound generated in the upper layer to the lower layer.
본 발명은 기재된 실시예에 한정되는 것이 아니고, 본 발명의 사상 및 범위를 벗어나지 않고 다양하게 수정 및 변형할 수 있음은 이 기술의 분야에서 통상의 지식을 가진 자에게 자명하다. 따라서, 그러한 수정 예 또는 변형 예들은 본 발명의 특허청구범위에 속한다 하여야 할 것이다.It is apparent to those skilled in the art that the present invention is not limited to the described embodiments, and that various modifications and changes can be made without departing from the spirit and scope of the present invention. Therefore, such modifications or variations will have to be belong to the claims of the present invention.
도 1은 본 발명의 제1실시예에 따른 바닥 구조물의 단면도,1 is a cross-sectional view of the floor structure according to the first embodiment of the present invention,
도 2는 본 발명의 제2실시예에 따른 바닥 구조물의 단면도,2 is a cross-sectional view of the floor structure according to the second embodiment of the present invention,
도 3은 본 발명의 제3실시예에 따른 바닥 구조물의 단면도,3 is a cross-sectional view of the floor structure according to the third embodiment of the present invention,
도 4는 본 발명의 제4실시예에 따른 바닥 구조물의 단면도,4 is a cross-sectional view of the floor structure according to the fourth embodiment of the present invention;
도 5는 본 발명의 제5실시예에 따른 바닥 구조물의 단면도,5 is a cross-sectional view of the floor structure according to the fifth embodiment of the present invention;
도 6은 본 발명의 바닥 구조물이 적용된 일 실시예에 따른 평면도이다.6 is a plan view according to an embodiment to which the floor structure of the present invention is applied.
* 도면의 주요 부분에 대한 부호의 설명 *Explanation of symbols on the main parts of the drawings
10a,10b,10c,10d,10e : 바닥 구조물 11 : 바닥 슬래브10a, 10b, 10c, 10d, 10e: floor structure 11: floor slab
13 : 문틀 지지층 15 : 벽체13: door frame support layer 15: wall
21 : 마감 모르타르층 23 : 난방배관21: finishing mortar layer 23: heating piping
31a,31b,31c,31d,31e : 제진부 41 : 경량기포콘크리트층31a, 31b, 31c, 31d, 31e: vibration suppressing part 41: lightweight foam concrete layer
45 : 단열 완충재 51 : 벽면 완충재45: insulation buffer 51: wall buffer
Claims (13)
Priority Applications (1)
Application Number | Priority Date | Filing Date | Title |
---|---|---|---|
KR1020080062655A KR101004733B1 (en) | 2008-06-30 | 2008-06-30 | Floor structure |
Applications Claiming Priority (1)
Application Number | Priority Date | Filing Date | Title |
---|---|---|---|
KR1020080062655A KR101004733B1 (en) | 2008-06-30 | 2008-06-30 | Floor structure |
Publications (2)
Publication Number | Publication Date |
---|---|
KR20100002678A KR20100002678A (en) | 2010-01-07 |
KR101004733B1 true KR101004733B1 (en) | 2011-01-04 |
Family
ID=41812682
Family Applications (1)
Application Number | Title | Priority Date | Filing Date |
---|---|---|---|
KR1020080062655A KR101004733B1 (en) | 2008-06-30 | 2008-06-30 | Floor structure |
Country Status (1)
Country | Link |
---|---|
KR (1) | KR101004733B1 (en) |
Cited By (1)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
KR101639319B1 (en) | 2015-02-06 | 2016-07-13 | 한국건설기술연구원 | Vibration Isolator Capable of Reducing the Transmission of Vibration of the Vertical Member and Floor Vibration Isolation System Using the Same |
Families Citing this family (1)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
KR102380357B1 (en) * | 2021-05-24 | 2022-03-29 | 노환근 | Double floor structure system to reduce inter-floor noise with vibration control anchor bolts |
Citations (5)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
KR20030078667A (en) * | 2002-03-29 | 2003-10-08 | 인터내셔널 비지네스 머신즈 코포레이션 | Inspection Method and Apparatus for EL Array Substrate |
KR100429103B1 (en) | 2001-08-06 | 2004-04-29 | 주식회사 한진중공업 | Floating floor structure for reducing floor shock sound and floor materials for building |
KR200378667Y1 (en) * | 2004-12-13 | 2005-03-16 | (주)삼세대시공 | Floor structure of apartment for decrease a heavyweight vibration |
KR200399631Y1 (en) * | 2005-07-29 | 2005-10-27 | 조준일 | Storey structure of floor for building |
KR100741634B1 (en) | 2006-11-01 | 2007-07-23 | 주식회사 한진중공업 | Slab structure for reduction of crashing sound |
-
2008
- 2008-06-30 KR KR1020080062655A patent/KR101004733B1/en active IP Right Grant
Patent Citations (5)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
KR100429103B1 (en) | 2001-08-06 | 2004-04-29 | 주식회사 한진중공업 | Floating floor structure for reducing floor shock sound and floor materials for building |
KR20030078667A (en) * | 2002-03-29 | 2003-10-08 | 인터내셔널 비지네스 머신즈 코포레이션 | Inspection Method and Apparatus for EL Array Substrate |
KR200378667Y1 (en) * | 2004-12-13 | 2005-03-16 | (주)삼세대시공 | Floor structure of apartment for decrease a heavyweight vibration |
KR200399631Y1 (en) * | 2005-07-29 | 2005-10-27 | 조준일 | Storey structure of floor for building |
KR100741634B1 (en) | 2006-11-01 | 2007-07-23 | 주식회사 한진중공업 | Slab structure for reduction of crashing sound |
Cited By (1)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
KR101639319B1 (en) | 2015-02-06 | 2016-07-13 | 한국건설기술연구원 | Vibration Isolator Capable of Reducing the Transmission of Vibration of the Vertical Member and Floor Vibration Isolation System Using the Same |
Also Published As
Publication number | Publication date |
---|---|
KR20100002678A (en) | 2010-01-07 |
Similar Documents
Publication | Publication Date | Title |
---|---|---|
KR20120007999A (en) | Complex floor structure for damping and isolation of floor impact sound | |
KR101269110B1 (en) | A method for manufacturing and execution of works with a panel for absorbing and cutting off impact noise | |
KR100783117B1 (en) | A product for reducing noise in architecture | |
KR101004733B1 (en) | Floor structure | |
KR100827424B1 (en) | Ondol floor structure for reducing noise between floors of apartment house and construction method thereof | |
KR200419673Y1 (en) | Dual Floor Panel Support for Reducing Noise Transfer between Floors | |
KR100429103B1 (en) | Floating floor structure for reducing floor shock sound and floor materials for building | |
KR102119407B1 (en) | Vibration dampener for reduction of crashing sound | |
JP4413344B2 (en) | Soundproof floor structure | |
KR100473834B1 (en) | Floating structure and method of carrying out construction with thereof | |
KR100611184B1 (en) | Separate/dual floor structure for reducing noise of wall-type apartment and method of construction such floor structure | |
KR101269113B1 (en) | A method for manufacturing with a panel for absorbing and cutting off impact noise | |
KR102235014B1 (en) | Cushioning-material for reducing noise between stories | |
KR101183908B1 (en) | Reduce noise floors and structure reduce noise between floors of building | |
KR100827426B1 (en) | Ondol floor structure for reducing noise between floors of apartment house and construction method thereof | |
KR100790468B1 (en) | A vibration damping board | |
KR200423550Y1 (en) | Isolating structure for floor impact sound of the apartment building | |
KR200392801Y1 (en) | Hypocaust Structure Using Damping Materials | |
KR100778659B1 (en) | Sound and dust proofing bottom parts for building | |
KR100740981B1 (en) | Hypocaust Structure Using Damping and insulating Materials | |
KR100739878B1 (en) | Slab structure for a building | |
KR100641873B1 (en) | Structure of isolating a crashing sound of floor of a building | |
JPH0355705Y2 (en) | ||
KR100462552B1 (en) | Floating floor structure for reducing floor shock sound | |
KR20190131675A (en) | Floor structure for reducing impact noise |
Legal Events
Date | Code | Title | Description |
---|---|---|---|
A201 | Request for examination | ||
E902 | Notification of reason for refusal | ||
E701 | Decision to grant or registration of patent right | ||
GRNT | Written decision to grant | ||
FPAY | Annual fee payment |
Payment date: 20131220 Year of fee payment: 4 |
|
FPAY | Annual fee payment |
Payment date: 20141222 Year of fee payment: 5 |
|
FPAY | Annual fee payment |
Payment date: 20151222 Year of fee payment: 6 |
|
FPAY | Annual fee payment |
Payment date: 20161222 Year of fee payment: 7 |
|
FPAY | Annual fee payment |
Payment date: 20171219 Year of fee payment: 8 |
|
FPAY | Annual fee payment |
Payment date: 20191219 Year of fee payment: 10 |