US20180237338A1 - High Performance Fire Resistant Concrete Containing Hybrid Fibers and Nano Particles - Google Patents
High Performance Fire Resistant Concrete Containing Hybrid Fibers and Nano Particles Download PDFInfo
- Publication number
- US20180237338A1 US20180237338A1 US15/899,376 US201815899376A US2018237338A1 US 20180237338 A1 US20180237338 A1 US 20180237338A1 US 201815899376 A US201815899376 A US 201815899376A US 2018237338 A1 US2018237338 A1 US 2018237338A1
- Authority
- US
- United States
- Prior art keywords
- concrete
- fibers
- approximately
- fiber
- concrete composition
- Prior art date
- Legal status (The legal status is an assumption and is not a legal conclusion. Google has not performed a legal analysis and makes no representation as to the accuracy of the status listed.)
- Granted
Links
Images
Classifications
-
- C—CHEMISTRY; METALLURGY
- C04—CEMENTS; CONCRETE; ARTIFICIAL STONE; CERAMICS; REFRACTORIES
- C04B—LIME, MAGNESIA; SLAG; CEMENTS; COMPOSITIONS THEREOF, e.g. MORTARS, CONCRETE OR LIKE BUILDING MATERIALS; ARTIFICIAL STONE; CERAMICS; REFRACTORIES; TREATMENT OF NATURAL STONE
- C04B18/00—Use of agglomerated or waste materials or refuse as fillers for mortars, concrete or artificial stone; Treatment of agglomerated or waste materials or refuse, specially adapted to enhance their filling properties in mortars, concrete or artificial stone
- C04B18/04—Waste materials; Refuse
- C04B18/06—Combustion residues, e.g. purification products of smoke, fumes or exhaust gases
- C04B18/08—Flue dust, i.e. fly ash
-
- C—CHEMISTRY; METALLURGY
- C04—CEMENTS; CONCRETE; ARTIFICIAL STONE; CERAMICS; REFRACTORIES
- C04B—LIME, MAGNESIA; SLAG; CEMENTS; COMPOSITIONS THEREOF, e.g. MORTARS, CONCRETE OR LIKE BUILDING MATERIALS; ARTIFICIAL STONE; CERAMICS; REFRACTORIES; TREATMENT OF NATURAL STONE
- C04B28/00—Compositions of mortars, concrete or artificial stone, containing inorganic binders or the reaction product of an inorganic and an organic binder, e.g. polycarboxylate cements
- C04B28/02—Compositions of mortars, concrete or artificial stone, containing inorganic binders or the reaction product of an inorganic and an organic binder, e.g. polycarboxylate cements containing hydraulic cements other than calcium sulfates
- C04B28/04—Portland cements
-
- C—CHEMISTRY; METALLURGY
- C04—CEMENTS; CONCRETE; ARTIFICIAL STONE; CERAMICS; REFRACTORIES
- C04B—LIME, MAGNESIA; SLAG; CEMENTS; COMPOSITIONS THEREOF, e.g. MORTARS, CONCRETE OR LIKE BUILDING MATERIALS; ARTIFICIAL STONE; CERAMICS; REFRACTORIES; TREATMENT OF NATURAL STONE
- C04B14/00—Use of inorganic materials as fillers, e.g. pigments, for mortars, concrete or artificial stone; Treatment of inorganic materials specially adapted to enhance their filling properties in mortars, concrete or artificial stone
- C04B14/02—Granular materials, e.g. microballoons
- C04B14/022—Carbon
- C04B14/026—Carbon of particular shape, e.g. nanotubes
-
- C—CHEMISTRY; METALLURGY
- C04—CEMENTS; CONCRETE; ARTIFICIAL STONE; CERAMICS; REFRACTORIES
- C04B—LIME, MAGNESIA; SLAG; CEMENTS; COMPOSITIONS THEREOF, e.g. MORTARS, CONCRETE OR LIKE BUILDING MATERIALS; ARTIFICIAL STONE; CERAMICS; REFRACTORIES; TREATMENT OF NATURAL STONE
- C04B14/00—Use of inorganic materials as fillers, e.g. pigments, for mortars, concrete or artificial stone; Treatment of inorganic materials specially adapted to enhance their filling properties in mortars, concrete or artificial stone
- C04B14/38—Fibrous materials; Whiskers
- C04B14/48—Metal
-
- C—CHEMISTRY; METALLURGY
- C04—CEMENTS; CONCRETE; ARTIFICIAL STONE; CERAMICS; REFRACTORIES
- C04B—LIME, MAGNESIA; SLAG; CEMENTS; COMPOSITIONS THEREOF, e.g. MORTARS, CONCRETE OR LIKE BUILDING MATERIALS; ARTIFICIAL STONE; CERAMICS; REFRACTORIES; TREATMENT OF NATURAL STONE
- C04B16/00—Use of organic materials as fillers, e.g. pigments, for mortars, concrete or artificial stone; Treatment of organic materials specially adapted to enhance their filling properties in mortars, concrete or artificial stone
- C04B16/04—Macromolecular compounds
- C04B16/06—Macromolecular compounds fibrous
- C04B16/0616—Macromolecular compounds fibrous from polymers obtained by reactions only involving carbon-to-carbon unsaturated bonds
- C04B16/0625—Polyalkenes, e.g. polyethylene
-
- C—CHEMISTRY; METALLURGY
- C04—CEMENTS; CONCRETE; ARTIFICIAL STONE; CERAMICS; REFRACTORIES
- C04B—LIME, MAGNESIA; SLAG; CEMENTS; COMPOSITIONS THEREOF, e.g. MORTARS, CONCRETE OR LIKE BUILDING MATERIALS; ARTIFICIAL STONE; CERAMICS; REFRACTORIES; TREATMENT OF NATURAL STONE
- C04B18/00—Use of agglomerated or waste materials or refuse as fillers for mortars, concrete or artificial stone; Treatment of agglomerated or waste materials or refuse, specially adapted to enhance their filling properties in mortars, concrete or artificial stone
- C04B18/04—Waste materials; Refuse
- C04B18/14—Waste materials; Refuse from metallurgical processes
- C04B18/146—Silica fume
-
- C—CHEMISTRY; METALLURGY
- C04—CEMENTS; CONCRETE; ARTIFICIAL STONE; CERAMICS; REFRACTORIES
- C04B—LIME, MAGNESIA; SLAG; CEMENTS; COMPOSITIONS THEREOF, e.g. MORTARS, CONCRETE OR LIKE BUILDING MATERIALS; ARTIFICIAL STONE; CERAMICS; REFRACTORIES; TREATMENT OF NATURAL STONE
- C04B20/00—Use of materials as fillers for mortars, concrete or artificial stone according to more than one of groups C04B14/00 - C04B18/00 and characterised by shape or grain distribution; Treatment of materials according to more than one of the groups C04B14/00 - C04B18/00 specially adapted to enhance their filling properties in mortars, concrete or artificial stone; Expanding or defibrillating materials
- C04B20/0016—Granular materials, e.g. microballoons
- C04B20/002—Hollow or porous granular materials
- C04B20/0036—Microsized or nanosized
-
- C—CHEMISTRY; METALLURGY
- C04—CEMENTS; CONCRETE; ARTIFICIAL STONE; CERAMICS; REFRACTORIES
- C04B—LIME, MAGNESIA; SLAG; CEMENTS; COMPOSITIONS THEREOF, e.g. MORTARS, CONCRETE OR LIKE BUILDING MATERIALS; ARTIFICIAL STONE; CERAMICS; REFRACTORIES; TREATMENT OF NATURAL STONE
- C04B20/00—Use of materials as fillers for mortars, concrete or artificial stone according to more than one of groups C04B14/00 - C04B18/00 and characterised by shape or grain distribution; Treatment of materials according to more than one of the groups C04B14/00 - C04B18/00 specially adapted to enhance their filling properties in mortars, concrete or artificial stone; Expanding or defibrillating materials
- C04B20/10—Coating or impregnating
- C04B20/1055—Coating or impregnating with inorganic materials
- C04B20/1062—Metals
-
- C—CHEMISTRY; METALLURGY
- C04—CEMENTS; CONCRETE; ARTIFICIAL STONE; CERAMICS; REFRACTORIES
- C04B—LIME, MAGNESIA; SLAG; CEMENTS; COMPOSITIONS THEREOF, e.g. MORTARS, CONCRETE OR LIKE BUILDING MATERIALS; ARTIFICIAL STONE; CERAMICS; REFRACTORIES; TREATMENT OF NATURAL STONE
- C04B24/00—Use of organic materials as active ingredients for mortars, concrete or artificial stone, e.g. plasticisers
- C04B24/24—Macromolecular compounds
- C04B24/28—Macromolecular compounds obtained otherwise than by reactions only involving carbon-to-carbon unsaturated bonds
- C04B24/283—Polyesters
-
- C—CHEMISTRY; METALLURGY
- C04—CEMENTS; CONCRETE; ARTIFICIAL STONE; CERAMICS; REFRACTORIES
- C04B—LIME, MAGNESIA; SLAG; CEMENTS; COMPOSITIONS THEREOF, e.g. MORTARS, CONCRETE OR LIKE BUILDING MATERIALS; ARTIFICIAL STONE; CERAMICS; REFRACTORIES; TREATMENT OF NATURAL STONE
- C04B2111/00—Mortars, concrete or artificial stone or mixtures to prepare them, characterised by specific function, property or use
- C04B2111/00034—Physico-chemical characteristics of the mixtures
- C04B2111/00068—Mortar or concrete mixtures with an unusual water/cement ratio
-
- C—CHEMISTRY; METALLURGY
- C04—CEMENTS; CONCRETE; ARTIFICIAL STONE; CERAMICS; REFRACTORIES
- C04B—LIME, MAGNESIA; SLAG; CEMENTS; COMPOSITIONS THEREOF, e.g. MORTARS, CONCRETE OR LIKE BUILDING MATERIALS; ARTIFICIAL STONE; CERAMICS; REFRACTORIES; TREATMENT OF NATURAL STONE
- C04B2111/00—Mortars, concrete or artificial stone or mixtures to prepare them, characterised by specific function, property or use
- C04B2111/20—Resistance against chemical, physical or biological attack
- C04B2111/28—Fire resistance, i.e. materials resistant to accidental fires or high temperatures
-
- C—CHEMISTRY; METALLURGY
- C04—CEMENTS; CONCRETE; ARTIFICIAL STONE; CERAMICS; REFRACTORIES
- C04B—LIME, MAGNESIA; SLAG; CEMENTS; COMPOSITIONS THEREOF, e.g. MORTARS, CONCRETE OR LIKE BUILDING MATERIALS; ARTIFICIAL STONE; CERAMICS; REFRACTORIES; TREATMENT OF NATURAL STONE
- C04B2201/00—Mortars, concrete or artificial stone characterised by specific physical values
- C04B2201/50—Mortars, concrete or artificial stone characterised by specific physical values for the mechanical strength
- C04B2201/52—High compression strength concretes, i.e. with a compression strength higher than about 55 N/mm2, e.g. reactive powder concrete [RPC]
-
- Y—GENERAL TAGGING OF NEW TECHNOLOGICAL DEVELOPMENTS; GENERAL TAGGING OF CROSS-SECTIONAL TECHNOLOGIES SPANNING OVER SEVERAL SECTIONS OF THE IPC; TECHNICAL SUBJECTS COVERED BY FORMER USPC CROSS-REFERENCE ART COLLECTIONS [XRACs] AND DIGESTS
- Y02—TECHNOLOGIES OR APPLICATIONS FOR MITIGATION OR ADAPTATION AGAINST CLIMATE CHANGE
- Y02W—CLIMATE CHANGE MITIGATION TECHNOLOGIES RELATED TO WASTEWATER TREATMENT OR WASTE MANAGEMENT
- Y02W30/00—Technologies for solid waste management
- Y02W30/50—Reuse, recycling or recovery technologies
- Y02W30/91—Use of waste materials as fillers for mortars or concrete
Definitions
- the invention relates to high performance concrete compositions and, more particularly, to high performance concrete compositions with fibers and nanoparticles.
- High performance concrete is a high-strength, high-durability concrete used in roadway, bridge, tunnel, and high-rise construction.
- HPC features high compressive strength, high modulus of elasticity, chemical resistance, and compaction without segregation.
- inferior fire resistance of HPC is a major factor hindering its widespread adoption in buildings. Fibers may be used in an effort to improve the fire resistance of HPC, but the introduction of fibers has been demonstrated to substantially reduce the workability of the concrete. In applications where concrete must be pumped to high levels, loss of workability precludes the use of such fiber-containing concrete.
- the present invention relates to high performance concrete compositions that are both fire-resistant and possess high workability.
- the present invention provides a high-workability, fire-resistant, anti-spalling concrete composition having a slump value of at least approximately 150 mm, a fire-resistant period of at least 4 hours, a compressive strength of at least 120 MPa at room temperature and 20 MPa at 700° C.
- the composition includes cement, fly ash, silica fume, aggregate particles having a particle size D 90 of approximately 20 mm or less and superplasticizer.
- the composition includes fiber including steel fibers in an amount ranging between approximately 0.1% and approximately 0.4% by volume of the concrete composition and polypropylene fibers having a melting point of approximately 200° C. or less in an amount ranging between approximately 0.05% and 0.3% by volume of the concrete composition. Carbon nanotubes are also present in an amount ranging between approximately 0.1% and approximately 0.3% by volume of the concrete composition.
- FIG. 1 depicts steel fibers for use in HPC.
- FIG. 2 depicts failure modes for steel fiber pull-out test.
- FIG. 3 is a graph depicting bonding strength of steel fibers.
- FIG. 4 is a photograph of polypropylene fibers for use in HPC.
- FIG. 5A and FIG. 5B show polypropylene-loaded specimens before and after oven heating, respectively.
- FIGS. 6A and 6B show steel-fiber-loaded HPC specimens before and after oven heating, respectively.
- FIG. 7 depicts heating curves for oven-heated specimens.
- FIG. 8 depicts a spalled concrete sample.
- FIGS. 9A, 9B, 9C, and 9D depict physical conditions of HPC specimens following testing.
- FIG. 10 depicts the compressive strength of specimens at different temperatures.
- FIG. 11 depicts compressive strength and residual strength of various specimens after water curing, steam curing.
- FIG. 12 depicts temperature vs. time for various samples comprising nanoparticles.
- FIGS. 13A, 13B, and 13C depict the short concrete column specimens following a fire test.
- FIGS. 14A, 14B, and 14C depict temperature inside short concrete column specimens vs. time during a fire test.
- FIGS. 15A and 15B depict the long concrete column specimens after the fire test.
- FIG. 16 depicts vertical deformation of the long column vs. time.
- FIG. 17 depicts the vertical deformation rate of the long column vs. time.
- FIG. 18 shows the specific heat capacity of a binder paste of HPC.
- Concrete slump is a measure of concrete workability. Concrete slump measures the consistency of fresh concrete before it sets by forming it into a cone shape and measuring the cone subsidence, an indication of the ease with which concrete flows. As the HPC of the present invention will contain multiple fibers and have a strength ranging from grade C80 to C100 and slump above 150 mm, concrete formulations without fibers were developed having an objective slump of 180 mm.
- Superplasticizer refers to materials used to disperse cement agglomerates. Superplasticizers may be polycarboxylate-based polymers such as polycarboxylate ether-based polymers. A commercial polycarboxylate-based plasticizer, ADVA 189, from GCP Applied Technologies is used. As shown in Table 1, seven formulations of concrete were tried. The slump of fresh concrete was measured with a slump cone, following the relevant standards.
- f cu is the measured 28 days compressive strength of concrete
- f cu,k is the strength grade of concrete
- ⁇ is the specified standard deviation of measured compressive strength, i.e. 8 MPa.
- the 28 day compressive strengths of Grade C80, C90 and C100 concrete should be not below 93 MPa, 103 MPa and 113 MPa, respectively.
- the slump and compressive strength of concrete formulations without fiber are shown in Table 2. It can be seen that all the formulations showed an excellent workability, i.e. slump not below 180 mm.
- the strength of WF1, WF4 and WF5 reaches grade C80, the strength of WF2 and WF6 reaches grade C90, while the strength of WF3 and WF7 reaches grade 100.
- formulations WF1, WF2, WF3 and WF4 their total cementitious material contents (cement, fly ash and silica fume) are relatively high and even higher than the upper limit (maximum 600 kg/m 3 ) specified in Hong Kong code.
- formulations WF1 to WF4 may not lead to practical applications.
- Formulations WF5, WF6 and WF7, as grades C80, C90 and C100 concrete respectively, were selected for use with fiber and other additives.
- Polymer fibers can enhance the fire resistance of concrete.
- Polymer fibers with a relatively low melting point may delay the temperature increase of concrete due to their endothermic effect as they melt and decompose.
- addition of polymer fibers has adverse effects on the workability of the resultant concrete, making in unsuitable for applications where the concrete needs to be pumped, as in high-rise building construction.
- the present invention enhances dispersion of polymeric fibers in the concrete composition.
- fire resistance may be enhanced, that is, fire resistance is obtained with a smaller quantity of fibers.
- the present invention determined the dispersibility of polymer fibers depends on their surface properties, particularly water contact angle and surface energy. Therefore, various fiber surface treatments were examined to select the fibers with the highest dispersibility in the concrete composition.
- the untreated F1 fibers had the largest water contact angle, while the remaining fibers were all lower that F1. This indicates that surface treatments effectively reduce the water contact angle of polypropylene fibers.
- F3 (Sika) and F2 (Yonggu) fibers show relatively lower water contact angles (82.2° and 88.4°, hydrophilic) amongst six types of polypropylene fibers.
- steel fibers may enhance the fire resistance of high performance concrete.
- steel fibers can protect concrete from spalling when exposed to fire by controlling the cracks caused by differential expansion of concrete as it is heated.
- galvanized and copper-coated steel fibers are used. Since the bonding between steel fibers and concrete is important for controlling crack formation and propagation, research needs to be conducted to evaluate if zinc/copper coatings degrade the bonding between steel fibers and concrete.
- B0.55-3D and B0.92 (specimens from B0.92-3D, 4D and 5D). Fibers with same diameter and surface treatment but different end hooks were grouped together for the pull-out test. For each group, at least 12 specimens were tested.
- Table 7 and FIG. 3 show the bonding strength of the fibers. It can be seen that, regarding bare fibers and galvanized fibers, the measured bonding strength of steel fibers increased with increasing fiber diameter. The copper coated microfiber with the smallest diameter but the highest length/diameter (L/D) ratio showed the highest bonding strength. The reason may be that increasing the L/D ratio, i.e. relatively small diameter and larger surface area, may increase the bonding strength of steel fibers. Regarding galvanized and bare fibers with similar diameter, the measured bonding strength of galvanized fibers was larger than that of bare fibers. Therefore, zinc and copper coatings increased the bonding strength of steel fibers in concrete.
- FIG. 4 depicts the fibers of Table 3. Fiber amounts were proposed to be in a range of 0.04-0.3 vol %. To study the effects of fiber dosage, two dosages were employed for each type of polypropylene fiber for concrete preparation, i.e. 0.165 vol % (1.5 kg/m 3 ) and 0.3 vol % (2.73 kg/m 3 ).
- the formulation WF7 was employed as the base concrete formulation to prepare concrete containing polypropylene fibers.
- 10 groups of specimens were prepared, i.e. F1-L, F1-H, F2-L, F2-H, F3-L, F3-H, F4-L, F4-H, F6-L and F6-H, in which F1, F2, F3, F4 and F6 indicated the fiber type, L indicated the lower dosage of 0.165 vol % and H indicated the higher dosage of 0.3 vol %.
- Table 8 shows the composition of concrete containing 0.165 vol % and 0.3 vol % polypropylene fibers. The slump of fresh concrete was measured with a slump cone following the relevant Hong Kong standards.
- the fire resistance test was conducted by heating concrete specimens in an oven, and the fire resistance of concrete was evaluated in terms of the spalling degree and residual strength. Prior to heating in an oven, for each group, two cube specimens were dried in an oven (105° C.) for one week leading to almost 0% moisture content, while the other two cube specimens were dried in an environmental cabinet (26° C., RH 50%) for two weeks until a moisture content of about 2.6% was reached. The temperature in the oven rose from room temperature to 800° C. in the first 3 hours, and then was maintained at 800° C. for 4 more hours. The specimens in oven were then cooled down naturally and tested in compression.
- Table 9 shows the slump and 28 days compressive strength of concrete containing polypropylene fibers. It can be seen that, irrespective of fiber dosage and type, polypropylene fiber addition reduced the slump and strength of concrete. For all five types of fibers, both the slump and strength of concrete were reduced with increasing fiber dosage. The strength reduction of the concrete may be caused by more pores in concrete with lower workability. Regarding the effect of fiber length, it can be seen that increasing the fiber length increased the slump of the concrete, especially when the dosage of fibers is higher, but slightly reduced the strength. The reason may be that, at a specified dosage, the number of fibers added was reduced with increasing fiber length. However, the cross-sectional shape and fibrillation of polypropylene fiber had almost no effect on the slump and strength of concrete.
- thermocouples The temperatures of the oven and of the center points of concrete without (WF7) and with polypropylene fiber (F3-L and F3-H) were measured by thermocouples. Compared with the oven temperature, the temperature rising of concrete was delayed. This is because time is needed to transfer heat to the center of concrete to cause a temperature rise. It can be seen that when the temperature rose to about 180-200° C., the temperature of concrete increased slowly. This may be caused by the endothermic effect of dehydration (bonded water) of concrete. Moreover, compared to concrete without fiber, there was a time lag in the temperature curves of concrete containing fiber, indicating temperature rising of concrete was delayed when polypropylene fiber was added.
- FIGS. 5A and 5B show six specimens before and after oven heating, respectively.
- Table 10 shows the residual strength of all concrete specimens after oven heating. It can be seen that polypropylene fiber addition did not significantly degrade the strength of concrete. This is because the residual strength degradation of concrete subject to fire resistance testing is mainly caused by the thermal decomposition of hydration products in concrete, while polypropylene fiber has no effect on such decomposition, and the pores in concrete caused by polypropylene fiber thermal decomposition and evaporation would lead to a slight strength degradation. It was concluded that the lower dosage of polypropylene fibers is desirable and does not significantly degrade the fire resistance of the concrete. Concrete with different moisture contents showed similar strength reduction after heating.
- Table 11 shows the composition of concrete containing 0.2 vol % and 0.4 vol % steel fiber.
- the slump and 28 days compressive strength of concrete containing steel fibers were shown in Table 12. It can be seen that, irrespective of the type of steel fibers, the strength of concrete increased while the slump of concrete reduced with increasing fiber dosage. Fiber length has significant effects on the slump of concrete. 13 mm long steel fiber significantly reduced the slump; 30 mm long fiber slightly reduced slump while 60 mm long fiber slightly increased the slump. The reason may be that, at certain dosage, the number of steel fibers reduced with increasing fiber length, hence, the slump is reduced. However, the end hook configuration had almost no effect on the concrete slump. 13 mm long steel microfibers increased the strength, even though the slump reduced; 30 mm or 60 mm long fiber slightly reduced the strength at lower dosage while increased the strength at higher dosage.
- the concrete containing fibers with 5D end hooks showed higher compressive strength than that of concrete containing 3D end hooks.
- Strength increase due to steel fiber may be the result of bridging effect of steel fibers (crack opening control) and high tensile strength of the fibers.
- Table 13 shows the residual strength of all concrete specimens after oven heating. It can be seen that steel fibers increased the strength degradation of concrete. The reason may be that, steel fibers show larger expansion at elevated temperature than concrete, leading to some cracks in concrete. The fiber dosage and type had almost no effect on the residual strength of concrete.
- F3 and F4 Sika fiber mesh 150 fibers showed the best compatibility with concrete, and had similar effects on the strength of concrete, but F4 fiber addition would induce more slump reduction compared with F3 fiber.
- steel fiber copper coated steel microfiber showed the highest bonding strength in concrete and most significant effect on increasing the strength of concrete. Consequently, F3, i.e. 12 mm long Sika fiber mesh 150 polypropylene fiber, and C0.16, i.e. 13 mm long copper coated steel microfiber, were selected for use. Fiber loading was determined to be polypropylene fibers in a range of 0.05-0.3 vol % and steel fibers in a range of 0.1-0.4 vol %.
- Four concrete formulations containing hybrid fibers were developed based on the C100 (WF7) formulation, and their compositions are shown in Table 14.
- the formulation ID HF0.083/0.2 means the hybrid fiber concrete containing 0.083 vol % polypropylene fibers and 0.2 vol % steel fibers.
- 6 cubic specimens of 100 mm ⁇ 100 mm ⁇ 100 mm were cast for each group. All the specimens were removed from moulds one day after casting, and then wet-cured at 27° C. for 6 days and 27 days prior to test. Compression tests were carried out at the age of 7 days and 28 days with a loading rate of 0.6 MPa/s. The strength of each sample was the average of results of three specimens.
- the slump and compressive strength of concrete containing hybrid fibers are shown in Table 15.
- the elastic modulus of C80, C90 and C100 concrete containing and steel fibers with dosage of 0.165 vol % and 0.3 vol % was tested. The results are given in Table 17.
- the elastic modulus increases with concrete grade. The test values are higher than the recommended values in HK Concrete Code, which demonstrates that the addition of polypropylene and steel fibers does not weaken the elastic modulus of concrete.
- the compressive strength of the specimens were tested at room temperature, 200° C., 300° C., 400° C., 500° C., 600° C. and 700° C. They were heated inside the electric furnace at a constant heating rate of 5° C./min without preloading to attain the specified temperature. After achieving a hold-period of three hours, loading was applied to the specimens inside the electric furnace by an MTS hydraulic testing machine of 4600 kN loading capacity.
- the splitting strength of the inventive compositions is given in Table 19.
- the addition of polypropylene and steel fibers greatly improves the splitting strength of the concrete.
- C80, C90 and C100 concrete increased their splitting strength by 25.9%, 18.9%, and 12.4%, respectively.
- Both polypropylene fiber and steel fiber contribute to the increase in splitting tensile strength of concrete.
- a greater dosage of polypropylene or steel fibers is beneficial to the improvement on tensile performance of concrete.
- FIGS. 9A-9D show the physical conditions of specimens after test. As the temperature the specimens were exposed to increased, the color of the specimens changed from dark grey to light grey. The groups containing steel fibers and hybrid fibers were damaged slightly more than the other two groups.
- the compressive strength of specimens at different temperatures is shown in FIG. 10 .
- the compressive strength of the control concrete drops to 21% of that at room temperature when the temperature increases to 700° C.
- Steel fibers show a positive effect on improving the compressive strength of concrete under high temperature. The improvement becomes increasingly prominent with increasing temperatures. Steel fibers enhance the loading capacity of concrete by 60% at 700° C.
- polypropylene fibers exert little influence on the compressive strength. This is because steel fibers can retain their strength at elevated temperatures, while polypropylene fibers melt completely above 400° C.
- nanoparticles were mixed into concrete compositions to evaluate their influence on strength and thermal conductivity of HPC.
- Grade C100 HPC developed above was adopted as a control formula.
- Solid nano Mg(OH) 2 , polyphenylsilsesquioxane (“POSS”), carbon nanotube (“CNT”), and nano SiO 2 slurries were considered as the nanoparticle additions.
- the dosage of nanoparticles is approximately 0.1% to 0.3% of the volume of the concrete.
- Solid nano Mg(OH) 2 , POSS and CNT were dispersed into a slurry by an ultrasonic mixture before use. Two different dispersion methods were used.
- Method A is dispersing nanoparticles and water with mass ratio of 1:11.4 for 4 hours by 30% of rated power.
- Method B is dispersing nanoparticles, water and superplasticizer with a mass ratio of 1:11.4:1 for 0.5 hour by 70% of rated power (Table 20).
- the specimens were removed from the moulds 24 hours after casting, and were wet-cured at 27° C. for 28 days or steam-cured at 60° C. for 7 days. After curing, 6 specimens were subjected to compression tests for each group. The other specimens were heated in an electric furnace.
- a thermocouple was embedded in a concrete cube with a dimension of 100*100*100 mm. The temperature at the centroid of the cube and furnace was measured. The heating rate was 5° C./min and the holding period was 4 hours. All specimens remain intact after test. The residual compressive strength of specimens was also tested.
- FIGS. 11 and 12 The compressive strength and temperature inside the concrete including nanoparticles are shown in FIGS. 11 and 12 .
- POSS impeded the development of concrete strength and carbon nanoparticles are the only materials to survive the high-temperature environment; therefore, carbon nanotubes are selected as additives to the high performance concrete composition.
- Fire tests were conducted in an accredited laboratory to verify the fire resistance of the concrete compositions of the present invention according to international standards. As high strength concrete is mainly used in vertical elements (such as columns, walls, etc.) in practical applications, fire tests were conducted on column specimens.
- FIGS. 13A-13C Specimens after the fire test are shown in FIGS. 13A-13C . It can be seen C100C-CS400-45 concrete column spalled severely and exposed its reinforcements. The spalling weakened the cross section of the column and raised the temperature at the centroid of the control specimen ( FIG. 14A ). In contrast, the specimens containing polypropylene and steel fibers kept their integrity during the fire test, which demonstrates that the addition of polypropylene and steel fibers can effectively improve the fire resistance of high performance concrete. As shown in FIG. 14A , C100 concrete has higher thermal conductivity than C80 and C90 concrete due to its denser structure. The addition of carbon nanotubes improved the thermal conductivity of the concrete. The effect of cover thickness and cross section on temperature of reinforcement are shown in FIGS.
- Thick concrete cover contributes to hinder the transmission of heat. Large cross sections can absorb more heat and thus reduce the temperature of reinforcements.
- Depth and area ratio (the ratio of spalled area to original area) of spalled concrete is given in Table 22. The risk of spalling increases with concrete grade.
- C100 concrete specimens C100HF2-CS400-45 with 0.22 vol % of polypropylene fibers and 0.3 vol % of steel fibers possessed the best structural integrity. Its mix proportion was used to prepare a long HPC column for fire test with loading.
- T is the average furnace temperature and t is the time in minutes.
- the fire tests lasted 241 minutes.
- the long column specimen kept its integrity generally after fire test except for some slight spalling of the concrete cover at its front ( FIGS. 15A and 15B ).
- the spalling can be explained by the fact that when the column was cast horizontally, the heavier aggregate sank, while the lighter paste and water floated and gather on the surface of the column.
- the excessive water content in the surface layer of the column led to the spalling in fire.
- the depths of all spalled concrete did not exceed 11 mm, which is much less than the thickness of concrete cover, 45 mm. The slight spalling will have little effect on the temperature inside the column.
- FIGS. 16 and 17 Vertical deformation and deformation rate of the long column are shown in FIGS. 16 and 17 . Although subject to compression of 400 kN, the column exhibited positive elongation during the whole fire test. According to BS EN 1363-1, for vertically loaded elements, when their vertical contraction (negative elongation) reaches 1% of their initial height, or their rate of vertical contraction (negative elongation) reaches 0.3% of their initial height, the elements will be identified to lose their loading capacity in a fire test. Because the long HPC column maintained continuous expansion (i.e. positive elongation), it maintained its ability to support the test load during the test and passed the fire test.
- continuous expansion i.e. positive elongation
- HPC slabs with dimensions of 300 mm ⁇ 300 mm ⁇ 75 mm and four HPC prisms with dimensions of 70 mm ⁇ 70 mm ⁇ 285 mm were prepared for thermal conduction and thermal expansion tests, respectively.
- the prisms for thermal expansion test were first heated in an electric furnace to 40° C. 60° C., 80° C., and 100° C. respectively and maintained for half an hour. The prisms were then removed from the furnace and their length was measured immediately by a length comparator.
- the coefficient of linear expansion ⁇ l was obtained by the following equation,
- ⁇ l CRD T - CRD i G ⁇ ( T - T i )
- CRD i and CRD T are difference between the comparator reading of the specimen and the reference bar under initial temperature and temperature T, respectively;
- G is the gage length, 250 mm;
- T i is initial temperature, 25° C.
- a binder paste specimen of the HPC was prepared by grinding in a ball mill.
- the specific heat capacity of the binder paste was then tested by differential scanning calorimetry and shown in FIG. 18 . Harmathy established a formula to calculate the specific heat capacity of concrete as follows:
- c pt , c fa , and c ca are specific heat of cement paste, fine aggregate, and coarse aggregate, respectively.
- ⁇ pt , ⁇ fa , and ⁇ ca are mass fraction of cement paste, fine aggregate, and coarse aggregate in concrete, respectively. Harmathy's formula was modified to calculate the specific heat capacity of the HPC containing steel and polypropylene fibers as follow.
- c c ⁇ p c p + ⁇ sa c sa + ⁇ st c st + ⁇ sf c sf + ⁇ pf c pf
- c p , c sa , c st , c sf and c pf are specific heat of binder paste, sand, stone, steel fiber and polypropylene fiber at 25° C., respectively.
- c p is 1.207 J/(g° C.) according to test results shown in FIG. 18 .
- c sa , c st , c sf and c pf are 0.92, 0.82, 0.469, 1.68 J/(g° C.), respectively [2-4].
- ⁇ pt , ⁇ sa , ⁇ st , ⁇ sf and ⁇ pf are mass fraction of binder paste, sand, stone, steel fiber and polypropylene fiber in HPC, respectively.
Landscapes
- Chemical & Material Sciences (AREA)
- Engineering & Computer Science (AREA)
- Ceramic Engineering (AREA)
- Organic Chemistry (AREA)
- Materials Engineering (AREA)
- Structural Engineering (AREA)
- Civil Engineering (AREA)
- Chemical Kinetics & Catalysis (AREA)
- Inorganic Chemistry (AREA)
- Environmental & Geological Engineering (AREA)
- Nanotechnology (AREA)
- Combustion & Propulsion (AREA)
- Curing Cements, Concrete, And Artificial Stone (AREA)
Abstract
Description
- The present application claims priority from the U.S. provisional patent application Ser. No. 62/600,379 filed Feb. 22, 2017, and the disclosure of which is incorporated by references in its entirety.
- The invention relates to high performance concrete compositions and, more particularly, to high performance concrete compositions with fibers and nanoparticles.
- High performance concrete (HPC) is a high-strength, high-durability concrete used in roadway, bridge, tunnel, and high-rise construction. Typically, HPC features high compressive strength, high modulus of elasticity, chemical resistance, and compaction without segregation. However, the inferior fire resistance of HPC is a major factor hindering its widespread adoption in buildings. Fibers may be used in an effort to improve the fire resistance of HPC, but the introduction of fibers has been demonstrated to substantially reduce the workability of the concrete. In applications where concrete must be pumped to high levels, loss of workability precludes the use of such fiber-containing concrete. Thus, there is a need in the art for high performance concrete compositions that possess high workability in addition to being fire resistant.
- The present invention relates to high performance concrete compositions that are both fire-resistant and possess high workability. In one aspect, the present invention provides a high-workability, fire-resistant, anti-spalling concrete composition having a slump value of at least approximately 150 mm, a fire-resistant period of at least 4 hours, a compressive strength of at least 120 MPa at room temperature and 20 MPa at 700° C. The composition includes cement, fly ash, silica fume, aggregate particles having a particle size D90 of approximately 20 mm or less and superplasticizer. The composition includes fiber including steel fibers in an amount ranging between approximately 0.1% and approximately 0.4% by volume of the concrete composition and polypropylene fibers having a melting point of approximately 200° C. or less in an amount ranging between approximately 0.05% and 0.3% by volume of the concrete composition. Carbon nanotubes are also present in an amount ranging between approximately 0.1% and approximately 0.3% by volume of the concrete composition.
-
FIG. 1 depicts steel fibers for use in HPC. -
FIG. 2 depicts failure modes for steel fiber pull-out test. -
FIG. 3 is a graph depicting bonding strength of steel fibers. -
FIG. 4 is a photograph of polypropylene fibers for use in HPC. -
FIG. 5A andFIG. 5B show polypropylene-loaded specimens before and after oven heating, respectively. -
FIGS. 6A and 6B show steel-fiber-loaded HPC specimens before and after oven heating, respectively. -
FIG. 7 depicts heating curves for oven-heated specimens. -
FIG. 8 depicts a spalled concrete sample. -
FIGS. 9A, 9B, 9C, and 9D depict physical conditions of HPC specimens following testing. -
FIG. 10 depicts the compressive strength of specimens at different temperatures. -
FIG. 11 depicts compressive strength and residual strength of various specimens after water curing, steam curing. -
FIG. 12 depicts temperature vs. time for various samples comprising nanoparticles. -
FIGS. 13A, 13B, and 13C depict the short concrete column specimens following a fire test. -
FIGS. 14A, 14B, and 14C depict temperature inside short concrete column specimens vs. time during a fire test. -
FIGS. 15A and 15B depict the long concrete column specimens after the fire test. -
FIG. 16 depicts vertical deformation of the long column vs. time. -
FIG. 17 depicts the vertical deformation rate of the long column vs. time. -
FIG. 18 shows the specific heat capacity of a binder paste of HPC. - As discussed in the Background section above, fibers and other additives to high performance concrete may reduce workability of concrete. “Concrete slump” is a measure of concrete workability. Concrete slump measures the consistency of fresh concrete before it sets by forming it into a cone shape and measuring the cone subsidence, an indication of the ease with which concrete flows. As the HPC of the present invention will contain multiple fibers and have a strength ranging from grade C80 to C100 and slump above 150 mm, concrete formulations without fibers were developed having an objective slump of 180 mm.
-
TABLE 1 Formulations of concrete without fibers (kg/m3) Formulation ID WF1 WF2 WF3 WF4 WF5 WF6 WF7 Water 165 155 145 156 165 147 130 Cement 460 467 475 440 383 382 380 Fly ash 166 170 177 120 137 141 145 Silica fume 60 68 75 40 28 43 58 Coarse — — — 580 590 595 600 aggregate (20 mm) Coarse 930 925 918 320 330 365 400 aggregate (10 mm) Fine aggregate 619 615 610 700 720 680 640 Superplasticizer 10.6 12.5 14.6 17.0 7.6 10.5 19.0 Water 0.24 0.22 0.199 0.26 0.301 0.260 0.223 binder ratio - Ordinary Portland cement, fly ash, silica fume, coarse aggregates (10 mm and 20 mm, granite), fine aggregates (stone fines and/or natural river sand), superplasticizer and water were employed for concrete preparation. “Superplasticizer” as used herein, refers to materials used to disperse cement agglomerates. Superplasticizers may be polycarboxylate-based polymers such as polycarboxylate ether-based polymers. A commercial polycarboxylate-based plasticizer, ADVA 189, from GCP Applied Technologies is used. As shown in Table 1, seven formulations of concrete were tried. The slump of fresh concrete was measured with a slump cone, following the relevant standards. Six cubic specimens of 100 mm×100 mm×100 mm were cast for each formulation to measure the 7-day and 28-day compressive strength. All the specimens were removed from moulds one day after casting, and were then wet-cured. Compression tests were carried out at the age of 7 days and 28 days, respectively with a loading rate employed of 0.6 MPa/s according to BS EN 12390-3. The compressive strength was the average of results of three specimens.
- According to relevant Hong Kong code, the below formulation was used to define the strength grade of concrete:
-
f cu ≥f cu,k+1.645σ - Where fcu is the measured 28 days compressive strength of concrete, fcu,k is the strength grade of concrete, while σ is the specified standard deviation of measured compressive strength, i.e. 8 MPa. Following the formulation, for example, the 28 day compressive strengths of Grade C80, C90 and C100 concrete should be not below 93 MPa, 103 MPa and 113 MPa, respectively.
-
TABLE 2 Slump and compressive strength of concrete formulations without fiber Formulation WF1 WF2 WF3 WF4 WF5 WF6 WF7 Slump (mm) 210 200 210 200 180 180 180 Compressive 7 days 78.4 85 88.3 79.2 78 85.2 99.7 strength (MPa) 28 days 100.9 107.8 115.2 95.4 99.5 110.4 120 - The slump and compressive strength of concrete formulations without fiber are shown in Table 2. It can be seen that all the formulations showed an excellent workability, i.e. slump not below 180 mm. The strength of WF1, WF4 and WF5 reaches grade C80, the strength of WF2 and WF6 reaches grade C90, while the strength of WF3 and WF7 reaches
grade 100. However, regarding formulations WF1, WF2, WF3 and WF4, their total cementitious material contents (cement, fly ash and silica fume) are relatively high and even higher than the upper limit (maximum 600 kg/m3) specified in Hong Kong code. As the high cementitious material content may induce large hydration heat and shrinkage leading to cracks in concrete elements, formulations WF1 to WF4 may not lead to practical applications. Formulations WF5, WF6 and WF7, as grades C80, C90 and C100 concrete respectively, were selected for use with fiber and other additives. - To develop a fire-resistant HPC composition with high workability, the effects of various additives were evaluated. Polymer fibers can enhance the fire resistance of concrete. Polymer fibers with a relatively low melting point may delay the temperature increase of concrete due to their endothermic effect as they melt and decompose. In addition, they enhance fire resistance by providing a path inside the concrete structure for moisture evaporation. Such moisture-evaporation pathways may prevent concrete from spalling caused by vapor build-up in the structure. However, addition of polymer fibers has adverse effects on the workability of the resultant concrete, making in unsuitable for applications where the concrete needs to be pumped, as in high-rise building construction.
- In order to minimize the adverse effect of polymeric fiber additions, the present invention enhances dispersion of polymeric fibers in the concrete composition. In addition to improving the workability of the concrete, fire resistance may be enhanced, that is, fire resistance is obtained with a smaller quantity of fibers. The present invention determined the dispersibility of polymer fibers depends on their surface properties, particularly water contact angle and surface energy. Therefore, various fiber surface treatments were examined to select the fibers with the highest dispersibility in the concrete composition.
- Several commercial fibers were studied in the present invention to measure the water contact angle and the surface energy. The selection criteria are: the smaller the contact angle and the larger the surface energy, the better the compatibility between the fibers and concrete. Because polypropylene fibers have a melting temperature less than 200° C., they can enhance the anti-spalling properties of concrete exposed to fire. The fiber source and properties are listed in Table 3 while the water contact angle and surface energy of the fibers are listed in Table 4.
-
TABLE 3 Properties of Polypropylene Fibers Sika Sika Brand fibermesh fibermesh name Chenqi Yonggu 150-12 mm 150-6 mm Grace Tianyi ID F1 F2 F3 F4 F5 F6 Type Monofilament Monofilament Monofilament Monofilament Fibrillated Fibrillated Surface No Yes Yes Yes Yes Yes treatment Length 19 12 12 6 16 12 (mm) Diameter 31 30 31 31 42 42 (um) Cross Hollow Y shape Triangle Triangle Rectangle — section circle Density 910 (kg/m3) Tensile 460 592 330 330 — 604 strength (MPa) Elastic 3850 4479 3500 3500 — 4600 modulus (MPa) Melting 160 163 162 162 — 160 point (° C.) -
TABLE 4 Measured water contact angle and surface energy of treated and commercial fibers NaOH-S3 NaOH-S2 F1 bare F3 F2 treated F1 F5 treated F1 fiber Fiber (Sika) (Yonggu) fiber (Grace) fiber (Chengqi) Water contact 82.2 88.4 93 93.2 96.9 101 angle (Degree) Fiber F1 bare fiber NaOH-S2 F2 F3 NaOH-S3 F5 (Chengqi) treated F1 (Yonggu) (Sika) treated F1 (Grace) fiber fiber Surface energy 54.6 46.3 30.6 29.6 29 18.5 (mN/m) - According to the results shown in Table 4, the untreated F1 fibers had the largest water contact angle, while the remaining fibers were all lower that F1. This indicates that surface treatments effectively reduce the water contact angle of polypropylene fibers. F3 (Sika) and F2 (Yonggu) fibers show relatively lower water contact angles (82.2° and 88.4°, hydrophilic) amongst six types of polypropylene fibers.
- Typically, one way to enhance wetting is increasing the surface energy of the material through surface treatment. However, the results in Table 4 show that all the surface treatments reduce the water contact angle but reduce the surface energy of the polypropylene fibers. Therefore, the compatibility between polypropylene fibers and concrete was evaluated according to the measured water contact angle; F3 (Sika) and F2 (Yonggu) fibers were determined to have the highest compatibility with concrete.
- In addition to polypropylene fibers, the addition of steel fibers may enhance the fire resistance of high performance concrete. In particular, steel fibers can protect concrete from spalling when exposed to fire by controlling the cracks caused by differential expansion of concrete as it is heated. To reduce corrosion, galvanized and copper-coated steel fibers are used. Since the bonding between steel fibers and concrete is important for controlling crack formation and propagation, research needs to be conducted to evaluate if zinc/copper coatings degrade the bonding between steel fibers and concrete.
- In order to study the effects of coatings on the bonding between steel fibers and concrete, pull-out tests were conducted to measure the bonding strength of steel fiber within concrete.
- As shown in Table 5, eight types of commercial steel fibers with different geometries, including one copper coated microfiber, three types of galvanized steel fiber and four types of bare steel fibers were used. End hooks of fibers can enhance pull-out resistance as a result of mechanical locking, but have no effect to the bonding strength. When measuring the bonding strength of the steel fibers, both end hooks of galvanized and bare fibers were cut, and only the middle portions with a length of 13 mm were used. Five types of steel fibers were tested for bonding strength, including C0.16 (i.e. C0.16), G0.62 (i.e. G0.62-3D), G0.92 (specimens from G0.92-3D and 5D), B0.55 (i.e. B0.55-3D) and B0.92 (specimens from B0.92-3D, 4D and 5D). Fibers with same diameter and surface treatment but different end hooks were grouped together for the pull-out test. For each group, at least 12 specimens were tested.
- For the pull-out test, steel fibers were embedded in the center of a mortar block with dimensions of 9.7 mm×12.7 mm, and an embedding length of 5 mm. Mortar with 28-day compressive strength of 66 MPa was employed to prepare pull-out test specimens having the composition of Table 6. Cured samples were subjected to pulling at a load rate of 0.4 mm/minute with the bonding strength defined as the maximum load divided by circumferential fiber area.
-
TABLE 6 Composition of the mortar used for pull-out test specimen Component Cement Sand Water kg/m3 710 1208 307 - As shown in
FIG. 2 , there are three kinds of failure modes found for the pull out testing specimens, i.e. fiber debonding, wedge failure of the mortar, and fiber damage. Only fiber debonding was considered to be the valid failure mode for bonding strength measurement. For each group of specimens, at least 6 specimens showing debonding failure were used to obtain an average measured bonding strength. -
TABLE 7 Measured bonding strength Sample B0.55 G0.62 B0.92 G0.92 C0.16 Bonding Average 1.01 1.34 3.87 4.46 6.88 strength Standard Deviation 0.08 0.26 0.40 0.37 0.64 (MPa) Maximum 1.16 1.66 4.42 5.12 7.96 Minimum 0.91 1.04 3.29 4.01 5.97 - Table 7 and
FIG. 3 show the bonding strength of the fibers. It can be seen that, regarding bare fibers and galvanized fibers, the measured bonding strength of steel fibers increased with increasing fiber diameter. The copper coated microfiber with the smallest diameter but the highest length/diameter (L/D) ratio showed the highest bonding strength. The reason may be that increasing the L/D ratio, i.e. relatively small diameter and larger surface area, may increase the bonding strength of steel fibers. Regarding galvanized and bare fibers with similar diameter, the measured bonding strength of galvanized fibers was larger than that of bare fibers. Therefore, zinc and copper coatings increased the bonding strength of steel fibers in concrete. - In order to optimize the performance of concrete containing polypropylene fibers, studies were conducted in the present invention to investigate the effects of dosage, length, cross section and fibrillation of polypropylene fibers on the slump, strength and fire resistance of concrete.
FIG. 4 depicts the fibers of Table 3. Fiber amounts were proposed to be in a range of 0.04-0.3 vol %. To study the effects of fiber dosage, two dosages were employed for each type of polypropylene fiber for concrete preparation, i.e. 0.165 vol % (1.5 kg/m3) and 0.3 vol % (2.73 kg/m3). -
TABLE 8 Compositions of concrete containing 0.165 vol % and 0.3 vol % polypropylene fibers (kg/m3) Coarse PP fiber Fly Silica aggregate Fine PP dosage Water Cement ash fume (20 mm) (10 mm) aggregate Superplasticizer fiber 0.165 vol % 130 380 145 58 600 400 640 19 1.5 0.3 vol % 130 380 145 58 600 400 640 19 2.73 - The formulation WF7 was employed as the base concrete formulation to prepare concrete containing polypropylene fibers. In total, 10 groups of specimens were prepared, i.e. F1-L, F1-H, F2-L, F2-H, F3-L, F3-H, F4-L, F4-H, F6-L and F6-H, in which F1, F2, F3, F4 and F6 indicated the fiber type, L indicated the lower dosage of 0.165 vol % and H indicated the higher dosage of 0.3 vol %. Table 8 shows the composition of concrete containing 0.165 vol % and 0.3 vol % polypropylene fibers. The slump of fresh concrete was measured with a slump cone following the relevant Hong Kong standards. Seven cubic specimens of 100 mm×100 mm×100 mm were cast for each group, in which three cubes were used for 28 days compressive strength measurement and the remaining four cubes were used for fire resistance evaluation; two were completely dried and two were cured under 50% relative humidity (“RH”). All the specimens were removed from moulds one day after casting, and specimens for compression testing were then wet-cured at 27° C. for 27 days prior to test, while specimens for fire resistance test were cured in steam at 60° C. for 7 days (to accelerate the curing of concrete) prior to drying or curing. Compression tests were carried out at the age of 28 days of concrete using a compression testing machine and the loading rate employed was 0.6 MPa/s. The compressive strength of each sample was the average of results of three specimens. The fire resistance test was conducted by heating concrete specimens in an oven, and the fire resistance of concrete was evaluated in terms of the spalling degree and residual strength. Prior to heating in an oven, for each group, two cube specimens were dried in an oven (105° C.) for one week leading to almost 0% moisture content, while the other two cube specimens were dried in an environmental cabinet (26° C.,
RH 50%) for two weeks until a moisture content of about 2.6% was reached. The temperature in the oven rose from room temperature to 800° C. in the first 3 hours, and then was maintained at 800° C. for 4 more hours. The specimens in oven were then cooled down naturally and tested in compression. - Table 9 shows the slump and 28 days compressive strength of concrete containing polypropylene fibers. It can be seen that, irrespective of fiber dosage and type, polypropylene fiber addition reduced the slump and strength of concrete. For all five types of fibers, both the slump and strength of concrete were reduced with increasing fiber dosage. The strength reduction of the concrete may be caused by more pores in concrete with lower workability. Regarding the effect of fiber length, it can be seen that increasing the fiber length increased the slump of the concrete, especially when the dosage of fibers is higher, but slightly reduced the strength. The reason may be that, at a specified dosage, the number of fibers added was reduced with increasing fiber length. However, the cross-sectional shape and fibrillation of polypropylene fiber had almost no effect on the slump and strength of concrete.
-
TABLE 9 Slump and 28 days compressive strength of concrete containing polypropylene fibers Sample WF7 F1-L F1-H F2-L F2-H F3-L F3-H F4-L F4-H F6-L F6- H Slump 180 170 160 170 150 170 150 170 140 170 150 (mm) 28 days 120 109.7 108.3 115.6 108.1 115.2 108.2 115.2 113.7 114.8 110.4 compressive strength (MPa) - The temperatures of the oven and of the center points of concrete without (WF7) and with polypropylene fiber (F3-L and F3-H) were measured by thermocouples. Compared with the oven temperature, the temperature rising of concrete was delayed. This is because time is needed to transfer heat to the center of concrete to cause a temperature rise. It can be seen that when the temperature rose to about 180-200° C., the temperature of concrete increased slowly. This may be caused by the endothermic effect of dehydration (bonded water) of concrete. Moreover, compared to concrete without fiber, there was a time lag in the temperature curves of concrete containing fiber, indicating temperature rising of concrete was delayed when polypropylene fiber was added. This phenomenon was ascribed to the melting of polypropylene fibers and evaporation of moisture. However, the temperature curves of F3-L and F3-H were almost same due to the relatively small amounts of polypropylene fiber (for both 0.165 vol % and 0.3 vol %) compared with concrete materials. As it was expected that the effects of F1, F2, F4 and F6 polypropylene fibers on delaying temperature rising (mainly depending on the melting point and amount of polypropylene fibers) of concrete were similar to F3 polypropylene fiber, the temperature curves of concrete containing F1, F2, F4 and F6 fibers were hence not measured.
- After oven heating, almost no spalling is found in concrete specimens containing polypropylene fibers, irrespective of the moisture content. This phenomenon was also found for the concrete without fiber. As an example,
FIGS. 5A and 5B show six specimens before and after oven heating, respectively. Table 10 shows the residual strength of all concrete specimens after oven heating. It can be seen that polypropylene fiber addition did not significantly degrade the strength of concrete. This is because the residual strength degradation of concrete subject to fire resistance testing is mainly caused by the thermal decomposition of hydration products in concrete, while polypropylene fiber has no effect on such decomposition, and the pores in concrete caused by polypropylene fiber thermal decomposition and evaporation would lead to a slight strength degradation. It was concluded that the lower dosage of polypropylene fibers is desirable and does not significantly degrade the fire resistance of the concrete. Concrete with different moisture contents showed similar strength reduction after heating. -
TABLE 10 Residual compressive strength of concrete containing polypropylene fibers Sample WF7 F1-L F1-H F2-L F2-H F3-L F3-H F4-L F4-H F6-L F6-H 28 days compressive 120 109.7 108.3 115.6 108.1 115.2 108.2 115.2 113.7 114.8 110.4 strength (MPa) Residual 0% 29.8 30.8 27.1 29.3 24.6 27.9 29.6 28.9 26.9 28.9 29.9 strength moisture (MPa) content 2.6% 33.4 31 28 28 24.5 25.7 26.9 28.5 24 29.3 30.5 moisture content Reduction 0% 75 72 75 75 77 76 73 75 76 75 73 (%) moisture content 2.6% 72 72 74 76 77 78 75 75 79 74 72 moisture content - In order to optimize the performance of concrete containing steel fibers, studies were also conducted to investigate the effects of dosage, size and end hooks of steel fiber on the slump, strength, and fire resistance of concrete. To study the effects of fiber dosage, two dosages were employed for each type of steel fiber, 0.2 vol % (15.8 kg/m3) and 0.4 vol % (31.6 kg/m3). The formulation WF7 was employed as the base concrete formulation to prepare concrete containing steel fibers. Eight groups of specimens were prepared, i.e. C0.16-L, C0.16-H, G0.62-3D-L, G0.62-3D-H, G0.92-3D-L, G0.92-3D-H, G0.92-5D-L and G0.92-5D-H, in which C0.16, G0.62-3D, G0.92-3D and G0.92-5D indicated the fiber type, L indicated the lower dosage of 0.2 vol % and H indicated the higher dosage of 0.4 vol %. Table 11 shows the composition of concrete containing 0.2 vol % and 0.4 vol % steel fiber. When preparing concrete containing steel fibers, steel fibers were mixed with the powdery raw materials first and then water and superplasticizer were added followed by continuous mixing to eliminate fiber agglomeration. The specimen number and curing scheme, slump test scheme, compression test scheme and fire resistance test scheme for steel fiber study were substantially similar to those for polypropylene fibers. However, after heating, the residual strengths of concrete cured at 50% RH were not measured.
-
TABLE 11 Compositions of concrete containing 0.2 vol % and 0.4 vol % steel fibers (kg/m3) Steel fiber Fly Silica Coarse aggregate Fine Steel dosage Water Cement ash fume (20 mm) (10 mm) aggregate Superplasticizer fiber 0.2 vol % 130 380 145 58 600 400 640 19 15.8 0.4 vol % 130 380 145 58 600 400 640 19 31.6 - The slump and 28 days compressive strength of concrete containing steel fibers were shown in Table 12. It can be seen that, irrespective of the type of steel fibers, the strength of concrete increased while the slump of concrete reduced with increasing fiber dosage. Fiber length has significant effects on the slump of concrete. 13 mm long steel fiber significantly reduced the slump; 30 mm long fiber slightly reduced slump while 60 mm long fiber slightly increased the slump. The reason may be that, at certain dosage, the number of steel fibers reduced with increasing fiber length, hence, the slump is reduced. However, the end hook configuration had almost no effect on the concrete slump. 13 mm long steel microfibers increased the strength, even though the slump reduced; 30 mm or 60 mm long fiber slightly reduced the strength at lower dosage while increased the strength at higher dosage. The concrete containing fibers with 5D end hooks showed higher compressive strength than that of concrete containing 3D end hooks. Strength increase due to steel fiber may be the result of bridging effect of steel fibers (crack opening control) and high tensile strength of the fibers.
-
TABLE 12 Slump and 28 days compressive strength of concrete containing steel fibers G0.62- G0.62- G0.92- G0.92- G0.92- G0.92- WF7 C0.16-L C0.16-H 3D-L 3D-H 3D-L 3D-H 5D-L 5D-H Slump (mm) 180 160 140 180 160 200 180 200 180 28 days 120 134.4 139.4 119.2 125.7 117.2 120.1 122.9 123.8 compressive strength (MPa) -
TABLE 13 Residual strength of concrete containing steel fibers (completely dried specimens) G0.62- G0.62- G0.92- G0.92- G0.92- G0.92- WF7 C0.16-L C0.16-H 3D-L 3D-H 3D-L 3D-H 5D-L 5D-H 28 days 120 134.4 139.4 119.2 125.7 117.2 120.1 122.9 123.8 compressive strength (MPa) Residual 29.8 24.5 27.6 25.8 25.6 24.5 23.7 25.3 28.2 strength (MPa) Reduction 75 82 80 78 80 79 80 79 77 (%) - After oven heating, there was almost no spalling in the concrete containing steel fibers (as shown in
FIGS. 6A and 6B ) irrespective of the moisture content. Table 13 shows the residual strength of all concrete specimens after oven heating. It can be seen that steel fibers increased the strength degradation of concrete. The reason may be that, steel fibers show larger expansion at elevated temperature than concrete, leading to some cracks in concrete. The fiber dosage and type had almost no effect on the residual strength of concrete. - As set forth above, F3 and F4
Sika fiber mesh 150 fibers showed the best compatibility with concrete, and had similar effects on the strength of concrete, but F4 fiber addition would induce more slump reduction compared with F3 fiber. Regarding steel fiber, copper coated steel microfiber showed the highest bonding strength in concrete and most significant effect on increasing the strength of concrete. Consequently, F3, i.e. 12 mm longSika fiber mesh 150 polypropylene fiber, and C0.16, i.e. 13 mm long copper coated steel microfiber, were selected for use. Fiber loading was determined to be polypropylene fibers in a range of 0.05-0.3 vol % and steel fibers in a range of 0.1-0.4 vol %. Four concrete formulations containing hybrid fibers were developed based on the C100 (WF7) formulation, and their compositions are shown in Table 14. -
TABLE 14 Compositions of concrete containing hybrid fibers (kg/m3) ID HF0.165/ HF0.083/0.2 HF0.165/0.1 HF0.165/0.2 0.3 Water 130 130 130 130 Cement 380 380 380 380 Fly ash 145 145 145 145 Silica fume 58 58 58 58 Coarse 600 600 600 600 aggregate (20 mm) Coarse 400 400 400 400 aggregate (10 mm) Fine aggregate 640 640 640 640 Superplasticizer 19.0 19.0 19.0 19.0 Water binder 0.223 0.223 0.223 0.223 ratio PP fiber 0.75 1.5 1.5 1.5 Steel fiber 15.8 7.9 15.8 23.7 - Two polypropylene fiber dosages, i.e. 0.083 vol % and 0.165 vol %, and three steel fiber dosages, i.e. 0.1 vol %, 0.2 vol % and 0.3 vol %, were employed. The formulation ID HF0.083/0.2 means the hybrid fiber concrete containing 0.083 vol % polypropylene fibers and 0.2 vol % steel fibers. 6 cubic specimens of 100 mm×100 mm×100 mm were cast for each group. All the specimens were removed from moulds one day after casting, and then wet-cured at 27° C. for 6 days and 27 days prior to test. Compression tests were carried out at the age of 7 days and 28 days with a loading rate of 0.6 MPa/s. The strength of each sample was the average of results of three specimens. The slump and compressive strength of concrete containing hybrid fibers are shown in Table 15.
-
TABLE 15 Slump and compressive strength of C100 concrete with hybrid fibers HF0.083/ HF0.165/ 0.2 HF0.165/0.1 0.2 HF0.165/0.3 Slump (mm) 180 190 170 150 7-day compressive 97.1 96.5 96.6 97.9 strength (MPa) 28-day compressive 124.5 119.4 118.8 122.7 strength (MPa) - The results further proved that the slump of concrete decreased with increasing fiber content, and steel fibers and polypropylene fibers imposed different effects on the slump and strength of concrete. All four formulations had a slump above 150 mm and a 28-day compressive strength above 113 MPa, i.e. reaching the grade C100 level. The formulations HF0.083/0.2 and HF0.165/0.3 showed better performance in both 7-day and 28-day compressive strength. In consideration of beneficial effect of polypropylene fibers and steel fibers on the fire resistance of concrete, HF0.165/0.3 is adopted as the dosage of fibers for C80, C90 and C100 concrete. C80, C90 concrete including both fibers with a dosage of HF0.165/0.3 were prepared. Their 7-day and 28-day compressive strength is given in Table 16.
-
TABLE 16 Compressive strength of C80 and C90 concrete containing hybrid fibers C80 C90 hybrid fibers hybrid fibers concrete concrete 7-day compressive strength 80.7 90.0 (MPa) 28-day compressive strength 98.4 111.8 (MPa) - The fire resistance test results of concrete containing steel or polypropylene fibers showed that concrete without moisture (dried at 105° C.) and with 2.6% moisture content had no spalling after being oven heated for 4 hours. For concrete containing PP, steel and hybrid fibers, cubic concrete specimens were immersed in water for 28 days to a saturated condition and then heated. The heating rate is depicted in
FIG. 7 . All the specimens without fibers irrespective of concrete grade spalled seriously during the heating as shown inFIG. 8 . Specimens containing PP, steel and hybrid fibers kept their integrities in the test. This demonstrates the effectiveness of polypropylene and steel fiber in preventing spalling of concrete in fire. - The elastic modulus of C80, C90 and C100 concrete containing and steel fibers with dosage of 0.165 vol % and 0.3 vol % (i.e. HF0.165/0.3) was tested. The results are given in Table 17. The elastic modulus increases with concrete grade. The test values are higher than the recommended values in HK Concrete Code, which demonstrates that the addition of polypropylene and steel fibers does not weaken the elastic modulus of concrete.
-
TABLE 17 Elastic modulus of C80, C90 and C100 hybrid fibers concrete Concrete grade C80 C90 C100 Elastic modulus (GPa) 37.9 39.7 40.7 Recommended elastic modulus in 34.2 36.0 37.8 HK Concrete Code (GPa) - Splitting tensile tests were conducted on C80, C90 and C100 concrete at 28 days according to Hong Kong Construction Standard CS1-2010. Specimens used for splitting tests were cylinders with diameters of 100 mm and heights of 200 mm. In addition, compression tests on C100 HPC at elevated temperatures was conducted to evaluate the effect of steel fibers and PP fibers on fire resistance of HPC. Specimens with various fiber types were prepared (Table 18). Cylindrical specimens with a diameter of 75 mm and a height of 150 mm were cast. The specimens were removed from the moulds 24 hours after casting, and were wet-cured at 27° C. for 28 days. The temperatures considered in this test include room temperature, 200° C., 300° C., 400° C., 500° C., 600° C. and 700° C. A pair of specimens was tested at each temperature to determine the mechanical properties.
-
TABLE 18 Mix proportion of C100 HPC PP Hybrid Group Control Steel fiber fiber fiber Water 130 130 130 130 Cement 380 380 380 380 Fly ash 145 145 145 145 Silica fume 58 58 58 58 Coarse aggregate 600 600 600 600 (20 mm) Coarse aggregate 400 400 400 400 (10 mm) Crushed stone 256 256 256 256 River sand 384 384 384 384 Superplasticizer 15.5 15.5 15.5 15.5 PP fiber — — 1.5 1.5 Steel fiber — 23.7 — 23.7 - The compressive strength of the specimens were tested at room temperature, 200° C., 300° C., 400° C., 500° C., 600° C. and 700° C. They were heated inside the electric furnace at a constant heating rate of 5° C./min without preloading to attain the specified temperature. After achieving a hold-period of three hours, loading was applied to the specimens inside the electric furnace by an MTS hydraulic testing machine of 4600 kN loading capacity.
- The splitting strength of the inventive compositions is given in Table 19. The addition of polypropylene and steel fibers greatly improves the splitting strength of the concrete. Following the addition of 0.165 vol % of polypropylene fibers and 0.3% of steel fibers, C80, C90 and C100 concrete increased their splitting strength by 25.9%, 18.9%, and 12.4%, respectively. The lower the concrete grade is, the more the splitting strength increases. Both polypropylene fiber and steel fiber contribute to the increase in splitting tensile strength of concrete. In the fiber dosage range adopted in the present invention, a greater dosage of polypropylene or steel fibers is beneficial to the improvement on tensile performance of concrete.
-
TABLE 19 Splitting strength of HPC Concrete grade C80 C90 C100 Fiber dosage HF HF HF HF HF HF None 0.165/0.3 None 0.165/0.3 None 0.083/0.2 0.165/0.1 0.165/0.2 0.165/0.3 Splitting 5.29 6.66 5.70 6.78 6.11 6.42 6.43 6.75 6.87 strength (MPa) -
FIGS. 9A-9D show the physical conditions of specimens after test. As the temperature the specimens were exposed to increased, the color of the specimens changed from dark grey to light grey. The groups containing steel fibers and hybrid fibers were damaged slightly more than the other two groups. The compressive strength of specimens at different temperatures is shown inFIG. 10 . For all groups, there is a decline in compressive strength with increasing temperatures. The compressive strength of the control concrete drops to 21% of that at room temperature when the temperature increases to 700° C. Steel fibers show a positive effect on improving the compressive strength of concrete under high temperature. The improvement becomes increasingly prominent with increasing temperatures. Steel fibers enhance the loading capacity of concrete by 60% at 700° C. However, polypropylene fibers exert little influence on the compressive strength. This is because steel fibers can retain their strength at elevated temperatures, while polypropylene fibers melt completely above 400° C. - To further enhance the fire resistance and workability of the present high performance concrete, nanoparticles were mixed into concrete compositions to evaluate their influence on strength and thermal conductivity of HPC. Grade C100 HPC developed above was adopted as a control formula. Solid nano Mg(OH)2, polyphenylsilsesquioxane (“POSS”), carbon nanotube (“CNT”), and nano SiO2 slurries were considered as the nanoparticle additions. The dosage of nanoparticles is approximately 0.1% to 0.3% of the volume of the concrete. Solid nano Mg(OH)2, POSS and CNT were dispersed into a slurry by an ultrasonic mixture before use. Two different dispersion methods were used. Method A is dispersing nanoparticles and water with mass ratio of 1:11.4 for 4 hours by 30% of rated power. Method B is dispersing nanoparticles, water and superplasticizer with a mass ratio of 1:11.4:1 for 0.5 hour by 70% of rated power (Table 20). The specimens were removed from the moulds 24 hours after casting, and were wet-cured at 27° C. for 28 days or steam-cured at 60° C. for 7 days. After curing, 6 specimens were subjected to compression tests for each group. The other specimens were heated in an electric furnace. A thermocouple was embedded in a concrete cube with a dimension of 100*100*100 mm. The temperature at the centroid of the cube and furnace was measured. The heating rate was 5° C./min and the holding period was 4 hours. All specimens remain intact after test. The residual compressive strength of specimens was also tested.
-
TABLE 20 High performance concrete containing nanoparticles Nano particle Dispersion Group Material dosage Fiber dosage method Control Grade C100 — — — concrete POSS Grade C100 0.5% of Method A concrete + binder POSS mass Mg(OH)2 Grade C100 concrete + Mg(OH)2 CNT1 Grade C100 concrete + CNT CNT2 Grade C100 Method B concrete + CNT SiO2 Grade C100 — concrete + SiO2 slurry Hybrid Grade C100 — PP: 0.22 vol %, — concrete + Steel: 0.3 vol % polypropylene fiber + steel fiber - The compressive strength and temperature inside the concrete including nanoparticles are shown in
FIGS. 11 and 12 . POSS impeded the development of concrete strength and carbon nanoparticles are the only materials to survive the high-temperature environment; therefore, carbon nanotubes are selected as additives to the high performance concrete composition. - Fire tests were conducted in an accredited laboratory to verify the fire resistance of the concrete compositions of the present invention according to international standards. As high strength concrete is mainly used in vertical elements (such as columns, walls, etc.) in practical applications, fire tests were conducted on column specimens.
- Twelve short HPC columns varying in mix proportions, dimensions and cover thickness were prepared. The short columns had two cross-section dimensions, 250 mm×250 mm×1000 mm and 400 mm×400 mm×1000 mm. The thickness of concrete cover (from surface of specimen to stirrups) was 30 mm for the former, and 30 mm or 45 mm for the latter (Table 21). Here, C80HF-CS250-30 indicates the column made of C80 hybrid fibers-containing concrete with cross section of 250 mm×250 mm and cover thickness of 30 mm. C100C and C100CNT indicate C100 control concrete (without fiber) and C100 hybrid fibers-containing concrete with CNT dosage of 0.13 vol %, respectively. The difference between “HF” and “HF2” is that polypropylene dosage is 0.165 vol % in the former while 0.22 vol % in the latter. Fire tests on short concrete column specimens without loading were conducted in a horizontal furnace in Research Engineering Development Facade Consultants Limited. The fire tests lasted four hours according to BS EN 1363-1.
-
TABLE 21 Details of HPC columns for fire test Concrete Cross Cover Additive (with respect to No Specimen ID grade section Length thickness the volume of concrete) 1 C80HF-CS250-30 C80 250 mm × 1000 mm 30 mm 0.165 vol % 2 C90HF-CS250-30 C90 250 mm polypropylene fiber and 3 C100HF-CS250-30 C100 0.3 vol % steel fiber 4 C80HF-CS400-30 C80 400 mm × 30 mm 5 C80HF-CS400-45 400 mm 45 mm 6 C90HF-CS400-30 C90 30 mm 7 C90HF-CS400-45 45 mm 8 C100HF-CS400-30 C100 30 mm 9 C100HF-CS400-45 45 mm 10 C100C-CS400-45 45 mm None 11 C100HF2-CS400-45 0.22 vol % polypropylene fiber and 0.3 vol % steel fiber 12 C100CNT-CS400-45 0.165 vol % polypropylene fiber, 0.3 vol % steel fiber and 0.13 vol % CNT - Specimens after the fire test are shown in
FIGS. 13A-13C . It can be seen C100C-CS400-45 concrete column spalled severely and exposed its reinforcements. The spalling weakened the cross section of the column and raised the temperature at the centroid of the control specimen (FIG. 14A ). In contrast, the specimens containing polypropylene and steel fibers kept their integrity during the fire test, which demonstrates that the addition of polypropylene and steel fibers can effectively improve the fire resistance of high performance concrete. As shown inFIG. 14A , C100 concrete has higher thermal conductivity than C80 and C90 concrete due to its denser structure. The addition of carbon nanotubes improved the thermal conductivity of the concrete. The effect of cover thickness and cross section on temperature of reinforcement are shown inFIGS. 14B and 14C . Thick concrete cover contributes to hinder the transmission of heat. Large cross sections can absorb more heat and thus reduce the temperature of reinforcements. Depth and area ratio (the ratio of spalled area to original area) of spalled concrete is given in Table 22. The risk of spalling increases with concrete grade. Among the C100 concrete specimens, C100HF2-CS400-45 with 0.22 vol % of polypropylene fibers and 0.3 vol % of steel fibers possessed the best structural integrity. Its mix proportion was used to prepare a long HPC column for fire test with loading. -
TABLE 22 Depth and area ratio of spalled concrete in short columns Depth Ratio of spalled of spalled area No Specimen ID cover (mm) to original area 1 C80HF- 0 0 CS250-30 2 C90HF- 8.2 1% CS250-30 3 C100HF- 11.4 7% CS250-30 4 C80HF- 0 0 CS400-30 5 C80HF- 0 0 CS400-45 6 C90HF- 0 0 CS400-30 7 C90HF- 6.8 0.65% CS400-45 8 C100HF- 9.4 9.20% CS400-30 9 C100HF- 8.5 4.28% CS400-45 10 C100C- 55 90% CS400-45 11 C100HF2- 6 1.10% CS400-45 12 C100CNT- 14.5 6% CS400-45 - Fire testing with axial loading was performed on a full-scale HPC column to test its fire resistance. For this test, one long HPC column with dimensions of 400 mm wide by 400 mm deep by 3300 mm high and cover thickness of 45 mm was prepared. Reinforcements of the specimen consisted of eight main reinforcements with a diameter of 20 mm and eighteen stirrups with diameter of 10 mm. The spacing of stirrups was 200 mm in the middle part, and 150 mm at both ends of the specimen. Nine thermocouples were installed on the main reinforcements and at the center of cross section of the specimen before concrete casting. The concrete composition is given in Table 23. Measured 28-day compressive strength of the concrete was 122 MPa. Thickness of concrete cover was 45 mm from surface of specimen to stirrups.
-
TABLE 23 Mix proportion of C100N HPC (kg/m3) Water 130 Cement 380 PFA 145 Silica fume 58 Coarse aggregate (20 mm) 700 Coarse aggregate (10 mm) 230 Fine aggregate (Sand) 440 Fine aggregate (crushed stone) 300 Superplasticizer ADVA189 28.7 PP fiber 2 Steel fiber 23.7 - The fire test on the long concrete column specimens was conducted in a vertical furnace in Research Engineering Development Facade Consultants Limited. Vertical loading of 400 kN was applied on the top of specimen by two hydraulic jacks. The eccentricity of the loading was 6 mm. According to BS EN 1363-1, the temperature of furnace follows the relationship,
-
T=345 log10(8t+1)+20 - Here, T is the average furnace temperature and t is the time in minutes. The fire tests lasted 241 minutes.
- The long column specimen kept its integrity generally after fire test except for some slight spalling of the concrete cover at its front (
FIGS. 15A and 15B ). The spalling can be explained by the fact that when the column was cast horizontally, the heavier aggregate sank, while the lighter paste and water floated and gather on the surface of the column. The excessive water content in the surface layer of the column led to the spalling in fire. However, the depths of all spalled concrete did not exceed 11 mm, which is much less than the thickness of concrete cover, 45 mm. The slight spalling will have little effect on the temperature inside the column. - Vertical deformation and deformation rate of the long column are shown in
FIGS. 16 and 17 . Although subject to compression of 400 kN, the column exhibited positive elongation during the whole fire test. According to BS EN 1363-1, for vertically loaded elements, when their vertical contraction (negative elongation) reaches 1% of their initial height, or their rate of vertical contraction (negative elongation) reaches 0.3% of their initial height, the elements will be identified to lose their loading capacity in a fire test. Because the long HPC column maintained continuous expansion (i.e. positive elongation), it maintained its ability to support the test load during the test and passed the fire test. - The thermal parameters of the concrete compositions of the present invention were tested. HPC slabs with dimensions of 300 mm×300 mm×75 mm and four HPC prisms with dimensions of 70 mm×70 mm×285 mm were prepared for thermal conduction and thermal expansion tests, respectively.
- The prisms for thermal expansion test were first heated in an electric furnace to 40° C. 60° C., 80° C., and 100° C. respectively and maintained for half an hour. The prisms were then removed from the furnace and their length was measured immediately by a length comparator. The coefficient of linear expansion αl was obtained by the following equation,
-
- Here, CRDi and CRDT are difference between the comparator reading of the specimen and the reference bar under initial temperature and temperature T, respectively; G is the gage length, 250 mm; Ti is initial temperature, 25° C.
- A binder paste specimen of the HPC was prepared by grinding in a ball mill. The specific heat capacity of the binder paste was then tested by differential scanning calorimetry and shown in
FIG. 18 . Harmathy established a formula to calculate the specific heat capacity of concrete as follows: -
c c=ωpt c pt+ωfa c fa+ωca c ca - Here, cpt, cfa, and cca are specific heat of cement paste, fine aggregate, and coarse aggregate, respectively. ωpt, ωfa, and ωca are mass fraction of cement paste, fine aggregate, and coarse aggregate in concrete, respectively. Harmathy's formula was modified to calculate the specific heat capacity of the HPC containing steel and polypropylene fibers as follow.
-
c c=ωp c p+ωsa c sa+ωst c st+ωsf c sf+ωpf c pf - Here, cp, csa, cst, csf and cpf are specific heat of binder paste, sand, stone, steel fiber and polypropylene fiber at 25° C., respectively. cp is 1.207 J/(g° C.) according to test results shown in
FIG. 18 . csa, cst, csf and cpf are 0.92, 0.82, 0.469, 1.68 J/(g° C.), respectively [2-4]. ωpt, ωsa, ωst, ωsf and ωpf are mass fraction of binder paste, sand, stone, steel fiber and polypropylene fiber in HPC, respectively. - Calculated specific heat capacity of HPC is 0.953 J/(g° C.). Coefficient of heat conduction and coefficient of thermal expansion of HPC are given in Tables 24 and 25.
-
TABLE 24 Coefficient of heat conduction of HPC (W/mK) Measuring point A B C D E Average Specimen 1 2.4546 2.4658 2.6682 2.3914 2.2181 2.4396 Specimen 22.3347 2.4811 2.6649 2.6475 2.7123 2.5681 Specimen 32.4861 2.8969 2.2158 2.7493 2.8877 2.6472 Average 2.5516 -
TABLE 25 Coefficient of thermal expansion of HPC (×10−6/° C.) Temperature (° C.) 40 60 80 100 Specimen 19.600 9.370 9.450 9.230 Specimen 29.600 9.490 9.820 9.760 Specimen 39.867 9.710 9.890 9.710 Specimen 48.267 9.370 9.670 9.490 Average 9.333 9.490 9.710 9.550 - Various of the above-disclosed and other features and functions, or alternatives thereof, may be combined into many other different systems or applications. Various presently unforeseen or unanticipated alternatives, modifications, variations or improvements therein may be subsequently made by those skilled in the art, each of which is also intended to be encompassed by the disclosed embodiments.
Claims (11)
Priority Applications (3)
Application Number | Priority Date | Filing Date | Title |
---|---|---|---|
US15/899,376 US10071934B1 (en) | 2017-02-22 | 2018-02-20 | High performance fire resistant concrete containing hybrid fibers and nano particles |
CN201810153787.3A CN108455931B (en) | 2017-02-22 | 2018-02-22 | Refractory high performance concrete containing hybrid fibers and nanoparticles |
HK18113915.5A HK1254824A1 (en) | 2017-02-22 | 2018-10-31 | High performance fire resistant concrete containing hybrid fibers and nano particles |
Applications Claiming Priority (2)
Application Number | Priority Date | Filing Date | Title |
---|---|---|---|
US201762600379P | 2017-02-22 | 2017-02-22 | |
US15/899,376 US10071934B1 (en) | 2017-02-22 | 2018-02-20 | High performance fire resistant concrete containing hybrid fibers and nano particles |
Publications (2)
Publication Number | Publication Date |
---|---|
US20180237338A1 true US20180237338A1 (en) | 2018-08-23 |
US10071934B1 US10071934B1 (en) | 2018-09-11 |
Family
ID=63166143
Family Applications (1)
Application Number | Title | Priority Date | Filing Date |
---|---|---|---|
US15/899,376 Active US10071934B1 (en) | 2017-02-22 | 2018-02-20 | High performance fire resistant concrete containing hybrid fibers and nano particles |
Country Status (3)
Country | Link |
---|---|
US (1) | US10071934B1 (en) |
CN (1) | CN108455931B (en) |
HK (1) | HK1254824A1 (en) |
Cited By (9)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
CN111339655A (en) * | 2020-02-24 | 2020-06-26 | 浙江大学 | Method for prejudging elastic modulus change of carbon nano tube composite material |
IT201900002651A1 (en) * | 2019-02-25 | 2020-08-25 | Varicom Italia S R L | PREFABRICATED REINFORCED CONCRETE PLATES FOR THE CONSTRUCTION OF VERTICAL TAKE-OFF AIRCRAFT LAUNCH RAMPS AND RELATED INDUSTRIAL MANUFACTURING PROCESS |
CN113024192A (en) * | 2021-02-25 | 2021-06-25 | 河海大学 | Machine-made sand hydraulic concrete mixture and preparation method thereof |
CN113111410A (en) * | 2021-03-19 | 2021-07-13 | 西安建筑科技大学 | Method for establishing hybrid fiber concrete dynamic split tensile strength scale model |
CN113480256A (en) * | 2021-06-29 | 2021-10-08 | 成都宏基建材股份有限公司 | STC (super-high-temperature-coefficient) ultrahigh-toughness concrete with high working performance and production method thereof |
CN114349418A (en) * | 2021-12-16 | 2022-04-15 | 上海二十冶建设有限公司 | Fiber reinforced cement-based composite marble backing mortar and preparation method thereof |
CN114634320A (en) * | 2022-02-28 | 2022-06-17 | 青岛中建富兴商砼有限公司 | Heat-resistant and wear-resistant concrete and preparation method thereof |
CN115259720A (en) * | 2022-06-07 | 2022-11-01 | 中国建筑第七工程局有限公司 | Nano material adhesive fiber and preparation method thereof |
GB2589908B (en) * | 2019-12-12 | 2023-09-20 | Una Developments Ltd | A method for preparing a geoolymer composition |
Families Citing this family (1)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
CN115947570B (en) * | 2022-12-15 | 2024-04-02 | 哈尔滨工业大学(深圳) | Toughened corrosion-resistant concrete and preparation method thereof |
Family Cites Families (24)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
FR2804952B1 (en) * | 2000-02-11 | 2002-07-26 | Rhodia Chimie Sa | ULTRA HIGH PERFORMANCE FIRE RESISTANT CONCRETE COMPOSITION |
US6488762B1 (en) * | 2000-10-30 | 2002-12-03 | Advanced Materials Technologies, Llc | Composition of materials for use in cellular lightweight concrete and methods thereof |
FR2866330B1 (en) * | 2004-02-13 | 2006-08-18 | Eiffage Tp | ULTRA HIGH PERFORMANCE, AUTOPLACING CONCRETE, PROCESS FOR PREPARING THE SAME AND USE THEREOF |
JP2006016900A (en) * | 2004-07-02 | 2006-01-19 | Nippon Concrete Ind Co Ltd | Tunnel constructing segment |
US20080134942A1 (en) * | 2006-12-12 | 2008-06-12 | Matthew Brenner | Carbon Nanotube-Fiber Reinforced Cement And Concrete |
WO2009011480A1 (en) * | 2007-07-18 | 2009-01-22 | Daewoo Engineering & Construction Co., Ltd | Fire- resistant concrete containing nylon and polypropylene fibers |
US9365456B2 (en) * | 2008-02-08 | 2016-06-14 | Northwestern University | Highly-dispersed carbon nanotube-reinforced cement-based materials |
KR101008322B1 (en) * | 2008-12-26 | 2011-01-13 | 주식회사 삼표 | Spalling prevention material composed of fiber and powder, and high strength refractory concrete using the same |
JP5592307B2 (en) * | 2010-05-18 | 2014-09-17 | 大成建設株式会社 | Method for producing high-strength concrete and concrete member |
WO2012151657A1 (en) * | 2011-05-11 | 2012-11-15 | Shawcor Ltd. | Cementitious compositions for making anti-tamper concrete (atc) coatings and coated pipes made therefrom |
US9249053B2 (en) * | 2012-02-21 | 2016-02-02 | Nano And Advanced Materials Institute Limited | Composite wall panel with low thermal conductivity and sufficient strength for structural use |
JP5623679B2 (en) * | 2012-08-21 | 2014-11-12 | 大成建設株式会社 | Cementitious matrix and fiber-reinforced cementitious mixture |
US8951343B2 (en) * | 2012-08-31 | 2015-02-10 | Metna Co. | Ultra high performance concrete reinforced with low-cost graphite nanomaterials and microfibers, and method for production thereof |
US8877329B2 (en) * | 2012-09-25 | 2014-11-04 | Romeo Ilarian Ciuperca | High performance, highly energy efficient precast composite insulated concrete panels |
WO2014094183A1 (en) * | 2012-12-21 | 2014-06-26 | Empa Eidgenössische Materialprüfungs- Und Forschungsanstalt | Fire resistant concrete |
CN103910510A (en) * | 2012-12-31 | 2014-07-09 | 中交武汉港湾工程设计研究院有限公司 | Scouring-resistant wear-resistant ocean engineering concrete |
CN103601439A (en) * | 2013-10-29 | 2014-02-26 | 江苏名和集团有限公司 | C200 superhigh-strength high-performance composite concrete |
KR101568923B1 (en) * | 2014-01-16 | 2015-11-12 | 동신대학교산학협력단 | Lightweight and high toughness concrete composition for absorbing shock and method of manufacturing the wing-wall by using the composition |
CN103896527A (en) * | 2014-03-18 | 2014-07-02 | 上海罗洋新材料科技有限公司 | Lightweight high-strength cement based composite material |
CN104030634B (en) * | 2014-06-12 | 2016-07-13 | 杭州固华新材料科技有限公司 | A kind of high-strength and high ductility RPC of carbon-doped nanometer tube and preparation method thereof |
CN105272004A (en) * | 2015-10-28 | 2016-01-27 | 上海罗洋新材料科技有限公司 | Light-weight high-strength cement-based composite material |
CN106082874B (en) * | 2016-06-23 | 2018-09-11 | 黄河科技学院 | Shellproof explosion-proof brick of high-content hybrid fiber concrete and preparation method thereof |
CN106116343B (en) * | 2016-06-23 | 2019-01-18 | 黄河科技学院 | Shellproof explosion-proof brick of high-content gradation fiber recovery aggregate concrete and preparation method thereof |
US20180072938A1 (en) * | 2016-09-12 | 2018-03-15 | Baker Hughes Incorporated | Ductile cementing materials and the use thereof in high stress cementing applications |
-
2018
- 2018-02-20 US US15/899,376 patent/US10071934B1/en active Active
- 2018-02-22 CN CN201810153787.3A patent/CN108455931B/en active Active
- 2018-10-31 HK HK18113915.5A patent/HK1254824A1/en unknown
Cited By (9)
Publication number | Priority date | Publication date | Assignee | Title |
---|---|---|---|---|
IT201900002651A1 (en) * | 2019-02-25 | 2020-08-25 | Varicom Italia S R L | PREFABRICATED REINFORCED CONCRETE PLATES FOR THE CONSTRUCTION OF VERTICAL TAKE-OFF AIRCRAFT LAUNCH RAMPS AND RELATED INDUSTRIAL MANUFACTURING PROCESS |
GB2589908B (en) * | 2019-12-12 | 2023-09-20 | Una Developments Ltd | A method for preparing a geoolymer composition |
CN111339655A (en) * | 2020-02-24 | 2020-06-26 | 浙江大学 | Method for prejudging elastic modulus change of carbon nano tube composite material |
CN113024192A (en) * | 2021-02-25 | 2021-06-25 | 河海大学 | Machine-made sand hydraulic concrete mixture and preparation method thereof |
CN113111410A (en) * | 2021-03-19 | 2021-07-13 | 西安建筑科技大学 | Method for establishing hybrid fiber concrete dynamic split tensile strength scale model |
CN113480256A (en) * | 2021-06-29 | 2021-10-08 | 成都宏基建材股份有限公司 | STC (super-high-temperature-coefficient) ultrahigh-toughness concrete with high working performance and production method thereof |
CN114349418A (en) * | 2021-12-16 | 2022-04-15 | 上海二十冶建设有限公司 | Fiber reinforced cement-based composite marble backing mortar and preparation method thereof |
CN114634320A (en) * | 2022-02-28 | 2022-06-17 | 青岛中建富兴商砼有限公司 | Heat-resistant and wear-resistant concrete and preparation method thereof |
CN115259720A (en) * | 2022-06-07 | 2022-11-01 | 中国建筑第七工程局有限公司 | Nano material adhesive fiber and preparation method thereof |
Also Published As
Publication number | Publication date |
---|---|
CN108455931A (en) | 2018-08-28 |
US10071934B1 (en) | 2018-09-11 |
CN108455931B (en) | 2021-03-05 |
HK1254824A1 (en) | 2019-07-26 |
Similar Documents
Publication | Publication Date | Title |
---|---|---|
US10071934B1 (en) | High performance fire resistant concrete containing hybrid fibers and nano particles | |
Pedro et al. | Structural concrete with simultaneous incorporation of fine and coarse recycled concrete aggregates: Mechanical, durability and long-term properties | |
Devi et al. | Properties of concrete manufactured using steel slag | |
GHORPADE et al. | Strength and permeability characteristics of fiber reinforced high performance concrete with recycled aggregates | |
Ranjith et al. | Comparative study on durability properties of engineered cementitious composites with polypropylene fiber and glass fiber | |
Asayesh et al. | Evaluating fresh state, hardened State, thermal expansion and bond properties of geopolymers for the repairing of concrete pavements under restrained conditions | |
Ghiasvand et al. | Effect of grinding method and particle size distribution on long term properties of binary and ternary cements | |
Shanmugam et al. | Effect of fibers on strength and elastic properties of bagasse ash blended HPC composites | |
Prabhu et al. | Durability properties of fly ash and silica fume blended concrete for marine environment | |
Selvi et al. | Mechanical and durability properties of steel and polypropylene fibre reinforced concrete | |
Gupta | Development of high strength self compacting mortar with hybrid blend of polypropylene and steel fibers | |
Sounthararajan et al. | Evaluation of composite polypropylene fibre reinforced concrete | |
Kumar et al. | Study of effect of nano-silica on strength and durability characteristics of high volume fly ash concrete for pavement construction | |
Hwang et al. | Application of Fuller's ideal curve and error function to making high performance concrete using rice husk ash | |
KR101752919B1 (en) | Manufacturing Method for PVA Fiber Reinforced Cememt | |
Kandil et al. | Permeation properties of concretes incorporating fly ash and silica fume | |
Salam | Effect of steel fiber and silica fume on hardened concrete compressive and flexural strength | |
Guo et al. | Influence of the amount of steel fibers on fracture energy and drying shrinkage of HPFRCC | |
Pradeep et al. | Effect of pre-soaked light expanded clay aggregate on strength, durability and flexural behaviour of high-performance concrete | |
Singh et al. | Assessment of chemical exposures on ECC containing stone slurry powder | |
CN112608103B (en) | High-strength concrete for building construction | |
Noushini et al. | Rheological properties and compressive strength behaviour of polyvinyl alcohol fibre-reinforced concrete | |
Varghese et al. | Effect of nano-silica on the physical, mechanical and thermal properties of the natural rubber latex modified concrete | |
Kumar et al. | Performance of ultra fine GGBFS based coconut shell less dense concrete slabs under low-velocity impact | |
Ruben et al. | Elevated Temperature Effects on the Properties of Self Compacting Mortar Containing Nano Materials and Zircon Sand |
Legal Events
Date | Code | Title | Description |
---|---|---|---|
AS | Assignment |
Owner name: NANO AND ADVANCED MATERIALS INSTITUTE LIMITED, HON Free format text: ASSIGNMENT OF ASSIGNORS INTEREST;ASSIGNORS:FANG, SHUAI;ZHU, HONGGANG;LAM, YUE KEE;AND OTHERS;SIGNING DATES FROM 20180205 TO 20180207;REEL/FRAME:044971/0474 |
|
FEPP | Fee payment procedure |
Free format text: ENTITY STATUS SET TO UNDISCOUNTED (ORIGINAL EVENT CODE: BIG.); ENTITY STATUS OF PATENT OWNER: SMALL ENTITY |
|
FEPP | Fee payment procedure |
Free format text: ENTITY STATUS SET TO SMALL (ORIGINAL EVENT CODE: SMAL); ENTITY STATUS OF PATENT OWNER: SMALL ENTITY |
|
STCF | Information on status: patent grant |
Free format text: PATENTED CASE |
|
MAFP | Maintenance fee payment |
Free format text: PAYMENT OF MAINTENANCE FEE, 4TH YR, SMALL ENTITY (ORIGINAL EVENT CODE: M2551); ENTITY STATUS OF PATENT OWNER: SMALL ENTITY Year of fee payment: 4 |