Frequency tripling transformer load test unit
Technical field
The present invention relates to a kind of load test device, relate in particular to a kind of frequency tripling transformer load test unit, belong to the electric power application, be applied to that power transformer dispatches from the factory, the load test device after handing-over, overhaul and the fault.
Background technology
According to the GB requirement, under the power frequency condition, carry out the transformer load test, test current should reach 50%~100%Ie.Because the on-the-spot needed high capacity power supply of satisfied test that is difficult to is about about 10% of test specimen rated capacity, the load test of electric company can only be 10%Ie and following carrying out at present.Even adopt capacitor shunt compensation mode, when the experiment power supply capacity reaches 100kVA, also can only carry out the 50%Ie load test of 66kV and following electric pressure transformer, but required compensation condenser capacity is very big, about 50 μ F, generally need about weight 50kg, tens in the capacitor of electric capacity 8 μ F, jumbo in addition pressure regulator and intermediate transformer, difficulty such as cause that transportation, carrying, wiring and scene are put, and the measurements and calculations error is also very big.
How can be under less power supply capacity conditions, it is convenient, fast and accurate that to carry out the transformer load test be the current engineering technology problem that needs to be resolved hurrily.
Summary of the invention
Patent of the present invention is at the problems referred to above, proposition utilizes 3 frequency multiplication generators as experiment power supply, by the low capacity compensator, realizes that electric current reaches the transformer load test unit of 50% Ie, solved in the prior art and can't under the small power supply capacity conditions, carry out the problem of transformer load test.
Technical scheme of the present invention is as follows:
3 frequency multiplication generators are as experiment power supply, 3 frequency multiplication generators are loaded on the tested transformer by pressure regulator, intermediate transformer, compensator is connected in parallel between intermediate transformer and the tested transformer, voltage table, reometer, power meter, frequency meter all are connected the former limit of tested transformer, and tested transformer is paid the limit short circuit.
Be parallel with control box between described 3 frequency multiplication generators and the pressure regulator.
Described pressure regulator is any in electric voltage regulator or the manual voltage regulator.
Described compensator is inductor or capacitor.
Advantageous effect of the present invention is as follows:
1, adopt 3 frequency multiplication generators as experiment power supply, rig-site utilization is strong, test current can reach 50%Ie and more than.
2, compensation capacity is about 1/9,100 experiment power supply capacity of compensation capacity under the power frequency condition; All reduce greatly compensator volume, weight and required test site etc.
3, test connection facility, the working site is easy to safety custody, saves human and material resources.
4, test current significantly improves, and test figure is accurate, and test findings has more using value.
5, by the present invention under the small power supply capacity conditions, can carry out transformer load test, measure the short-circuit impedance and the load loss of transformer, provide important parameter for identifying transformer quality, performance service condition and temperature rise test.
Description of drawings
Fig. 1 is a schematic diagram of the present invention.
Fig. 2 is a wiring diagram of the present invention.
Among the figure, T1-frequency tripling generator; The T2-pressure regulator; The T3-intermediate transformer; The tested transformer of T4-; Hz-hertz table; The A-reometer; The W-power meter; The V-voltage table; 1, control box, 2, compensator.
Embodiment
Below in conjunction with accompanying drawing, in conjunction with specific embodiments, it is as follows to describe the present invention.
Embodiment 1
3 frequency multiplication generators are parallel with control box as experiment power supply between 3 frequency multiplication generators and the pressure regulator; 3 frequency multiplication generators are loaded on the tested transformer by electric voltage regulator, intermediate transformer, capacitive compensator is connected in parallel between intermediate transformer and the tested transformer, voltage table, reometer, power meter, frequency meter are connected the former limit of tested transformer, and tested transformer is paid the limit short circuit.
Embodiment 2
Described pressure regulator is a manual voltage regulator, and compensator is the inductance compensation device, and other structure is with embodiment 1.
Technical indicator of the present invention is as follows:
1,3 frequencys multiplication generator-capacity 100kVA, frequency 150Hz, voltage 380kV;
2, capacitive compensator-many taps electric capacity;
3, inductance compensation device-many taps inductance;
4,50%~100%Ie of test current-test specimen rated current;
5, environment temperature--5~30
0C;
6, ambient humidity-50%-80%.
Principle of work of the present invention and process are as follows:
Utilize 3 frequency multiplication generators to obtain the single-phase experiment power supply of 150Hz, tested transformer is inserted in the test circuit, select inductance or electric capacity as reactive-load compensator, tested transformer is paid the limit short circuit, as shown in Figure 2, measure original edge voltage, electric current, power, frequency, obtain short-circuit impedance and load loss data, carry out corrected Calculation such as electric current, temperature, frequency again, obtain short-circuit impedance and load loss value under the power frequency condition.