Summary of the invention:
The utility model is for avoiding above-mentioned existing in prior technology weak point, a kind of band parallel connection gaps combination overvoltage protector is provided, solve the high residual voltage problem of zinc oxide, improving the safety in utilization of equipment.
The technical scheme that the utility model technical solution problem is adopted is:
The utility model serves as the protection branch road with zinc oxide or with the zinc oxide series gap; constitute the fabricated structure with mid point by many protection branch roads, described many protection branch roads comprise from mid point and connect each phase line protection branch road of A, B, C phase respectively and from the ground protection spur track of neutral earthing.
Design feature of the present utility model is that described ground protection spur track and/or each phase line protection branch road are set to the protection branch road RF with parallel connection gaps; the protection branch road RF of described band parallel connection gaps constitutes described zinc oxide R by valve block R1 and valve block R2 that series connection is provided with, on its valve block R2 parallel connection gaps F is set.
The impulse current that internal overvoltage produces generally can not surpass 5KA; Have only thunder-strike current from several kilo-amperes to kilo-amperes up to a hundred, just can produce very big impulse current.Therefore solve that residual voltage is too high to surpass apparatus insulated value, the heavy current impact residual voltage that solves exactly under the thunderbolt situation is too high, and internal overvoltage can not cause residual voltage too high.
The utility model is in the protection branch road; at partial oxidation zinc valve block parallel connection gaps is set; in case residual voltage surpasses its feasible value; parallel connection gaps forms discharge; this partial oxidation zinc valve block of short circuit; residual voltage value on the protection branch road only depends on the zinc oxide valve plate of remainder, thereby the residual voltage value reduces greatly.
Compared with the prior art, the beneficial effects of the utility model are embodied in:
1, the utility model is simple in structure, effective.
2, the utility model is widely used in the above extra high voltage system of 110KV, 3~66KV medium voltage network, and low-voltage power supply system.
Embodiment:
Shown in Fig. 1 (a), the protection branch road RF of band parallel connection gaps is set.
Shown in Fig. 1 (b), concrete structure is to constitute the zinc oxide R that protects in the branch road by valve block R1 and valve block R2 that series connection is provided with, and gap F is arranged in parallel on its valve block R2.Under the normal condition, in the protection branch road, bear operating voltage jointly, leakage current can be limited residual voltage to enough low numerical value by valve block R1 and valve block R2; And run into that the impulsive discharge electric current is excessive, when residual voltage surpasses due protection level, parallel connection gaps F discharge short circuit valve block R2, residual voltage will only be determined by valve block R1.
Embodiment 1: present embodiment is applicable to the extra high voltage system that 110KV is above.
The above extra high voltage system of 110KV is a solidly earthed neutral system, and the sound voltage rise height that powers on mutually is not more than 1.4 times during single-phase earthing, and the relaying protection meeting starts the tripping faulty line; Continue operation unlike system when the single-phase earthing of the non-directly system of neutral point, perfect phase voltage and raise and surpass line voltage.Therefore, there are not continuous operating voltage, 1mA reference voltage, impact the difficult problem that residual voltage is difficult to mate, thus need not on every protection branch road of combination overvoltage protector, to install series gap, to bring into play the advantage of zinc oxide better.
Fig. 2 (a) is applicable to the low area of large lightning current amplitude probability, can reduce cost.This protector has four protection branch roads; each bar protection branch road has the mid point that connects altogether; article four, the protection branch road is respectively: connect each phase line protection branch road of A, B, C phase respectively and from the ground protection spur track of neutral earthing from mid point; for the low area of large lightning current amplitude probability, only need in ground protection spur track, adopt the protection branch road RF4 of band parallel connection gaps.
Fig. 2 (b) and Fig. 2 (c) all are applicable to the high area of large lightning current amplitude probability.In Fig. 2 (b), four protection branch roads all adopt the protection branch road of band parallel connection gaps, comprise RF1, RF2, RF3 and RF4.Be in three phase line protection branch roads, to adopt band parallel connection gaps protection branch road respectively shown in Fig. 2 (c), comprise RF1, RF2 and RF3.
Embodiment 2: present embodiment is applicable to 3~66KV medium voltage network.
For 3~66KV neutral point non-direct grounding system, the insulation of circuit itself is too low, stops direct lightning strike even load onto lightning conducter, often still be difficult to avoid strikeing back, and the effect of reduction Lightning Over-voltage is also not obvious.So adopt neutral point indirect earthing, when taking place, single-phase earthing do not influence the symmetry of three-phase voltage, and system can continue operation.But be that non-fault phase-to-ground voltage can raise more than the line voltage; the continuous operating voltage that is connected to the zinc oxide overvoltage protection device of non-fault phase becomes line voltage by phase voltage; make continuous operating voltage, 1mA reference voltage, impact residual voltage be difficult to coupling; can cause the zinc oxide overvoltage protection device to be difficult to adjust like this; therefore will add series gap F and satisfy and protect requirement in the overvoltage protection branch road, the adding series gap makes that zinc oxide is not charged under the normal condition prolongs the zinc oxide life-span.
Fig. 3 (a) is applicable to the low area of large lightning current amplitude probability, can reduce cost.This protector has four protection branch roads equally, comprises three phase line protection branch roads and a ground protection spur track, for the low area of large lightning current amplitude probability, only need adopt the protection branch road RF4 of band parallel connection gaps in ground protection spur track.
Fig. 3 (b) and Fig. 3 (c) are applicable to the high area of large lightning current amplitude probability.Fig. 3 (b) is the protection branch road that adopts the band parallel connection gaps in four protection branch roads, comprises RF1, RF2, RF3 and RF4; Fig. 3 (c) is the protection branch road that adopts the band parallel connection gaps in three phase line protection branch roads, comprises RF1, RF2 and RF3.
Embodiment 3, and present embodiment is applicable to low-pressure system.
Low-voltage power supply system is the three-phase and four-line electric power system, is the maximum electric pressure of human being's production life contact, also is the electric pressure of non-electricity professional contact, for preventing accident of human electric shock's generation, therefore takes the three-phase and four-line electric power system.Protector has five at the protection branch road of this system, comprises three phase line protection branch roads, a ground protection spur track and a zero connection protection branch road, and wherein, the zero connection protection branch road has identical setting with ground protection spur track.
Structure shown in Fig. 4 (a) and Fig. 4 (d) is applicable to the area saving cost that large lightning current amplitude probability is low; Only adopt protection branch road RF4 and the RF5 that is with parallel connection gaps at ground protection spur track and zero connection protection branch road.
Structure is applicable to the high area of large lightning current amplitude probability shown in Fig. 4 (b), Fig. 4 (c), Fig. 4 (e) and Fig. 4 (f).Perhaps five protection branch roads all adopt the protection branch road of being with parallel connection gaps, comprise RF1, RF2, RF3, RF4 and RF5, perhaps only install parallel connection gaps additional in three phase lines protection branch roads, comprise RF1, RF2 and RF3.
In the present embodiment, each protects branch road can install additional also can not install series gap F additional.