[summary of the invention]
Fundamental purpose of the present invention is: a kind of transformer Buchholz relay shock test method is provided, comprises following process:
Frequency conversion test: relay is filled with transformer oil, connect with indicating device in trip-point, be placed in to add and shake on platform, vibration-testing frequency is 8~20Hz frequency sweep, X, Y, Z axis is each to be continued more than 1 minute, and acceleration is more than 0.25g, records the indication result of indicating device.
Above-mentioned transformer Buchholz relay shock test method, in embodiment wherein, each lasting 80 seconds of X, Y, Z axis test duration,
Above-mentioned transformer Buchholz relay shock test method, in embodiment wherein, testing acceleration is that 4g or testing acceleration are 2g.
Above-mentioned transformer Buchholz relay shock test method, in embodiment wherein, also comprise and determine frequency test: the transformer oil that relay is filled to clean, connect with indicating device at heavy gas action connection point, be placed in to add and shake on platform, carry out vibrational excitation with the test frequency of fixing in three directions of X, Y, Z axis, record the indication result of indicating device.
Above-mentioned transformer Buchholz relay shock test method, in embodiment wherein, it is fixed that the test duration is at least 1 minute frequently, described fixing test frequency adopts 100Hz, when acceleration amplitude is considered maximum on-the-spot no-load transformer input, 2 times of nargin of Buchholz relay vibration acceleration measured value, are 4g.
Above-mentioned transformer Buchholz relay shock test method, in embodiment wherein, described vibration-testing adopts sinusoidal wave, and described indicating device adopts multimeter.
By transformer Buchholz relay shock test method of the present invention, various Buchholz relay anti-seismic performance is carried out to testing evaluation, can provide theoretical support clearly for the type selecting of transformer Buchholz relay: in view of Buchholz relay is mounted on transformer, separately propose shockproof requirements or standard is irrational from the angle of Buchholz relay, need to propose shockproof requirements from the angle of whole voltage transformer system.When design of transformer, conventionally can resist eight grades more than seismic intensity, through consulting " GB/T17742-2008 ", it is 0.25g that eight grades of seismic intensity are converted to acceleration peak-peak, be far smaller than the earthquake resistant level of each Buchholz relay producer, visible, at present domestic standard " JB/T9647-1999 Buchholz relay " is too harsh to the shockproof requirements of Buchholz relay.Therefore,, in the type selecting of transformer Buchholz relay, as long as being not less than the shockproof requirements of main body transformer, its antidetonation parameter can meet production safety requirement.
[embodiment]
Below by specific embodiment, the present invention is described in further detail.
In order to study the anti-seismic performance of Buchholz relay, multiple Buchholz relay has been carried out to laboratory vibration-testing, it comprises following process.
Frequency conversion test
According to the vibration frequency under earthquake operating mode, the transformer oil that relay is filled to clean, connect with indicating device in trip-point, then shake on platform adding, make sinusoidal vibration test, be 8~20Hz frequency sweep by vibration-testing frequency selection purposes, each 80 seconds of X, Y, Z axis, acceleration is that 4g and 2g respectively do once, observes tested relay output node have or not moment shake or closing phenomenon, tripping operation contact is received to the indicating devices such as multimeter, check contact on-state.
Fixed test frequently
The transformer oil that relay is filled to clean, connect with multimeter at heavy gas action connection point, then shake on platform adding, make sinusoidal vibration test, shown in 3 directions of X, Y, Z axis, carry out vibrational excitation, test period is at least 1 minute, and test frequency is 100Hz, observes heavy gas contact action situation.When acceleration amplitude is considered maximum on-the-spot no-load transformer input, 2 times of nargin of Buchholz relay vibration acceleration measured value, are 4g.
Embodiment mono-
Tested person object: German TU DR80, bicylindrical body float-type, dry-reed contact
Its heavy gas operating principle is the connection baffle plate of the heavy gas float of oil stream impulsion in connecting pipe, connects baffle plate and drives heavy gas float to decline, and dry-reed contact in floating block is closed and connect heavy gas protective circuit.
Test result:
Frequency sweep test:
Fixed test frequently: pass through
Embodiment bis-
Tested person object: Britain P & B Weir 3DE/HF2, two float-types, mercury contact
The principle of its heavy gas action is that oil stream impacts the baffle plate on floating block, and baffle plate drives the mercury contact in floating block to connect heavy gas trip(ping) circuit.
Test result:
Frequency sweep test:
Fixed test frequently: pass through
Embodiment tri-
Tested person object: domestic QJ-80, spring catch is board-like, dry-reed contact
The principle of its heavy gas action is oil stream impact baffle plate, and baffle plate drives lower tongue tube inner contact to connect heavy gas trip(ping) circuit with magnet attraction.
Test result:
Frequency sweep test:
Fixed test frequently:
Due to the structure difference of Buchholz relay, therefore the earthquake resistant level of Buchholz relay does not have unified standard in the world, and the vibration standard that each Buchholz relay producer provides is all not identical:
Domestic Buchholz relay (being only applicable to the QJ series Buchholz relay of magnet baffle-type, dry-reed contact structure): in accordance with GB: 4~20Hz, acceleration is 4g;
Germany EMB (two float-ball types, dry-reed contact): 2~200Hz, acceleration is 2g;
Germany TU(bicylindrical body float-type, dry-reed contact): 5~15Hz, acceleration is 2g;
The two float-types of Britain P & B Weir(, mercury contact): 100Hz frequency is frequency surely, 0.25mm amplitude (peak is to peak), being scaled acceleration is 2g.
Known by the interpretation of result to the various embodiments described above:
(1) the action situation under the test of higher frequency band according to several relays, the anti-seismic performance that can judge common frequency excitation (50~100Hz) in the time bearing transformer operation or put into operation is all better, but owing to lacking corresponding actual measurement vibration data, when transformer is suffered to outside passing through property short circuit, the anti-seismic performance of Buchholz relay there is no method evaluation.
(2) in the frequency sweep vibration test result of low-frequency range, the performance that shows the anti-low frequency of Buchholz relay (8~20Hz) vibration of different structure is differentiated, magnet baffle-type is more much better than the Buchholz relay anti-seismic performance of float-type, be the oil flow surge due to the generation of transformer oil under Vibration Condition, the buoyancy that overcomes float is easier than the pulling force that overcomes spring; And for the Buchholz relay that is all float-type, the relay of mercury contact is more less better than the anti-seismic performance of the relay of dry-reed contact, this is because mercury exists certain mobility, in continuous vibration processes, mercury there will be rock and desultory connect or disconnect tripping operation control contact, so that in the unturned situation of float, also likely make the contact malfunction of tripping, and dry-reed contact does not exist the influence factor of this respect, therefore dry-reed contact is more winning than mercury contact aspect anti-seismic performance.
(3) in view of Buchholz relay is mounted on transformer, therefore can not from the angle of Buchholz relay, shockproof requirements or standard be proposed separately, need to shockproof requirements be proposed from the angle of whole voltage transformer system.When design of transformer, conventionally can resist eight grades more than seismic intensity, through consulting " GB/T17742-2008 ", it is 0.25g that eight grades of seismic intensity are converted to acceleration peak-peak, is far smaller than the earthquake resistant level of each Buchholz relay producer.Therefore, at present domestic standard " JB/T9647-1999 Buchholz relay " is too harsh to the shockproof requirements of Buchholz relay.Therefore, in the type selecting of transformer Buchholz relay, as long as its antidetonation parameter is not less than the requirement of main body transformer.
Above content is in conjunction with concrete preferred implementation further description made for the present invention, can not assert that specific embodiment of the invention is confined to these explanations.For general technical staff of the technical field of the invention, without departing from the inventive concept of the premise, can also make some simple deduction or replace, all should be considered as belonging to protection scope of the present invention.