A kind of load tapchanging on a large scale testing transformer
Technical field
The present invention relates to a kind of load tapchanging testing transformer on a large scale, belong to the transformer technology field.
Background technology
Development along with power technology, the change in voltage scope of power transformer is increasing, therefore the change in voltage area requirement of the testing transformer that power transformer is tested is also increasing, has to dispose the test requirements document that many testing transformers could satisfy the power transformer of different levels thereby caused.
In order to adapt to above requirement, realize that by transformer the demand of the testing transformer of voltage pressure regulation on a large scale put on schedule, and the manufacture difficulty of this transformer is: range of regulation is big, tap position is many, the impedance voltage of transformer significantly increases under the approaching several operating voltages of minimum tap (minimum operating voltage) of transformer, even reached 170%, can not satisfy normal transformer test work.
Summary of the invention
Purpose of the present invention solves the above-mentioned problems in the prior art exactly, provides that a kind of range of regulation is big, tap position is many, and the impedance voltage of transformer can satisfy the load tapchanging testing transformer of normal test requirements document on a large scale.
For realizing purpose of the present invention, technical solution of the present invention is: a kind of load tapchanging on a large scale testing transformer, and its every phase winding is made of low pressure winding, high pressure winding, pressure regulation winding from inside to outside successively; The low pressure winding adopts and axially draws; The high pressure winding is divided into high pressure the first half winding and high pressure the latter half winding, lifts one's head the width of cloth to drawing for its four; The pressure regulation winding is divided into identical upper and lower two parts; Connecting three between top outlet H4, the H2 of high pressure the first half winding and the latter half winding and end position outlet H3, H1 is in series-conversion off circuit tap changer DTC2 in parallel, under high pressure connecting three-phase between the end position outlet of half part winding and the pressure regulation winding does not have excitation tap change over switch DTC1, and positive and negative accent on-load tap changer OLTC is installed on the pressure regulation winding.
Above-mentioned described three be in series-terminal 4 of conversion off circuit tap changer DTC2 in parallel links to each other with high pressure the first half winding top outlet H4, the terminal 2 of DTC2 links to each other with high pressure the latter half winding top outlet H2, the terminal 3 of DTC2 links to each other with high pressure the first half winding end position outlet H3, and the joint 1 of DTC2 links to each other with high pressure the latter half winding end position outlet H1; The terminal 1 of no excitation tap change over switch DTC1 links to each other with high pressure the first half winding top outlet H4, and the terminal 2 of DTC1 links to each other with the terminal K of positive and negative accent on-load tap changer OLTC, and the terminal 3 of DTC1 links to each other with high pressure the latter half winding end position outlet H1; Each joint of positive and negative accent on-load tap changer OLTC links to each other with each lead-out wire of pressure regulation winding respectively.
Testing transformer high pressure winding of the present invention adopts one three and is in series-and conversion off circuit tap changer DTC2 in parallel realizes the series, parallel conversion of high pressure principal tapping, thereby high pressure principal tapping voltage is realized the variation of twice, realize that in conjunction with a positive and negative accent on-load tap changer OLTC testing transformer low pressure powers up the purpose of high tension voltage wide variation simultaneously.In order to solve the problem that approaching minimum tap position transformer impedance that this structure causes increases substantially, this testing transformer is introduced a three-phase does not again have excitation tap change over switch DTC1, when several tapping voltage at the approaching minimum tap position place of service test transformer, there is not excitation tap change over switch DTC1 with transformer high-voltage main winding complete resection by this three-phase, realize small voltage by pressure regulation winding and the operation of low pressure winding two windings, low-impedance output, well solved transformer near several operating voltages of minimum tap that is minimum operating voltage under the problem that increases substantially of the impedance voltage of transformer, satisfied normal test requirements document.The testing transformer that adopts the technology of the present invention to make just can realize smoothly that with one low pressure powers up, and high pressure is from the output on a large scale of 2598V~145492V, and has solved the big problem of several tap position transformer impedances at the approaching minimum tap place of transformer.It is simple in structure, and cost is low, and is easy to make.
Description of drawings
Fig. 1 is the distributed architecture schematic diagram between iron core, low pressure winding, high pressure winding and the pressure regulation winding of a phase wherein in the three-phase among the present invention;
Among the figure: 111 is unshakable in one's determination, 112 is the low pressure winding, and 114 is high pressure the first half winding, and 115 are pressure regulation the first half winding, 116 are pressure regulation the latter half winding, 117 is high pressure the latter half winding, and 113 is the axial outlet in low pressure winding upper end, and 118 is the axial outlet in low pressure winding bottom, H3 is the position outlet of high pressure the first half winding end, H4 is the top outlet of high pressure the first half winding, and H2 is the top outlet of high pressure the latter half winding, and H1 is the position outlet of high pressure the latter half winding end.
Fig. 2 is an elementary diagram of the present invention.
Among the figure: DTC2 three is in series-conversion off circuit tap changer in parallel, and DTC1 is that three-phase does not have excitation tap change over switch, and OLTC is positive and negative accent on-load tap changer.
Table 1 and table 2 do not have the explanation of excitation tap change over switch pressure regulation position for three being in series of describing in conjunction with Fig. 2-conversion off circuit tap changer in parallel, positive and negative accent on-load tap changer, three-phase.
Embodiment
The present invention will be further described below in conjunction with the drawings and specific embodiments.
That testing transformer as shown in Figure 1 and Figure 2, every phase A, B, C comprise respectively is unshakable in one's determination 111, low pressure winding 112, high pressure winding, pressure regulation winding, three are in series-conversion off circuit tap changer DTC2 in parallel, three-phase do not have excitation tap change over switch DTC1, positive and negative accent on-load tap changer OLTC and form.Every phase winding is followed successively by low pressure winding 112, high pressure winding and pressure regulation winding from inside to outside.Low pressure winding 112 adopts axially draws, and 113 is the axial outlet in low pressure winding upper end, and 118 is the axial outlet in low pressure winding bottom.The high pressure winding is divided into high pressure the first half winding 114 and high pressure the latter half winding 117, lift one's head the width of cloth to drawing for its four, high pressure the first half winding end position outlet H3, high pressure the first half winding top outlet H4, high pressure the latter half winding end position outlet H1, high pressure the latter half winding top outlet H2.The pressure regulation winding is divided into identical upper and lower two parts: pressure regulation the first half winding 115 and pressure regulation the latter half winding 116.Three be in series-terminal 4 of conversion off circuit tap changer DTC2 in parallel links to each other with high pressure the first half winding top outlet H4, the terminal 2 of DTC2 links to each other with high pressure the latter half winding top outlet H2, the terminal 3 of DTC2 links to each other with high pressure the first half winding end position outlet H3, and the joint 1 of DTC2 links to each other with high pressure the latter half winding end position outlet H1; The terminal 1 that three-phase does not have excitation tap change over switch DTC1 links to each other with high pressure the first half winding top outlet H4, the terminal 2 of DTC1 links to each other with the terminal K of positive and negative accent on-load tap changer OLTC, and the terminal 3 of DTC1 links to each other with high pressure the latter half winding end position outlet H1; Each joint of positive and negative accent on-load tap changer OLTC links to each other with each lead-out wire of pressure regulation winding respectively.
Table 1
Table 2
As shown in Table 1 and Table 2, when three among Fig. 2 be in series-conversion off circuit tap changer DTC2 operating contact in parallel is positioned at 2-3,3-0 coupled position, when no excitation tap change over switch DTC1 operating contact is positioned at the 2-3 coupled position, transformer high-voltage the first half winding 114 and high pressure the latter half winding 117 are in the series operation state, can realize the conversion of the high pressure 62354~145492V voltage in the table 1 by the positive and negative accent on-load tap changer OLTC among adjusting Fig. 2.When three among Fig. 2 be in series-when conversion off circuit tap changer DTC2 operating contact in parallel is positioned at 2-4,1-3 coupled position, three-phase and does not have excitation tap change over switch DTC1 operating contact and be positioned at the 2-3 coupled position, transformer high-voltage the first half winding 114 and high pressure the latter half winding 117 are in the parallel running state, can realize the conversion of the high pressure 25981~93531V voltage in the table 2 by the positive and negative accent on-load tap changer OLTC among adjusting Fig. 2.When three-phase among Fig. 2 does not have excitation tap change over switch DTC1 operating contact and is positioned at the 1-2 coupled position, no matter three are in series-and which position conversion off circuit tap changer DTC2 operating contact in parallel be in, the transformer high-voltage winding does not all participate in operation, thereby realized the state of pressure regulation winding and low pressure winding operation, by the positive and negative accent on-load tap changer OLTC among Fig. 2 being adjusted to+conversion of the high pressure 2598~23383V voltage of shelves in can realization table 2, solved the problem of transformer impedance drop sharp increase in this voltage range when introducing not that three-phase does not have excitation tap change over switch DTC1 among Fig. 2 simultaneously.
Certainly; the present invention also has other various embodiments; under the situation of the present invention's spirit and essence; those of ordinary skill in the art can make corresponding change and distortion according to the present invention; but these corresponding changes and distortion all should belong to the improvement of equivalent technologies, belong to the protection range of claim of the present invention.