Summary of the invention
For solving the deficiencies in the prior art, the object of the present invention is to provide a kind of effectively rapidly to the method that the optimum angle of incidence of roof distributed photovoltaic system calculates.
In order to realize above-mentioned target, the present invention adopts following technical scheme:
The optimum angle of incidence computing method of a kind of roof distributed photovoltaic system, comprise the optimum angle of incidence of single photovoltaic module and the optimum angle of incidence of plural number row photovoltaic module, it is characterized in that: the optimum angle of incidence of described plural number row photovoltaic module, its computing formula distributes as follows according to the ratio that blocks of front-seat photovoltaic module to rear row's photovoltaic module:
Blocking ratio is
Blocking ratio is
Blocking ratio is
Blocking ratio is
Blocking ratio is
Blocking ratio is
Block ratio
now do not generate electricity, do not do to consider;
Wherein, parameter meaning is as follows: the rent on roof is m, and roof is long is a, and wide is b; Single photovoltaic panel area is long is k, and wide is t; Single photovoltaic module cost is n, single photovoltaic module be in optimum angle of incidence and shadow-free blocks time annual generated energy be Q
max; The inclination angle of photovoltaic arrays is α, and the block ratio of front-seat photovoltaic module to rear row's photovoltaic module is x; Photovoltaic module battery row is s; The cost of every kilowatt hour generated energy is y; η
αfor the generated energy Q under unobstructed different angle and the generated energy Q under unobstructed optimum angle of incidence
maxbetween ratio;
The by-pass diode of each described photovoltaic module is provided with 3; The described roof side of being flat-top; In described assembly, every block battery is all be in perfect condition.
The optimum angle of incidence computing method of aforesaid a kind of roof distributed photovoltaic system, is characterized in that: the optimum angle of incidence of described single photovoltaic module, adopt " solar radiation calculation procedure " to calculate optimum angle of incidence.
The beneficial effect that the present invention reaches: the present invention is when considering many factors, the optimum angle of incidence method for designing of a kind of roof distributed photovoltaic system of proposition; Output energy cost is minimum when ensureing photovoltaic system per kilowatt, the optimum angle of incidence of single plural number row photovoltaic module being calculated, the inclination angle of the best can be installed according to actual conditions, improve the generating efficiency of photovoltaic system.
Embodiment
Below in conjunction with accompanying drawing, the invention will be further described.Following examples only for technical scheme of the present invention is clearly described, and can not limit the scope of the invention with this.
For the generating efficiency of photovoltaic system, its mounted angle can be described as very important influence factor.Therefore the method for designing of the optimum angle of incidence of photovoltaic system is concerned to the development trend in photovoltaic industry future.
Now design the optimum angle of incidence computing method of a kind of roof distributed photovoltaic system, comprise the optimum angle of incidence of single photovoltaic module and the optimum angle of incidence of plural number row photovoltaic module.
The optimum angle of incidence of plural number row photovoltaic module, its computing formula distributes as follows according to the ratio that blocks of front-seat photovoltaic module to rear row's photovoltaic module:
Blocking ratio is
Blocking ratio is
Blocking ratio is
Blocking ratio is
Blocking ratio is
Blocking ratio is
Block ratio
now do not generate electricity, do not do to consider;
Wherein, parameter meaning is as follows: the rent on roof is m, and roof is long is a, and wide is b; Single photovoltaic panel area is long is k, and wide is t; Single photovoltaic module cost is n, single photovoltaic module be in optimum angle of incidence and shadow-free blocks time annual generated energy be Q
max; The inclination angle of photovoltaic arrays is α, and the block ratio of front-seat photovoltaic module to rear row's photovoltaic module is x; Photovoltaic module battery row is s; The cost of every kilowatt hour generated energy is y; η
αfor the generated energy Q under unobstructed different angle and the generated energy Q under unobstructed optimum angle of incidence
maxbetween ratio;
The by-pass diode of each photovoltaic module is provided with 3, and in assembly, every block battery is all be in perfect condition.The roof side of being flat-top.
The optimum angle of incidence of single photovoltaic module, adopts " solar radiation calculation procedure " to calculate optimum angle of incidence.Shanghai University Of Electric Power's software adopts C language to work out by Shanghai University Of Electric Power, is suitable as photovoltaic generating system designing and calculating aid.
Be described below in conjunction with two embodiments:
Represent Shanghai for Yangtze River Delta Area, single photovoltaic module optimum angle of incidence sees the following form, and gets 22 °;
Following table is the single photovoltaic module optimum angle of incidence statistical form of District of Shanghai:
η
αsee Fig. 2, and approximate meet function η
α=-8.65 × 10
-5× (α-22)
2+ 1;
Therefore, for the optimum angle of incidence of plural number row photovoltaic module, the cost y of every kilowatt hour generated energy can be listed and block the relational expression of ratio x and inclination alpha:
Block ratio
Block ratio
Block ratio
Block ratio
Block ratio
Block ratio
We select this roof of Fig. 3 as case, and Fig. 3 is roof, Hohai University, Changzhou library, can completion roof, and making long is 13400mm, and wide is 45850mm.
We select Trina Solar TSM-250P05A photovoltaic module as calculating sample, and power is 250W.The wide 992mm of the long 1650mm of this photovoltaic module, cell number is 6 × 9 pieces.Price is 1075 yuan, support price 200 yuan.Suppose that roof rent is 300 yuan of/square metre of years.
Therefore, when computing time is 20 years:
Blocking ratio is
Get
the then cost minimization y when α=8 ° as can be seen from Table 1
min=1.258956385 yuan/kilowatt hour.
Inclination alpha/° |
Often spend electric cost/unit |
Inclination alpha/° |
Often spend electric cost/unit |
0 |
1.280006305 |
45 |
1.779679031 |
1 |
1.2752369 |
46 |
1.817675346 |
2 |
1.271091657 |
47 |
1.857999028 |
3 |
1.26756232 |
48 |
1.900818732 |
4 |
1.264641955 |
49 |
1.946320423 |
5 |
1.262324925 |
50 |
1.994709568 |
6 |
1.260606859 |
51 |
2.046213659 |
7 |
1.259484639 |
52 |
2.101085141 |
8 |
1.258956385 |
53 |
2.159604821 |
9 |
1.259021451 |
54 |
2.22208585 |
10 |
1.259680421 |
55 |
2.288878385 |
11 |
1.260935116 |
56 |
2.360375092 |
12 |
1.262788603 |
57 |
2.437017646 |
13 |
1.265245216 |
58 |
2.519304458 |
14 |
1.26831057 |
59 |
2.607799909 |
15 |
1.271991599 |
60 |
2.703145439 |
16 |
1.276296584 |
61 |
2.806072935 |
17 |
1.2812352 |
62 |
2.917421009 |
18 |
1.286818561 |
63 |
3.038154894 |
19 |
1.29305928 |
64 |
3.169390954 |
20 |
1.299971532 |
65 |
3.312427095 |
21 |
1.307571131 |
66 |
3.46878079 |
22 |
1.315875606 |
67 |
3.640237054 |
23 |
1.324904303 |
68 |
3.828909523 |
24 |
1.334678484 |
69 |
4.037319018 |
25 |
1.345221445 |
70 |
4.268495717 |
26 |
1.356558647 |
71 |
4.526113619 |
27 |
1.36871786 |
72 |
4.814669902 |
28 |
1.381729325 |
73 |
5.13972762 |
29 |
1.395625934 |
74 |
5.508249492 |
30 |
1.410443425 |
75 |
5.929065296 |
31 |
1.426220611 |
76 |
6.413539663 |
32 |
1.442999619 |
77 |
6.976548218 |
33 |
1.460826169 |
78 |
7.637941943 |
34 |
1.47974988 |
79 |
8.424810468 |
35 |
1.499824607 |
80 |
9.37510358 |
36 |
1.521108828 |
81 |
10.54366738 |
37 |
1.543666064 |
82 |
12.01280791 |
38 |
1.567565362 |
83 |
13.91190993 |
39 |
1.592881825 |
84 |
16.45667498 |
40 |
1.619697216 |
85 |
20.03544633 |
41 |
1.648100634 |
86 |
25.42502246 |
42 |
1.678189279 |
87 |
34.43809992 |
43 |
1.710069314 |
88 |
52.5130484 |
44 |
1.743856846 |
89 |
106.842345 |
Table 1 blocks ratio
time, system inclination angle with often spend electric cost relation table
Blocking ratio is
Visible, when x increases, y increases, so should get
therefore, its result should be identical with table 1, the cost minimization y when α=8 °
min=1.258956385 yuan/kilowatt hour.
Blocking ratio is
Get
then as can be seen from Table 2, when α=9 °, y
min=1.3507984 yuan/kilowatt hour.
Inclination alpha/° |
Often spend electric cost/unit |
Inclination alpha/° |
Often spend electric cost/unit |
0 |
1.373862371 |
45 |
1.891629738 |
1 |
1.368736486 |
46 |
1.931193358 |
2 |
1.364267087 |
47 |
1.973178377 |
3 |
1.360445418 |
48 |
2.017759755 |
4 |
1.35726411 |
49 |
2.0651304 |
5 |
1.354717142 |
50 |
2.115503437 |
6 |
1.352799825 |
51 |
2.169114823 |
7 |
1.351508773 |
52 |
2.226226384 |
8 |
1.350841899 |
53 |
2.287129346 |
9 |
1.3507984 |
54 |
2.352148455 |
10 |
1.351378762 |
55 |
2.421646819 |
11 |
1.35258476 |
56 |
2.496031599 |
12 |
1.354419471 |
57 |
2.575760746 |
13 |
1.356887291 |
58 |
2.661351011 |
14 |
1.359993958 |
59 |
2.75338751 |
15 |
1.363746579 |
60 |
2.852535208 |
16 |
1.36815367 |
61 |
2.959552793 |
17 |
1.373225196 |
62 |
3.075309537 |
18 |
1.378972624 |
63 |
3.200805911 |
19 |
1.385408982 |
64 |
3.337198975 |
20 |
1.392548924 |
65 |
3.485833876 |
21 |
1.400408807 |
66 |
3.648283249 |
22 |
1.409006779 |
67 |
3.826396902 |
23 |
1.418362873 |
68 |
4.022365099 |
24 |
1.428499116 |
69 |
4.238799937 |
25 |
1.439439653 |
70 |
4.478841179 |
26 |
1.451210876 |
71 |
4.746295553 |
27 |
1.46384158 |
72 |
5.045822526 |
28 |
1.477363126 |
73 |
5.383185714 |
29 |
1.49180963 |
74 |
5.765598631 |
30 |
1.507218167 |
75 |
6.202208828 |
31 |
1.523629001 |
76 |
6.704789628 |
32 |
1.541085841 |
77 |
7.28875124 |
33 |
1.559636129 |
78 |
7.974657586 |
34 |
1.579331348 |
79 |
8.790570683 |
35 |
1.600227388 |
80 |
9.775801894 |
36 |
1.622384928 |
81 |
10.98716431 |
37 |
1.645869887 |
82 |
12.50991484 |
38 |
1.670753916 |
83 |
14.47807569 |
39 |
1.697114951 |
84 |
17.11507811 |
40 |
1.725037837 |
85 |
20.82317953 |
41 |
1.75461503 |
86 |
26.4070078 |
42 |
1.785947389 |
87 |
35.74419618 |
43 |
1.819145071 |
88 |
54.467927 |
44 |
1.854328544 |
89 |
110.7447463 |
Table 2 blocks ratio
time, system inclination angle with often spend electric cost relation table
Blocking ratio is
Visible, when x increases, y increases, so should get
its result should be identical with table 2, when α=9 °, and y
min=1.3507984 yuan/kilowatt hour.
Blocking ratio is
Get
then as can be seen from Table 3, when α=9 °, y
min=1.424211125 yuan/kilowatt hour.
Inclination alpha/° |
Often spend electric cost/unit |
Inclination alpha/° |
Often spend electric cost/unit |
0 |
1.45008035 |
45 |
1.944217782 |
1 |
1.444650994 |
46 |
1.98253536 |
2 |
1.439876594 |
47 |
2.023192348 |
3 |
1.435748208 |
48 |
2.066356295 |
4 |
1.432258253 |
49 |
2.112211914 |
5 |
1.429400472 |
50 |
2.16096324 |
6 |
1.427169911 |
51 |
2.21283613 |
7 |
1.425562895 |
52 |
2.268081157 |
8 |
1.424577015 |
53 |
2.326976982 |
9 |
1.424211125 |
54 |
2.389834287 |
10 |
1.424465333 |
55 |
2.457000388 |
11 |
1.425341008 |
56 |
2.528864673 |
12 |
1.426840789 |
57 |
2.605865022 |
13 |
1.428968601 |
58 |
2.688495453 |
14 |
1.431729674 |
59 |
2.77731524 |
15 |
1.435130571 |
60 |
2.872959869 |
16 |
1.439179223 |
61 |
2.976154275 |
17 |
1.443884972 |
62 |
3.087728914 |
18 |
1.449258613 |
63 |
3.208639424 |
19 |
1.455312454 |
64 |
3.339990841 |
20 |
1.46206038 |
65 |
3.483067634 |
21 |
1.469517924 |
66 |
3.639371267 |
22 |
1.477702347 |
67 |
3.810667583 |
23 |
1.486632735 |
68 |
3.999047135 |
24 |
1.496330097 |
69 |
4.207002775 |
25 |
1.506817485 |
70 |
4.437530555 |
26 |
1.518120119 |
71 |
4.69426253 |
27 |
1.530265533 |
72 |
4.981643869 |
28 |
1.543283732 |
73 |
5.305172531 |
29 |
1.557207371 |
74 |
5.671728877 |
30 |
1.572071952 |
75 |
6.090037203 |
31 |
1.587916043 |
76 |
6.571325168 |
32 |
1.604781523 |
77 |
7.130287671 |
33 |
1.622713852 |
78 |
7.786532819 |
34 |
1.641762377 |
79 |
8.566816753 |
35 |
1.661980665 |
80 |
9.508619595 |
36 |
1.683426885 |
81 |
10.66610562 |
37 |
1.706164229 |
82 |
12.12055389 |
38 |
1.73026138 |
83 |
13.99972994 |
39 |
1.755793048 |
84 |
16.51662965 |
40 |
1.78284056 |
85 |
20.05471674 |
41 |
1.811492536 |
86 |
25.38101761 |
42 |
1.841845637 |
87 |
34.28540791 |
43 |
1.87400543 |
88 |
52.137762 |
44 |
1.908087344 |
89 |
105.7880071 |
Table 3 blocks ratio
time, system inclination angle with often spend electric cost relation table
Blocking ratio is
Visible, when x increases, y increases, so should get
its result should be identical with table 3, when α=9 °, and y
min=1.424211125 yuan/kilowatt hour.
In sum, be 8 ° when getting inclination angle, and make to block ratio and be
time often spend electricity cost minimum, now the spacing of front and rear row photovoltaic module is 1.71m.
The present invention is when considering many factors, the optimum angle of incidence method for designing of a kind of roof distributed photovoltaic system of proposition; Output energy cost is minimum when ensureing photovoltaic system per kilowatt, the optimum angle of incidence of single plural number row photovoltaic module being calculated, the inclination angle of the best can be installed according to actual conditions, improve the generating efficiency of photovoltaic system.
The above is only the preferred embodiment of the present invention; it should be pointed out that for those skilled in the art, under the prerequisite not departing from the technology of the present invention principle; can also make some improvement and distortion, these improve and distortion also should be considered as protection scope of the present invention.